Add any input/outputs you need (in this case we will add E-Stop input X0/X1)
Module Parameter: Double Input Discrepancy:
1: Used
Note: this will allow remote I/O to automatically recover on chain fault (discrepancy check)
Module Parameters X0_X1
Wiring:
Safety Double Wiring
(to use test pulses)
Input Response Time:
1.0ms
(default okay)
Double Input Discrepancy:
Detect
Double Input Disc. Detection Time:
10
x 10 = 100ms
(100ms recommended for physical devices)
Input Dark Test Execution:
Perform
Checks for Shorts (using test pulses)