MOTOR THERMISTOR INTERFACE
6.3.4 Thermistor calibration (C29)
Perform calibration of the inverter and FR-A7AZ (thermistor interface) at installation, before starting the
motor.
(1) Calibration method
1) Set the thermistor calibration status switch (SW2) to the line to place the FR-A7AZ in the calibration status.
2)Read
C29 (Pr. 925)
and set the compensation value.
⋅
Compensation using the operation panel (FR-DU07)
refer to page 35
⋅
Compensation using the parameter unit (FR-PU07)
refer to page 36
3)After compensation, reset the thermistor calibration status switch (SW2) to the original position.
CAUTION
⋅
Calibration must be performed at installation.
CAUTION
⋅
Always return the SW2 to the original position after calibration. Starting the motor in the calibration status
results in motor overload trip (E.THM), shutting off the inverter output.