12. (M) Item and Output Signal for Monitoring
12.2 Monitor item selection on operation panel or via communication
*1
The monitor code is used for the Mitsubishi inverter protocol, CC-Link, CC-Link IE TSN, and CC-Link IE Field Network Basic.
*2
The monitor code is used for the MODBUS RTU, MODBUS/TCP, and BACnet/IP.
*3
The monitor number is used for the EtherNet/IP and PROFINET.
*4
Indication with a minus sign is not possible via RS-485 communication (Mitsubishi inverter protocol or MODBUS RTU).
*5
To monitor the item on the LCD operation panel (FR-LU08) in the monitor mode, use
Pr.774 to Pr.776
or the monitor function of the FR-LU08 for
setting.
*6
The cumulative energization time and actual operation time are accumulated from 0 to 65535 hours, then cleared, and accumulated again from 0.
*7
The actual operation time does not increase if the cumulative running time before power OFF is less than an hour.
*8
Since each readout of the output voltage and output current displayed on the operation panel is a 4-digit number, a value of more than "9999" is
displayed as "----".
*9
The inverter regards the output current which is less than the specified current level (5% of the rated inverter current) as 0 A. Therefore, each
readout of an output current and output power may show "0" if a too small-capacity motor is used as contrasted with the inverter capacity and the
output current falls below the specified value.
*10 Available when the plug-in option is connected.
Option input
terminal status 1
(for
communication)
—
—
3A
The ON/OFF state of the input terminals X0 to
X15 on the digital input option (FR-A8AX) is
monitored via communication.
Option input
terminal status 2
(for
communication)
—
—
3B
The ON/OFF state of the input terminal DY on
the digital input option (FR-A8AX) is monitored
via communication.
Option output
terminal status
(for
communication)
—
—
H3C
3C
The ON/OFF state of the output terminals on the
digital output option (FR-A8AY) or the relay
output option (FR-A8AR) is monitored via
communication.
Motor thermal
load factor
0.1%
61
H3D
40261
3D
The accumulated heat value of the motor
thermal O/L relay is displayed.
The Motor overload trip (electronic thermal relay
function) (E.THM) occurs at 100%.
Inverter thermal
load factor
0.1%
62
H3E
40262
3E
The accumulated heat value of the inverter
thermal O/L relay is displayed.
The Inverter overload trip (electronic thermal
relay function) (E.THT) occurs at 100%.
PID measured
value 2
0.1%
67
H43
40267
43
The PID measured value is displayed while the
PID control is enabled (
Pr.128
≠
"0"), even if PID
control operating conditions are not satisfied.
(Refer to
32-bit cumulative
energy (lower 16
bits)
1 kWh
—
H4D
40277
4D
The upper or lower 16 bits of the 32-bit
cumulative energy is displayed on each
indication.
Monitoring via communication is available.
32-bit cumulative
energy (upper 16
bits)
1 kWh
—
H4E
40278
4E
32-bit cumulative
energy (lower 16
bits)
0.01 kWh
—
H4F
40279
4F
32-bit cumulative
energy (upper 16
bits)
0.01 kWh
—
H50
40280
50
BACnet valid
APDU counter
1
83
H53
40283
53
The count of valid APDU detection is displayed.
(Available only for the FR-E800-EPA and FR-
E800-SCEPA.)
PID manipulated
amount
0.1%
91
H5B
40291
5B
○
The PID control manipulated amount is
displayed. (Refer to
.)
Dancer main set
speed
97
H61
40297
61
The set speed for main speed during the dancer
control operation is displayed.
Monitor item
Incremen
t and unit
Pr.
setting
Communication
Negative
indicatio
n (-)
*4
Description
Monitor
code 1
*1
Monitor
code 2
*2
Monitor
number
*3
Summary of Contents for FR-E800
Page 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Page 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Page 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Page 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Page 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Page 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Page 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Page 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Page 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...