320
Inspection items
6.1.4
Display of the life of the inverter parts
The self-diagnostic alarm is output when the life span of the control circuit capacitor, cooling fan and each parts of the inrush
current limit circuit is near its end. It gives an indication of replacement time.
The life alarm output can be used as a guideline for life judgement.
6.1.5
Checking the inverter and converter modules
<Preparation>
(1) Disconnect the external power supply cables (R/L1, S/L2, T/L3) and motor cables (U, V, W).
(2) Prepare a tester. (Use 100
range.)
<Checking method>
Change the polarity of the tester alternately at the inverter terminals R/L1, S/L2, T/L3, U, V, W, + and -, and check for
continuity.
<Module device numbers and terminals to be checked>
6.1.6
Cleaning
Always run the inverter in a clean status.
When cleaning the inverter, gently wipe dirty areas with a soft cloth immersed in neutral detergent or ethanol.
Parts
Judgement Level
Main circuit capacitor
85% of the initial capacity
Control circuit capacitor
Estimated remaining life 10%
Inrush current limit circuit
Estimated remaining life 10%
(Power ON: 100,000 times left)
Cooling fan
Less than 50% of the predetermined speed
POINT
to perform the life check of the inverter parts.
NOTE
1. Before measurement, check that the smoothing capacitor is discharged.
2. At the time of discontinuity, the measured value is almost
. When there is an instantaneous continuity, due to the
smoothing capacitor, the tester may not indicate
.
At the time of continuity, the measured value is several to
several tens-of ohms depending on the module type, circuit tester type, etc. If all measured values are almost the
same, the modules are without fault.
Tester Polarity
Result
Tester Polarity
Result
C
onver
ter
module
D1
R/L1
P/
Discontinuity
D4
R/L1
N/
Continuity
P/
R/L1 Continuity
N/
R/L1 Discontinuity
D2
S/L2
P/
Discontinuity
D5
S/L2
N/
Continuity
P/
S/L2 Continuity
N/
S/L2 Discontinuity
D3
T/L3
P/
Discontinuity
D6
T/L3
N/
Continuity
P/
T/L3 Continuity
N/
T/L3 Discontinuity
In
ver
ter
m
odule
TR1
U
P/
Discontinuity
TR4
U
N/
Continuity
P/
U
Continuity
N/
U
Discontinuity
TR3
V
P/
Discontinuity
TR6
V
N/
Continuity
P/
V
Continuity
N/
V
Discontinuity
TR5
W
P/
Discontinuity
TR2
W
N/
Continuity
P/
W
Continuity
N/
W
Discontinuity
(Assumes the use of an analog meter.)
NOTE
Do not use solvent, such as acetone, benzene, toluene and alcohol, as these will cause the inverter surface paint to peel off.
The display, etc. of the operation panel and parameter unit (FR-PU04/FR-PU07) are vulnerable to detergent and alcohol.
Therefore, avoid using them for cleaning.
Converter module
Inverter module
D1
D2
D3
D4
D5
D6
TR1
TR3
TR5
TR4
TR6
TR2
U
V
W
R/L1
S/L2
T/L3
C
P/
N/