3 - 50
3. CONNECTION TO AZBIL CONTROL EQUIPMENT
3.5 Control Equipment Side Setting
3.5.6
Connecting to DMC50
Communication settings
Make the communication settings by operating the
Smart Loader Package (SLP-D50/SLP-H21)of the
temperature controller.
*1
Adjust the settings with GOT settings.
*2
Set the module address using the rotary switch for module
address.
*3
Do not set to "0".
*4
Select the module address without overlapping with that of
other units.
Module address setting
Set the module address using the rotary switch for
module address.
3.5.7
Connecting to SDC45/46
Communication settings
Make the communication settings by operating the
Smart Loader Package (SLP-C45) of the temperature
controller.
*1
Adjust the settings with GOT settings.
*2
Set to CPL.
*3
Do not set to "0".
*4
Select the station address without overlapping with that of
other units.
*5
When using the interface converter CMC10L, set the
communication minimum response time to 3ms or more.
3.5.8
Connecting to CMS, CMF015
Communication settings
Make the communication settings by operating the key
of the control equipment.
*1
Adjust the settings with GOT settings.
*2
Do not set to "0".
*3
Select the station address without overlapping with that of
other units.
3.5.9
Connecting to CML, CMF050
Communication settings
Make the communication settings by operating the key
of the control equipment.
*1
Adjust the settings with GOT settings.
*2
Do not set to "0".
*3
Select the station address without overlapping with that of
other units.
3.5.10 Connecting to MQV
Communication settings
Make the communication settings by operating the key
of the control equipment.
*1
Adjust the settings with GOT settings.
*2
Do not set to "0".
*3
Select the station address without overlapping with that of
other units.
Item
Set value
Transmission speed
*1
9600bps, 19200bps, 38400bps
Communication mode
CPL
Data bit
8bits (fixed)
Parity bit
Even (fixed)
Stop bit
1bit (fixed)
Module address
*2*3*4
0 to F
Item
Set value
Transmission speed
*1
9600bps, 19200bps, 38400bps
Communication mode
*2
CPL
Data bit
7bits, 8bits
Parity bit
*1
Odd, even, none
Stop bit
1bit, 2bits
Communication minimum
response time
*5
1 to 250ms
Station address
*3*4
0 to 120
Rotary switch for the module address
0
1
234
56
7
8
9
A
BCDEF
Item
Set value
Transmission speed
*1
9600bps
Communication condition
selection
0: 8-bit data length, Even parity, Stop bit 1
1: 8-bit data length, Non parity, Stop bit 2
Station address
*2*3
0 to 99
Item
Set value
Transmission speed
*1
9600bps
Communication condition
selection
*1
00: 8-bit data length, Even parity, Stop bit 1
01: 8-bit data length, Non parity, Stop bit 2
Station address
*2*3
0 to 7F
Item
Set value
Transmission speed
*1
9600bps, 19200bps, 38400bps
Communication condition
selection
*1
00: 8-bit data length, Even parity, Stop bit 1
01: 8-bit data length, Non parity, Stop bit 2
Station address
*2*3
0 to 127
Summary of Contents for GOT 1000 Series
Page 2: ......
Page 76: ...1 46 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Page 78: ......
Page 114: ...2 36 2 CONNECTION TO IAI ROBOT CONTROLLER 2 7 Precautions ...
Page 232: ...5 18 5 CONNECTION TO OMRON TEMPERATURE CONTROLLER 5 7 Precautions ...
Page 254: ...6 22 6 CONNECTION TO KEYENCE PLC 6 4 Device Range that Can Be Set ...
Page 404: ...14 14 14 CONNECTION TO PANASONIC SERVO AMPLIFIER 14 7 Precautions ...
Page 432: ...REVISIONS 3 ...
Page 435: ......