Class 0x2A Instance 1
Attribute ID
Access
Data
type
No. of
data bytes
Range
Definition
101
Set
UINT
2
Any
Inverter reset
Set a value other than "0" in
Pr. 340
to start in Network operation mode
after reset. (Refer to
102
Set
UINT
2
0x965A
Parameter clear
103
Set
UINT
2
0x99AA
All parameter clear
105
Set
UINT
2
0x5A96
Clear parameters
Communication parameters are not
cleared.
106
Set
UINT
2
0xAA99
All parameter clear
112
Get/Set
UINT
2
0 to 0xE678
Set frequency (RAM)
Either write the set frequency to RAM
or read from RAM.
(0.01 Hz increments)
113
Set
UINT
2
0 to 0xE678
Set frequency (EEPROM)
Write the set frequency to EEPROM
(0.01 Hz increments)
114
Get/Set
UINT
2
—
Inverter status monitor/run command (Refer to
120
Get/Set
UINT
2
0
External operation
Operation mode read (Get)
1
PU operation
2
External JOG operation
3
PU JOG operation
4
Network operation
5
External/PU combined operation
0x0010
External operation
Operation mode write (Set) Input
2-byte data.
0x0011
PU operation (when
Pr. 79
= 6)
0x0014
Network operation