36
4.5 CC-Link IE Field Network function setting
4.5.1
Network number setting (Pr. 434)
Set the inverter network number in
Pr. 434
.
The setting range of
Pr. 434
is "0 to 255", but its active range is "1 to 239".
The values out of the active range are invalid because such values cannot be transmitted to the master station.
NOTE
• The setting is applied after an inverter reset or power-ON.
4.5.2
Station number setting (Pr. 435)
Use
Pr. 435
to set station number of the inverter.
The setting range of
Pr. 435
is "0 to 255", but its active range is "1 to 120".
The values out of the active range are invalid because such values cannot be transmitted to the master station.
NOTE
• Use different station numbers for different devices. (If different devices have the same station number, the
communication cannot be performed properly. If an error occurs due to a duplicated number, re-assign the station
numbers, then reset the master station or the inverter power.)
• Station numbers do not have to be consecutive numbers.
• The setting is applied after an inverter reset or power-ON.
Pr.
Name
Initial value
Setting range
434
Network number (CC-Link IE)
0
0 to 255
Pr.
Name
Initial value
Setting range
435
Station number (CC-Link IE)
0
0 to 255