2
(2) Loosen the terminal screw and insert the cable into the terminal.
NOTE
• Undertightening can cause cable disconnection or malfunction. Overtightening can cause a short circuit or malfunction
due to damage to the screw or unit.
• When wiring cables to the inverter's RS-485 terminals while a plug-in option is mounted, take caution not to let the
cables touch the circuit board of the option or of the inverter. Otherwise, electromagnetic noises may cause
malfunctions.
Screw size
Tightening torque
Cable size
Screwdriver
M2
0.22 N
m to 0.25 N
m
0.3 mm
2
to 0.75 mm
2
Small
flat-blade screwdriver
(Tip thickness: 0.4 mm/tip width: 2.5 mm)
CAUTION
After wiring, wire offcuts must not be left in the inverter. They may cause a fault, failure or malfunction.