15
WT07936X05
5-4-2. Method 2: Installation using DIN rail
1. Have a metal control box ready.
2. Attach the supplied two DIN rail attachments to the EW-50 with the supplied roundhead screws (M3 × 12).
3. Attach the supplied DIN rail auxiliary bracket to the EW-50 with the supplied roundhead screws (M3 × 6).
4. Mount the DIN rail (not supplied) to the metal control box.
* Use a DIN rail of 35 mm (1-7/16 in) width.
Note
● To secure the strength, the screw pitch must be 200 mm (7-7/8 in) or less when DIN rail is mounted to the metal control box.
● The surface on which the EW-50 will be installed needs to be strong enough to support its weight (1.7 kg (4 lbs) each).
● Do not install the EW-50 where it may receive vibration.
● To avoid the contact of the DIN rail fixing screws with the DIN rail attachment, do not tighten the fixing screws at the shaded
areas in the figure below.
DIN rail attachment
(supplied)
Roundhead screw (M3 × 12)
(supplied)
Roundhead screw (M3 × 6)
(supplied)
DIN rail auxiliary bracket
(supplied)
EW-50
Max. 200 (7-14/16)
Unit: mm (in)
Do not tighten the fixing screw here.