14. (C) Motor Constant Parameters
14.2 Offline auto tuning
*1
The setting range for the 575 V class is "0, 3, 5, 6, 10, 13, 15, 16, 30, 33, 8090, 8093, 9090, and 9093".
*2
The initial value for the FR-E820-0050(0.75K) or lower, FR-E840-0026(0.75K) or lower, FR-E860-0017(0.75K), and FR-E820S-0050(0.75K) or
lower is set to the 85% of the inverter rated current.
*3
The initial value differs according to the voltage class (200/400/575 V).
*4
The setting range and unit change according to the
Pr.71 (Pr.450)
setting.
*5
To perform offline auto tuning for the 400 V class 0.1 kW Mitsubishi Electric geared motor (GM-[]), set "1803" in
Pr.71 (Pr.450)
.
• The setting is valid under Advanced magnetic flux vector control, Real sensorless vector control, or Vector control.
• By using the offline auto tuning function, the optimum operation characteristics are obtained for a motor other than Mitsubishi
Electric standard efficiency motors (SF-JR 0.2 kW or higher), high-efficiency motors (SF-HR 0.2 kW or higher), Mitsubishi
Electric constant-torque motors (SF-JRCA 4P, SF-HRCA 0.2 kW to 7.5 kW), Mitsubishi Electric high-performance energy-
serving motor (SF-PR), Mitsubishi Electric high-performance energy-saving motor with encoder (SF-PR-SC), Mitsubishi
Electric Vector control dedicated motor (SF-V5RU (1500 r/min series)), Mitsubishi Electric geared motor (GM-[]), or Mitsubishi
Electric inverter-driven geared motor for encoder feedback control (GM-DZ, GM-DP), such as an induction motor of other
manufacturers or SF-JRC, or with a long wiring length (30 m or longer).
• Tuning is enabled even when a load is connected to the motor.
• Reading/writing of the motor constants tuned by offline auto tuning are enabled.
• The offline auto tuning status can be monitored on the operation panel.
Before performing offline auto tuning
Check the following points before performing offline auto tuning:
• Check that a value other than "9999" is set in
Pr.80
and
Pr.81
, and Advanced magnetic flux vector control, Real sensorless
vector control, or Vector control is selected (with
Pr.800
). (Refer to
• Check that a motor is connected. (Check that the motor is not rotated by an external force during tuning.)
• Select a motor with the rated current equal to or less than the inverter rated current. (Note that the motor rated current
should be 0.4 kW or higher (0.1 kW or higher for the 200 V class).) If a motor with substantially low rated current compared
with the inverter rated current is used, speed and torque accuracies may deteriorate due to torque ripples, etc. Set the
rated motor current to about 40% or higher of the inverter rated current.
• Tuning is not available for a high-slip motor, high-speed motor, or special motor.
• The maximum frequency is 400 Hz.
• Tuning is enabled even when a load is connected to the motor. The motor may run slightly. Fix the motor securely with a
mechanical brake, or before tuning, make sure that it is safe even if the motor rotates. (Caution is required especially in
vertical lift applications.) Note that even if the motor runs slightly, tuning performance is unaffected.
• Offline auto tuning is not performed correctly when the surge voltage suppression filter (FR-ASF-H/FR-BMF-H) is inserted
between the inverter and motor. Be sure to remove it before performing tuning.
• Make sure to connect the encoder to the motor without coaxial misalignment for Vector control. Speed ratio must be 1:1.
Settings
• To perform tuning, set the following parameters about the motor.
*1
The initial value differs according to the voltage class (200/400/575 V).
First
motor
Pr.
Second
motor
Pr.
Name
Initial value
Description
80
453
Motor capacity
9999 (V/F control)
Set the motor capacity (kW).
81
454
Number of motor poles 9999 (V/F control)
Set the number of motor poles (2 to 12).
800
451
Control method
selection
40 (in
Pr.800
) / 9999
(in
Pr.451
)
Set this parameter under Advanced magnetic flux vector control, Real
sensorless vector control, or Vector control.
9
51
Electronic thermal O/L
relay
Inverter rated current
Set the rated motor current (A).
83
456
Rated motor voltage
200/400/575 V
Set the rated motor voltage (V) printed on the motor's rating plate.
84
457
Rated motor
frequency
9999
Set the rated motor frequency (Hz).
When the setting is "9999", the
Pr.3 Base frequency
setting is used.
71
450
Applied motor
0 (standard motor)
Set this parameter according to the motor.
Three types of motor
constant setting ranges, units and tuning data can be stored according
to settings.
96
463
Auto tuning setting/
status
0
Set "1".
1: Tuning is performed without the motor rotating. (Excitation noise
occurs at this point.)
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...