Check first when you have some troubles
5.5 Check first when you have some troubles
POINT
If the cause is still unknown after every check, it is recommended to initialize the parameters (initial value) then re-
set the required parameter values and check again.
5.5.1
Motor will not start
1) Check the
Pr. 0 Torque boost
setting if V/F control is exercised.
2) Check the main circuit.
Check that a proper power supply voltage is applied. (Operation panel display is provided.)
Check that the motor is connected properly.
Check that the jumper and P1 is connected.
3) Check the input signals
Check that the start signal is input.
Check that both the forward and reverse rotation start signals are not input simultaneously.
Check that the frequency setting signal is not zero. (When the frequency command is 0Hz and the start
command is entered, RUN LED of the operation panel flickers.)
Check that the AU signal is on when terminal 4 is used for frequency setting.
Check that the output stop signal (MRS) or reset signal (RES) is not on.
Check that the sink or source jumper connector is fitted securely.
Check that the jumper across S1-SC, S2-SC is connected.
4) Check the parameter settings
Check that
Pr. 78 Reverse rotation prevention selection
is not set.
Check that the
Pr. 79 Operation mode selection
setting is correct.
Check that the bias and gain
(calibration parameter C2 to C7)
settings are correct.
Check that the starting frequency
Pr. 13 Starting frequency
setting is not greater than the running frequency.
Check that frequency settings of each running frequency (such as multi-speed operation) are not zero. Check
that especially the maximum frequency
Pr. 1 Maximum frequency
is not zero.
Check that the
Pr. 15
Jog frequency
setting is not lower than the
Pr. 13 Starting frequency
value.
Check that the operation location by
Pr. 551
is appropriate. (Example: write from the operation panel is disabled
when parameter unit is connected)
5) Inspection of load
Check that the load is not too heavy.
Check that the shaft is not locked.
6) Others
Check that the operation panel display does not show a fault (e.g. E.OC1).
5.5.2
Motor generates abnormal noise
No carrier frequency noises (metallic noises) are generated.
Soft-PWM control to change the motor tone into an unoffending complex tone is factory-set to valid by
Pr. 72
PWM frequency selection
.
Adjust
Pr. 72 PWM frequency selection
to change the motor tone.
Check for any mechanical looseness.
Contact the motor manufacturer.