280
21 MAINTENANCE AND INSPECTION
21.1 Daily Inspection
21.1
Daily Inspection
Daily inspection items
21.2
Periodic Inspection
Yearly or half-yearly inspection items
The following inspection should also be performed when equipment has been moved or modified or the wiring changed.
Item Inspection Item
Inspection Method
Criterion
Corrective action
1
GOT mounting status
Check for loose mounting
screws.
Securely mounted
Retighten screws within the specified
torque range
2
Connection
status
Loose terminal screws
Retighten screws with
screwdriver
Not loose
Retighten terminal screws
Proximate solderless
terminals
Visual check
Proper space
Correction
Loose connectors
Visual check
Not loose
Retighten connector fixing screws
3
Usage status
Foreign material
attachment
Visual check
No foreign matter sticking
Remove, clean
Item Inspection Item
Inspection Method
Criterion
Action
1
Surrounding
environment
Ambient temperature
Make measurement with
thermometer or hygrometer.
Measure corrosive gas.
0 to 50°C
For use in control panel, temperature
inside control panel is ambient
temperature
Ambient humidity
10 to 90%RH
Atmosphere
No corrosive gas
2
Power supply voltage check
24VDC Measure voltage
across terminals.
20.4 to 26.4VDC
Change supply power
3
Mounting
status
Looseness
Move module
Should be mounted firmly
Retighten screws
Foreign material
attachment
Visual check
No foreign matter sticking
Remove, clean
4
Connection
status
Loose terminal screws
Retighten screws with
screwdriver
Not loose
Retighten terminal screws
Proximate solderless
terminals
Visual check
Proper space
Correction
Loose connectors
Visual check
Not loose
Retighten connector fixing screws
Summary of Contents for GOT SIMPLE Series
Page 1: ...GOT SIMPLE Series User s Manual GS21 model ...
Page 2: ......
Page 20: ...18 MEMO ...
Page 24: ...22 1 OVERVIEW 1 1 Features MEMO ...
Page 34: ...32 3 SPECIFICATIONS 3 4 GOT Connector Specifications MEMO ...
Page 40: ...38 4 PART NAME 4 3 Bottom MEMO ...
Page 62: ...60 7 WIRING 7 2 Wiring Inside and Outside the Panel MEMO ...
Page 76: ...74 10 LANGUAGE SETTING LANGUAGE 10 1 Display language setting MEMO ...
Page 130: ...128 12 DISPLAY AND OPERATION SETTINGS GOT SET UP 12 7 IP Filter Setting MEMO ...
Page 160: ...158 14 CLOCK SETTINGS TIME SETTING AND DISPLAY 14 1 Time Setting and Display MEMO ...
Page 268: ...266 16 GOT SELF CHECK DEBUG 16 3 FX3U ENET ADP Communication Setting Function MEMO ...
Page 274: ...272 17 MAINTENANCE 17 3 Clean MEMO ...
Page 280: ...278 20 ERROR MESSAGE LIST MEMO ...
Page 296: ...294 22 TROUBLESHOOTING 22 1 GOT Restoration Sheets MEMO ...
Page 298: ...296 23 CONNECTION MEMO ...
Page 305: ...24 APPENDIX 24 1 External Dimensions 303 24 MEMO ...
Page 309: ......