Parameter
Useful functions
FR-E700 SC EC/ENE
6 - 321
Main circuit capacitor life display (Pr. 258, Pr. 259)
The deterioration degree of the main circuit capacitor is displayed in Pr. 258 as a life.
On the assumption that the main circuit capacitor capacitance at factory shipment is 100%, the ca-
pacitor life is displayed in Pr. 258 every time measurement is made. When the measured value falls to
or below 85%, Pr. 255 bit 1 is turned on and also an alarm is output to the Y90 signal.
Measure the capacitor capacity according to the following procedure and check the deterioration lev-
el of the capacitor capacity.
햲
Check that the motor is connected and at a stop.
햳
Set "1" (measuring start) in Pr. 259.
햴
Switch power off. The inverter applies DC voltage to the motor to measure the capacitor capacity
while the inverter is off.
햵
After confirming that the LED of the operation panel is off, power on again.
햶
Check that "3" (measuring completion) is set in Pr. 259, read Pr 258, and check the deterioration
degree of the main circuit capacitor.
When the main circuit capacitor life is measured under the following conditions, "forced end" (Pr. 259
= "8") or "measuring error" (Pr. 259 = "9") occurs or it remains in "measuring start" (Pr. 259 = "1"). There-
fore, do not measure in such case. In addition, even when "measurement completion" (Pr. 259 = "3")
is confirmed under the following conditions, normal measurement can not be done.
쐃
FR-HC or FR-CV is connected.
쐇
DC power supply is connected to the terminal P/+ and N/ .
쐋
The power supply switched on during measurement.
쐏
The motor is not connected to the inverter.
쐄
The motor is running. (The motor is coasting.)
쐂
The motor capacity is two ranks (or more) smaller as compared to the inverter capacity.
쐆
The inverter is at an alarm stop or an alarm occurred while power is off.
쐊
The inverter output is shut off with the MRS signal.
쐎
The start command is given while measuring.
쐅
The parameter unit (FR-PU04/FR-PU07) is connected.
쐈
Use terminal PC as power supply.
쐉
I/O terminal of the control terminal block and plug-in option is on (continuity).
씈
Plug-in option is fitted. (FR-E720S-050SC or less, FR-E740-026SC or less)
Pr. 259
Description
Remarks
0
No measurement
Initial value
1
Measurement start
Measurement starts when the power supply is
switched off.
2
During measurement
Only displayed and cannot be set
3
Measurement complete
8
Forced end
(see
���
,
���
,
���
,
���
below)
9
Measurement error
(see
���
,
���
,
���
below)
Tab. 6-120:
Parameter 259
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......