12. CONNECTION TO TOSHIBA PLC
12.2 Serial Connection
RS422 connection diagram 3)
RS422 connection diagram 4)
RS422 connection diagram 5)
RS422 connection diagram 6)
(2) Precautions when preparing a cable
(a) Cable length
The length of the RS-422 cable must be 1km or
less.
(b) GOT side connector
For the GOT side connector, refer to the following.
1.4.1 GOT connector specifications
(c) TOSHIBA PLC side connector
Use the connector compatible with the TOSHIBA
PLC.
For details, refer to the TOSHIBA PLC user's
manual.
(3) Setting terminating resistors
(a) GOT side
• For GT16, GT15, GT12
Set the terminating resistor setting switch of the
GOT main unit to "Disable".
• For GT14, GT11
Set the terminating resistor selector to "330 ".
For details of terminating resistor settings, refer to
the following.
1.4.3 Terminating resistors of GOT
(b) TOSHIBA PLC side
When connecting an TOSHIBA PLC to a GOT, a
terminating resistor must be set to the TOSHIBA
PLC.
For the setting of the terminating resistor, refer to
the following manual.
TOSHIBA PLC user's Manual
• T2 (PU224), T2N, T3, T3H, model 3000 (S3)
Connect the terminating resistor (1/2W-120 )
across RXA and RXB.
• T2E, model 2000 (S2, S2T)
Short across the RXA and TERM terminals.
SDA1(TXD1+)
SDB1(TXD1-)
RDA1(RXD1+)
RDB1(RXD1-)
SDA2(TXD2+)
SDB2(TXD2-)
RDA2(RXD2+)
RDB2(RXD2-)
RSA(RTS+)
RSB(RTS-)
CSA(CTS+)
CSB(CTS-)
SG
NC
RXA
RXB
TXA
TXB
SG
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Shell
2
10
3
11
1
4
5
6
7
9
12
13
8
14
15
TOSHIBA PLC side
GOT side
R
GOT side
RDA
RDB
SDA
SDB
RSA
RSB
CSA
CSB
SG
FG
3
11
2
10
13
1
5
4
7
12
2
7
1
6
3
8
4
9
5
-
TXA
TXB
RXA
RXB
RTSB
FG
RTSA
CTSA
SG
CTSB
TOSHIBA PLC side
R
GOT side
RDA
RDB
SDA
SDB
RSA
RSB
CSA
CSB
SG
FG
2
7
1
6
3
8
4
9
5
-
TXA
TXB
RXA
RXB
SG
TERM
TOSHIBA PLC side
GOT side
RDA
RDB
SDA
SDB
RSA
RSB
CSA
CSB
SG
FG
3
11
2
10
8
2
7
1
6
3
8
4
9
5
-
TXA
TXB
RXA
RXB
SG
TOSHIBA PLC side
R
Summary of Contents for GOT 1000 Series
Page 2: ......
Page 76: ...1 46 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Page 78: ......
Page 114: ...2 36 2 CONNECTION TO IAI ROBOT CONTROLLER 2 7 Precautions ...
Page 232: ...5 18 5 CONNECTION TO OMRON TEMPERATURE CONTROLLER 5 7 Precautions ...
Page 254: ...6 22 6 CONNECTION TO KEYENCE PLC 6 4 Device Range that Can Be Set ...
Page 404: ...14 14 14 CONNECTION TO PANASONIC SERVO AMPLIFIER 14 7 Precautions ...
Page 432: ...REVISIONS 3 ...
Page 435: ......