FX2NC Series Programmable Controllers
Installation notes 3.
3-4
3.2
FX
2NC
RUN/STOP Control
RUN or STOP of the FX
2NC
can be controlled by:
n
The RUN/STOP switch mounted next to the programming port.
o
A standard input (X000 to X017; X000 to X007 for FX
2NC
-16M
★
units) defined by the system
parameters.
p
Remotely from a personal computer or other programming peripheral.
Note
:The FX
2NC
RUN/STOP switch
n
works in parallel with the RUN-input terminal
o
.
Please refer to table 3.2.
During remote operation the FX
2NC
RUN/STOP status is determined by the most
recently operated control.
E.g. If the RUN/STOP switch is in RUN and a remote STOP is made from a personal
computer the RUN/STOP switch must be switched to STOP then back to RUN to
switch the MPU back to RUN mode.
Summary of Contents for FX0N-485ADP
Page 1: ...D UL HARDWARE MANUAL FX2NC D UL SERIES PROGRAMMABLE CONTROLLERS ...
Page 12: ...FX2NC Series Programmable Controllers Introduction 1 ...
Page 40: ...FX2NC Series Programmable Controllers Introduction 1 1 28 MEMO ...
Page 42: ...FX2NC Series Programmable Controllers Terminal layouts 2 ...
Page 48: ...FX2NC Series Programmable Controllers Installation notes 3 ...
Page 70: ...FX2NC Series Programmable Controllers Power supply 4 ...
Page 78: ...FX2NC Series Programmable Controllers Inputs 5 ...
Page 88: ...FX2NC Series Programmable Controllers Inputs 5 5 10 MEMO ...
Page 90: ...FX2NC Series Programmable Controllers Outputs 6 ...
Page 108: ...FX2NC Series Programmable Controllers Outputs 6 6 18 MEMO ...
Page 110: ...FX2NC Series Programmable Controllers Diagnostics 7 ...
Page 130: ...FX2NC Series Programmable Controllers Discontinued model 8 ...
Page 132: ...FX2NC Series Programmable Controllers Discontinued model 8 8 2 MEMO ...
Page 134: ...FX2NC Series Programmable Controllers Appendix 9 ...
Page 139: ......