Part Name
Check Points
Booster heater
Measure the resistance between the terminals with a tester.
Thermostat (90 °C) and thermal cut out (11 °C)
90 °C
Manual reset
water
thermostat
121 °C
Thermal
cut-out
AWG18
AWG18
9
10
Terminal
Normal
Abnormal
9-10
110(±35)mΩ
Open or Short
kW heater (0V, 1 phase)
1
2
2kW
AWG15 FEP WHITE
AWG15 FEP WHITE
Terminal
Normal
Abnormal
1-
26.5(+3/-1.3)Ω
Open or Short
+ 4kW heater (0V, 1 phase)
1
2
2kW
AWG15 FEP WHITE
AWG15 FEP WHITE
3
4
2kW
AWG13 FEP BLUE
AWG13 FEP BLUE
2kW
Terminal
Normal
Abnormal
1-
26.5(+3/-1.3)Ω
Open or Short
-4
13.3(+1.5/-0.6)Ω
Open or Short
+ 6kW heater (400V, phase)
5
6
AWG15 FEP WHITE
AWG15 FEP WHITE
AWG13 FEP BLUE
2kW
4
AWG15 FEP WHITE
2kW
2kW
2
3
1kW
1
1kW
1kW
AWG13 FEP BLUE
AWG13 FEP BLUE
Terminal
Normal
Abnormal
1-=-=1-
105.8(+11.8/-5)Ω
Open or Short
4-5=5-6=4-6
52.9(+5.8/-2.5)Ω
Open or Short
Earth leakage circuit breaker for heater
If a short circuit occurs on the booster heater, immersion heater, or each power
line, a short-circuit breaker will trip and power source will be blocked.
Eliminate the causes of short circuit and then turn on the breaker again.
Relay for heater
R S T A1 A2
U V W
When the applied voltage is not 230V AC across the terminals A1-A2, check the
terminals R-U, S-V, and T-W are open.
When the applied voltage is 230V AC across the terminals A1-A2, check the
terminals R-U, S-V, and T-W are short.
Flow switch
Flow
1
2
3
Measure the resistance between the terminals with a tester.
State of moving part
Normal
Abnormal
Paddle vertical (Flow < 5.5 l/min)
Open
Other than open
Paddle inclined (Flow > 5.5 l/min)
Short
Other than short
66
67
OCH531