200
Selection of operation mode and operation location
4.19 Selection of operation mode and operation location
4.19.1 Operation mode selection (Pr. 79)
The above parameter can be changed during a stop in any operation mode.
Purpose
Parameter that should be Set
Refer to Page
Operation mode selection
Operation mode selection
Pr. 79
Started in Network operation mode Operation mode at power-on
Pr. 79, Pr. 340
Selection of operation location
Operation command source and
speed command source during
communication operation, selection
of operation location
Pr. 338, Pr. 339
Pr. 551
Used to select the operation mode of the inverter.
Mode can be changed as desired among operation using external command signals (External operation), operation
from the operation panel and PU (FR-PU07/FR-PU04) (PU operation), combined operation of PU operation and
External operation (External/PU combined operation), and Network operation (when RS-485 communication is used).
Parameter
Number
Name
Initial Value
Setting Range
79
Operation mode selection
0
0 to 4, 6, 7
POINT
Use the easy setting mode to set
Pr. 79
in simple steps.
Pr.79
Setting
Description
LED Indication
: OFF
: ON
Refer
to
Page
0
(Initial
value)
Use External/PU switchover mode (At power ON, the inverter is in the External operation
mode.)
Press
to switch between the PU and External operation mode.
PU operation mode
External operation mode
NET operation mode
1
Operation mode
Frequency command
Start command
PU operation mode
PU operation mode (fixed)
Setting by the operation
panel and PU (FR-PU04/FR-
PU07)
Input by
on the
operation panel or
and
on PU (FR-PU04/FR-
PU07)
2
External operation mode (fixed)
The operation can be performed
by switching between the
External and NET operation
modes.
External signal input (from
terminal 2, 4, JOG, multi-
speed selection, etc.)
External signal input (from
terminal STF and STR)
External operation mode
NET operation mode
3
External/PU combined
operation mode 1
Operation panel and PU (FR-
PU04/FR-PU07) setting or
external signal input (multi-
speed setting, across
terminals 4 and 5 (valid when
AU signal turns ON)).
External signal input (from
terminal STF and STR)
External/PU combined
operation mode
4
External/PU combined
operation mode 2
External signal input
(Terminal 2, 4, JOG, multi-
speed selection, etc.)
Input by
on the
operation panel or
and
on PU (FR-PU04/FR-
PU07)
6
Switchover mode
Switch among PU operation, External operating, and NET operation while keeping the
same operating status.
PU operation mode
External operation mode
NET operation mode
7
External operation mode (PU operation interlock)
X12 signal ON: Operation mode can be switched to the PU operation mode.
(output stop during External operation)
X12 signal OFF: Operation mode cannot be switched to the PU operation mode.
The priorities of the frequency commands when
Pr. 79
= "3" are "Multi-speed operation (RL/RM/RH/REX) > PID control (X14) > terminal 4 analog input (AU)
> digital input from the operation panel".
REMARKS
If switching of the operation mode is invalid even though
Pr. 79
is set,
refer to page 314
.