(N) Operation via communication and its settings
Parameters
5 - 620
Signal loss detection (Pr. 122, Pr. 336 "RS-485 communication check time interval")
●
If a signal loss (communication stop) is detected between the inverter and computer as a result
of a signal loss detection, a communication fault (PU connector communication: E.PUE, RS-485
terminal communication: E.SER) occurs and the inverter trips.
●
When the setting is "9999", communication check (signal loss detection) is not made.
●
When the setting is "0", communication from the PU connector is not possible. In the case of
communication by RS-485 terminals, reading, etc. of monitors and parameters is possible, though
a communication error (E.SER) occurs instantly when the Network operation mode is switched to.
●
A signal loss detection is made when the setting is any of "0.1 s to 999.8 s". To make a signal loss
detection, it is necessary to send data (for details on control codes, refer to page 5-616) from the
computer within the communication check time interval. (The inverter makes a communication
check (clearing of communication check counter) regardless of the station number setting of the
data sent from the master).
●
Communication check is started at the first communication in the operation mode having the
operation source (PU operation mode for PU connector communication in the initial setting or
Network operation mode for RS-485 terminal communication).
Instructions for the program
●
When data from the computer has any error, the inverter does not accept that data. Hence, in the
user program, always insert a retry program for data error.
●
All data communication, for example, run command or monitoring, are started when the com-
puter gives a communication request. The inverter does not return any data without the comput-
er's request. Hence, design the program so that the computer gives a data read request for
monitoring, etc. as required.
I002739E
Fig. 5-314:
Open cable detection
ENQ
ALM
Computer
Computer
Inverter
Inverter
Operation Mode
External
PU
Example: PU connector communication, Pr. 122 = "0.1 to 999.8 s"
Pr. 122
OFF
ON
Time
Fault (E.PUE)
Check start
Communication
check counter
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......