2. Ethernet Communication
2.12 PROFINET
1
2
3
4
5
6
7
8
9
10
• Inverter Parameters (P12288 to P16383)
For the numbers and names of inverter parameters, refer to the parameter list of the Instruction Manual (Function).
NOTE
• Set 65520 (FFF0h) as a parameter value "8888" and 65535 (FFFFh) as "9999".
• When user defined cyclic communication data are selected (Telegram 102), the subindex cannot be specified (fixed to 0).
• Monitor Data (P16384 to P20479)
For details of the monitor codes and monitor items, refer to the description of
Pr.52
in the FR-E800 Instruction Manual
(Function).
NOTE
• Display of negative numbers during monitoring set in
Pr.290 Monitor negative output selection
is disabled.
• Inverter Control Parameters (P20480 to P24575)
*1
The data is written as a control input command for writing.
The data is read as the inverter status for reading.
PNU
Sub
Access
Name
Data Type
Description
Default
12288 to
16383
0, 1
R/W
Inverter Parameters
Array[n]
Unsigned16
The inverter parameter 12288
(3000h) is the PNU number.
Subindex 1 is set when
C3 (Pr.902), C4
(Pr.903), C6 (Pr.904), C7 (Pr.905), C39
(Pr.932), C41 (Pr.933), C43 (Pr.934), or
C45 (Pr.935)
is accessed.
Example)
C3 (Pr.902)
: PNU = 902 + 12288
= 13190 (3386h), sub = 1
—
PNU
Sub
Access
Name
Data Type
Description
Default
16384 to
20479
0
R
Monitor Data
Unsigned16
The monitor code + 16384 (4000h) is the
PNU number.
—
PNU
Sub
Access
Name
Data Type
Description
Default
20480 to
24575
0
R/W
Inverter Control
Parameters
Unsigned16
Inverter control parameter
—
PNU
Definition
Read/write
Remarks
20488 (5008h)
Inverter status / control input command
(extended)
Read/write
Refer to the following.
20489 (5009h)
Inverter status / control input command
Read/write
Refer to the following.
20981 (51F5h)
Fault record 1
Read/write
Being 2 bytes in length, the data is stored as 00
○○
h.
Refer to the lowest 1 byte for the error code. (For
details on error codes, refer to the list of fault displays
in the Instruction Manual (Maintenance).)
The fault history is batch-cleared by writing to 20981
(51F5h).
Set any value as data.
20982 (51F6h)
Fault record 2
Read
20983 (51F7h)
Fault record 3
Read
20984 (51F8h)
Fault record 4
Read
20985 (51F9h)
Fault record 5
Read
20986 (51FAh)
Fault record 6
Read
20987 (51FBh)
Fault record 7
Read
20988 (51FCh)
Fault record 8
Read
20989 (51FDh)
Fault record 9
Read
20990 (51FEh)
Fault record 10
Read
Summary of Contents for E820S
Page 5: ...4 ...
Page 177: ...176 2 Ethernet Communication 2 15 Ethernet communication parameters MEMO ...
Page 207: ...206 3 RS 485 Communication 3 5 MODBUS RTU MEMO ...
Page 211: ...210 4 Other Communication Options 4 2 Automatic connection with GOT MEMO ...
Page 212: ...211 CHAPTER 5 CHAPTER 5 4 5 6 7 8 9 10 Common Settings ...
Page 219: ...218 5 Common Settings MEMO ...
Page 220: ...219 CHAPTER 6 CHAPTER 6 4 5 6 7 8 9 10 Appendix 6 1 How to check specification changes 220 ...