FX2NC Series Programmable Controllers
Installation notes 3.
3-19
3.13
Termination of screw terminals
Cables terminating at a screw terminal of an FX
2N
and FX
0N
product should be fitted with insu-
lated crimp terminals, see example shown. Terminals screws should be tightened to between
0.5 to 0.8 N
m. Screw terminals must be secured to prevent a loose connection from causing a
malfunction. Failure to do so may cause equipment failures or malfunctions.
•
When one wire is connected to one terminal.
•
When two wires are connected to one terminal.
Caution
Make sure to turn OFF the power before starting any wiring work.
Figure 3.14:
Terminal
Terminal
Terminal
screw
Crimp
terminal
φ
3.2
(0.13")
φ
3.2
(0.13")
6.2mm
(0.24")
or less
6.2mm
(0.24")
or less
Terminal
screw
Crimp
terminal
Terminal
6.2mm
(0.24")
or less
φ
3.2
(0.13")
6.3mm
(0.25")
or more
6.2mm
(0.24")
or less
φ
3.2
(0.13")
6.3mm
(0.25")
or more
Summary of Contents for FX0N-485ADP
Page 1: ...D UL HARDWARE MANUAL FX2NC D UL SERIES PROGRAMMABLE CONTROLLERS ...
Page 12: ...FX2NC Series Programmable Controllers Introduction 1 ...
Page 40: ...FX2NC Series Programmable Controllers Introduction 1 1 28 MEMO ...
Page 42: ...FX2NC Series Programmable Controllers Terminal layouts 2 ...
Page 48: ...FX2NC Series Programmable Controllers Installation notes 3 ...
Page 70: ...FX2NC Series Programmable Controllers Power supply 4 ...
Page 78: ...FX2NC Series Programmable Controllers Inputs 5 ...
Page 88: ...FX2NC Series Programmable Controllers Inputs 5 5 10 MEMO ...
Page 90: ...FX2NC Series Programmable Controllers Outputs 6 ...
Page 108: ...FX2NC Series Programmable Controllers Outputs 6 6 18 MEMO ...
Page 110: ...FX2NC Series Programmable Controllers Diagnostics 7 ...
Page 130: ...FX2NC Series Programmable Controllers Discontinued model 8 ...
Page 132: ...FX2NC Series Programmable Controllers Discontinued model 8 8 2 MEMO ...
Page 134: ...FX2NC Series Programmable Controllers Appendix 9 ...
Page 139: ......