5. CONNECTION TO OMRON TEMPERATURE CONTROLLER
5.4 GOT Side Settings
5.4 GOT Side Settings
5.4.1
Setting communication
interface (Communication
settings)
Set the channel of the equipment to be connected to the
GOT.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: OMRON
• Controller Type: OMRON THERMAC/INPANEL
NEO
• I/F: Interface to be used
• Driver: OMRON THERMAC/INPANEL NEO
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
5.4.2 Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
5.4.2
Communication detail settings
Make the settings according to the usage environment.
2.
3.
4.
Click!
Item
Description
Range
Transmission Speed
Set this item when change the
transmission speed used for
communication with the
connected equipment.
(Default: 9600bps)
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
Data Bit
Set this item when change the
data length used for
communication with the
connected equipment.
(Default: 7bits)
7bits/8bits
Stop Bit
Specify the stop bit length for
communications.
(Default: 2bits)
1bit/2bits
Parity
Specify whether or not to
perform a parity check, and
how it is performed during
communication.
(Default: Even)
None
Even
Odd
Retry
Set the number of retries to be
performed when a
communication error occurs.
(Default: 0time)
0 to 5times
Timeout Time
Set the time period for a
communication to time out.
(Default: 3sec)
3 to 30sec
Delay Time
Set this item to adjust the
transmission timing of the
communication request from
the GOT.
(Default: 2ms)
0 to 300 (ms)
Format
Select the communication
format.
(Default: 1)
format 1: only continuous
access
format 2: continuous and
random access
1/2
Summary of Contents for GOT 1000 Series
Page 2: ......
Page 76: ...1 46 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Page 78: ......
Page 114: ...2 36 2 CONNECTION TO IAI ROBOT CONTROLLER 2 7 Precautions ...
Page 232: ...5 18 5 CONNECTION TO OMRON TEMPERATURE CONTROLLER 5 7 Precautions ...
Page 254: ...6 22 6 CONNECTION TO KEYENCE PLC 6 4 Device Range that Can Be Set ...
Page 404: ...14 14 14 CONNECTION TO PANASONIC SERVO AMPLIFIER 14 7 Precautions ...
Page 432: ...REVISIONS 3 ...
Page 435: ......