217
7
(4) Single-phase 100V power supply
Note: 1. The applicable motor capacity indicated is the maximum capacity applicable
when the Mitsubishi 4-pole standard motor is used.
Normally, the rated current (at 50Hz) of the motor applied should not exceed
the rated current.
2. The rated output capacity indicated assumes that the output voltage is 230V.
3. The overload capacity indicated in % is the ratio of the overload current to the
inverter's rated current. For repeated duty, allow time for the inverter and motor
to return to or below the temperatures under 100% load.
4. For single-phase 100V power input, the output voltage provided cannot be
twice or more than the power supply voltage. The pulse voltage value of the
inverter output side voltage remains unchanged at about
that of the power
supply.
5. The power supply capacity changes with the values of the power supply side
inverter impedances (including those of the input reactor and cables). Prepare
the power supply capacity which is not less than the indicated.
6. Load applied to the motor will reduce the output voltage about 10 to 15%.
When using a general-purpose motor, it must be used under reduced load.
7. The rated output current in the parentheses applies when low acoustic noise
operation is to be performed at the ambient temperature higher than 40
°
C with
the Pr. 72 "PWM frequency selection" value set to not less than 2kHz.
8. For single-phase 100V power input, the application of motor load reduces the
output voltage about 10 to 15%. Therefore, the load must be reduced when a
general-purpose motor is used.
Type FR-E510W-
K
0.1
0.2
0.4
0.75
Applicable motor capacity (kW)
(Note 1)
0.1
0.2
0.4
0.75
Ou
tp
u
t
Rated capacity (kVA)
(Note 2)
0.3
0.6
1.2
2
Rated output current (A)
(Note 7)
0.8
(0.8)
1.5
(1.4)
3.0
(2.5)
5.0
(4.1)
Overload capacity
(Note 3)
150% 60s 200% 0.5s (inverse-time characteristics)
Rated output voltage
(Note 4)
Three phase, 200V to 230V 50Hz/60Hz (Note 4, 8)
Po
w
e
r su
pp
ly
Rated input AC voltage,
frequency
Single phase, 100V to 115V 50Hz/60Hz
Permissible AC voltage
fluctuation
Single phase, 90 to 132V 50Hz/60Hz
Permissible frequency
fluctuation
Within ±5%
Power supply capacity (kVA)
(Note 5)
0.5
0.9
1.5
2.5
Protective structure (JEM1030)
Enclosed type (IP20)
Cooling system
Self-cooling
Approximate weight (kg)
0.6
0.6
1.0
1.7