(A) Application parameters
Parameters
5 - 336
5.11.2 Self
power
management
By turning ON the magnetic contactor (MC) on the input side before the motor is started and turning
OFF the MC after the motor is stopped, power is not supplied to the main circuit, reducing the standby
power.
Connection diagram
●
Terminal R1, S1 inputs
Pr.
Name
Initial
value
Setting
range
Description
248
A006
Self power management
selection
0
0
Self power management function disabled
1
Self power management function enabled (main
circuit OFF at protective function activation)
2
Self power management function enabled (main
circuit OFF at protective function activation due to a
circuit failure)
137
A002
Start waiting time
0.5 s
0 to 100 s
Set a time period that is a little longer than the time
period from the ON signal input to the actual pick-up
operation of MC1 (0.3 to 0.5 s).
254
A007
Main circuit power OFF
waiting time
600 s
0
1 to 3600 s
Set the waiting time until the main circuit power
supply is turned OFF after the motor is stopped.
9999
The main circuit power supply is turned OFF only
when the protective function selected by Pr. 248 is
activated.
30
E300
Regenerative function
selection
0
100, 101
Power supply to the inverter: AC (terminals R, S, and
T)
When power is supplied only to the control circuit,
and then switched to be supplied to both the control
and main circuits, inverter reset is not performed.
0 to 2, 10, 11,
20, 21, 102,
110, 111,
120, 121
For other settings, refer to page 5-532.
I003034E
Fig. 5-151:
Power input via terminals R1 and S1
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
MC1
MC1
R/L1
S/L2
T/L3
R1/L11
S1/L21
U
V
W
M
MC1
SE
MCCB
MC1
R/L1
S/L2
T/L3
R1/L11
S1/L21
U
V
W
M
MC1
SE
MC1
MCCB
R1/L11
S1/L21
P/+
N/-
P/+
N/-
RDA
X10
RSO
RES
Y17
X94
SE
SD
24
V DC
Separated converter type
24 V DC
Standard models
Inverter
Converter unit
Inverter
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......