Parameter
Misoperation prevention and parameter setting restriction
FR-A700 EC
6 - 403
6.21
Misoperation prevention and parameter setting restriction
6.21.1
Reset selection/disconnected PU detection/PU stop selection (Pr. 75)
You can select the reset input acceptance, disconnected PU (FR-DU07/FR-PU04/FR-PU07)
connector detection function and PU stop function.
The Pr. 75 value can be set any time. Also, if parameter (all) clear is executed, this setting will
not return to the initial value.
Purpose
Parameters that must be set
Refer to
Section
Limit reset function
Make alarm stop when PU is
disconnected
Stop from PU
Reset selection/
disconnected PU detection/
PU stop selection
Pr. 75
Prevention of parameter rewrite
Parameter write selection
Pr. 77
Prevention of reverse rotation of the
motor
Reverse rotation prevention selection
Pr. 78
Display necessary parameters
Reverse rotation prevention selection
Pr. 160,
Pr. 172 to Pr. 174
Control of parameter write by
communication
EEPROM write selection
Pr. 342
Pr.
No.
Name
Initial
Value
Setting
Range
Description
Parameters referred to
Refer to
Section
75
Reset selection/
disconnected PU
detection/
PU stop selection
14
01800
or
less
0–3/
14–17
For the initial value, reset always
enabled, without disconnected PU
detection, and with PU stop func-
tion are set.
250
Stop selection
02160
or
more
0–3/
14–17/
100–103/
114–117
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......