1 PRODUCT CHECKING AND PARTS IDENTIFICATION
Unpack the inverter and check the capacity plate on the front cover and the rating plate on the inverter side face to ensure that
the product agrees with your order and the inverter is intact.
z
Installation of the inverter
Enclosure surface mounting
Remove the front cover and wiring cover to mount the inverter to the surface.
Note
y
When encasing multiple inverters, install them in parallel as a
cooling measure.
y
When using the inverters at the surrounding air temperature of
40°C (104°F) or less, the inverters can be installed without any
clearance between them (0cm (0 inches) clearance). When
surrounding air temperature exceeds 40°C (104°F), clearances
between the inverters should be 1cm (0.39inches) or more (5cm
(1.96inches) or more for the FR-D720-238 and FR-D740-120 or
higher).
y
Install the inverter vertically.
FR
D740
036
-
-
- NA
Symbol
Voltage class
D740
Three-phase 400V class
Rating plate
Inverter model
Input rating
Output rating
Serial number
FR-D740-036-NA
Inverter model
Rating plate
Represents
the rated
current
Inverter model Serial number
Capacity plate FR-D740-036-NA
D720S
Single-phase 200V class
D710W
Single-phase 100V class
D720
Three-phase 200V class
DATE:XXXX-XX
Production year and month
Front cover
Front cover
Wiring cover
Wiring cover
FR-D720-008 to 042
FR-D720S-008 to 042
FR-D710W-008 to 025
FR-D720-070 or higher
FR-D740-012 or higher
FR-D720S-070, 100
FR-D710W-042
10cm(3.94inches)
or more
10cm(3.94inches)
or more
V
e
rtical
Refer to the
clearances
on the left.