Frequency setting by external terminals
4.7 Frequency setting by external terminals
4.7.1
Operation by multi-speed operation (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in
Pr. 77 Parameter write selection
.
The above parameters can be set when
Pr. 160 Extended function display selection
= "0".
Performing IPM parameter initialization changes the settings.
Purpose
Parameter that should be Set
Refer to Page
Make frequency setting by
combination of terminals
Multi-speed operation
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Perform Jog operation
Jog operation
Pr. 15, Pr. 16
Infinitely variable speed setting by
terminals
Remote setting function
Pr. 59
Can be used to change the preset speed in the parameter with the contact signals.
Any speed can be selected by merely turning ON/OFF the contact signals (RH, RM, RL, REX signals).
Parameter
Number
Name
Initial Value
Setting Range
Description
4
Multi-speed setting (high
speed)
60Hz
0 to 400Hz
Frequency when RH turns ON
5
Multi-speed setting (middle
speed)
30Hz
0 to 400Hz
Frequency when RM turns ON
6
Multi-speed setting (low
speed)
10Hz
0 to 400Hz
Frequency when RL turns ON
24
Multi-speed setting (speed 4)
9999
0 to 400Hz, 9999
Frequency from 4 speed to 15 speed can
be set according to the combination of
the RH, RM, RL and REX signals.
9999: not selected
25
Multi-speed setting (speed 5)
9999
0 to 400Hz, 9999
26
Multi-speed setting (speed 6)
9999
0 to 400Hz, 9999
27
Multi-speed setting (speed 7)
9999
0 to 400Hz, 9999
232
Multi-speed setting (speed 8)
9999
0 to 400Hz, 9999
233
Multi-speed setting (speed 9)
9999
0 to 400Hz, 9999
234
Multi-speed setting (speed 10)
9999
0 to 400Hz, 9999
235
Multi-speed setting (speed 11)
9999
0 to 400Hz, 9999
236
Multi-speed setting (speed 12)
9999
0 to 400Hz, 9999
237
Multi-speed setting (speed 13)
9999
0 to 400Hz, 9999
238
Multi-speed setting (speed 14)
9999
0 to 400Hz, 9999
239
Multi-speed setting (speed 15)
9999
0 to 400Hz, 9999
(1) Multi-speed setting for 3 speeds
(Pr. 4 to Pr. 6)
The inverter operates at frequencies set in
Pr. 4
when RH signal is ON,
Pr. 5
when RM signal is ON and
Pr. 6
when RL
signal is ON.
For the RL signal, set "0" in any of
Pr.178 to Pr.182 (input terminal function selection)
to assign the function to a terminal.
ON
ON
ON
Output frequency (Hz)
Speed 1
(High speed)
Speed 2
(Middle speed)
Speed 3
(Low speed)
RH
RM
RL
Time
Multi-Speed Operation
Connection Example
10
2
5
STF
RH
RM
RL
SD
Inverter
Multi-speed
selection
Frequency setting
potentiometer
Forward
rotation
REMARKS
In the initial setting, if two or three of multi-speed settings are simultaneously selected, priority is given to the set frequency of
the lower signal.
For example, when the RH and RM signals turn ON, the RM signal
(Pr. 5)
has a higher priority.
The RH and RM signals are assigned to the terminals RH and RM in the initial setting. By setting "1 (RM)" or "2 (RH)" in
any of
Pr. 178 to Pr. 182 (input terminal function selection)
, you can assign the signals to other terminals.