INVERTER SETTING
33
4
4.3.2
Fault and measures
Inverter operation in each operation mode at error occurrences
Depends on the
Pr.502
setting.
Measures at error occurrences
When faults other than the above are displayed, refer to the Instruction Manual (Detailed) of the inverter and remove the cause of the
error.
Location
Status
Operation mode
Network operation
External operation
PU operation
Inverter
Inverter operation
Output shutoff
Output shutoff
Output shutoff
Data communication
Continued
Continued
Continued
Communication
line
Inverter operation
Output shutoff
Continued
Continued
Data communication
Stop
Stop
Stop
Communication
option
Communication
option connection
error
Inverter operation
Output shutoff
Output shutoff
Output shutoff
Data
communication
Continued
Continued
Continued
Error of
communication
option itself
Inverter operation
Output shutoff
Continued
Continued
Data
communication
Stop
Stop
Stop
Fault indication
Fault description
Measures
E.OP1
Communication line error
• Check the LED status of the option unit and remove the cause of the alarm (Refer to
for LED indication status).
• Inspect the master.
E.1, E.2, E.3
Option fault
• Insert the communication option to the inverter option connector 1.
• Check the connection between the inverter and option unit for poor contact, etc. and remove
the cause of the error.