Misoperation prevention and parameter setting restriction
Parameter
6 - 408
6.21.2
Parameter write selection (Pr. 77)
You can select whether write to various parameters can be performed or not. Use this function
to prevent parameter values from being rewritten by misoperation.
Pr. 77 can be always set independently of the operation mode and operation status.
Write parameters only at a stop (Pr. 77 = 0)
Parameters can be written only during a stop in the PU operation mode.
The half-tone screened parameters in the parameter list (Tab. 6-1) can always be written,
regardless of the operation mode and operation status. However, Pr. 72 "PWM frequency selec-
tion" and Pr. 240 "Soft-PWM operation selection" can be written during operation in the PU oper-
ation mode, but cannot be written in external operation mode.
Disable parameter write (Pr. 77 = 1)
Parameter write is not enabled. (Reading is enabled.)
Parameter clear and all parameter clear cannot be performed, either.
The parameters given below can be written if Pr. 77 = 1.
Pr.
No.
Name
Initial
Value
Setting
Range
Description
Parameters referred to
Refer to
Section
77
Parameter write selection
0
0
Write is enabled only during a stop.
79
Operation mode
selection
1
Parameter write is not enabled.
2
Parameter write is enabled in any opera-
tion mode regardless of operation status.
Parameter
Name
22
Stall prevention operation level
75
Reset selection/disconnected PU detection/PU stop selection
77
Parameter write selection
79
Operation mode selection
160
User group read selection
Tab. 6-116:
Parameters that can be written even if Pr. 77 = 1
Summary of Contents for FR-A700 EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Page 38: ...Enclosure design Installation 2 14 ...
Page 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Page 820: ...Parameter list with instruction codes Appendix A 50 ...
Page 825: ......