Mitsubishi Electric City Multi PMFY-P100VBM-E Installation Manual Download Page 3

3

2. Installing the indoor unit

C

A

D

A

B

11

0

230

E

F

230

Fig. 2-2

2.2. Service space (Fig. 2-2)

• The dimensions of ceiling opening can be regulated within the range shown in

following diagram; so center the main unit against the opening of ceiling, ensuring
that the respective opposite sides on all sides of the clearance between them be-
comes identical.

A

Air intake

B

Air outlet

C

Ceiling panel

D

Min. 200 mm

E

Suspension bolts W3/8 or M10

F

Grille

2.3. Ceiling openings and suspension bolt installation

locations (Fig. 2-3)

• Make an opening in the ceiling 430 mm 

×

 960 mm in size. This functions as a check

window and will be needed later during servicing.

• If the dimensions are not accurate, when the grille is installed there may be gaps

between it and the indoor unit. This may result in dripping water or other problems.

• When deciding on placement, consider carefully the space around the ceiling and

make your measurements generous.

• Ceiling types and building construction differ. Therefore you should consult with the

builder and decorator.

A

The centers of the ceiling opening and the indoor unit should be aligned.

1

Outer side of grille

2

Ceiling opening

3

Bolt pitch

4

Electric box

• Using the installation template (top of the package) and the gauge (supplied as an

accessory with the grille), make an opening in the ceiling so that the main unit can
be installed as shown in the diagram. (The method for using the template and the
gauge are shown.)

• Use M10 (3/8") suspension bolts.

* Suspension bolts are to be procured at the field.

• After suspending the indoor unit, you will have to connect the pipes and wiring

above the ceiling. Once the location has been fixed and the direction of the pipes
has been determined, place the refrigerant and drainage pipes, the wiring for the
remote controller, and the wiring that connects the indoor and outdoor units in their
desired locations before suspending the indoor unit. This is especially important in
cases where the ceiling is already in existence.

1

Wooden structures (Fig. 2-4)

• Use tie beams (single storied houses) or second floor beams (two story houses) as

reinforcing members.

• Wooden beams for suspending air conditioners must be sturdy and their sides

must be at least 6 cm long if the beams are separated by not more than 90 cm and
their sides must be at  least 9 cm long if the beams are separated by as much as
180 cm. The size of the suspension bolts should be ø10 mm (3/8"). (The bolts do
not come with the unit.)

• Use channel, duct and other parts procured locally to suspend the indoor unit.

2

Ferro-concrete structures (Fig. 2-5)

Secure the suspension bolts using the method shown, or use steel or wooden hang-
ers, etc. to install the suspension bolts.

A

247

69

53

17.5

17.5

20

20

28

28

45

20

45

20

340 

3

430 

2

470 

1

26

74.5

20

26

74.5

20

759

811 

3

960 

2

1000 

1

4

Fig. 2-3

(mm)

I

Suspension bolts M10 (3/8") (procure lo-
cally)

J

Steel reinforcing rod

K

C channel

L

Channel suspension bracket

M

M10 suspension bolt

D

Ceiling panel

E

Rafter

F

Beam

G

Roof beam

H

Use inserts rated at 100-150 kg each (pro-
cure locally)

2.4. Unit suspension procedures (Fig. 2-6)

Procure 3/8" bolts or M10 bolts locally.
• Adjust the length of the bolt’s protrusion from the ceiling surface beforehand.

*1. When using an extra upper nut in suspending the unit, in some cases you may

have to add it later.

A

Suspension bolt

B

Ceiling panel

C

Nut

D

Washer (with insulation) 

2

E

Washer (without insulation) 

1

A
C
D

E
C

 *1

B

Min. 20

Min. 30

(mm)

D

E

F G

340

811

K

L

M

J

H

I

Fig. 2-4

Fig. 2-6

Fig. 2-5

(mm)

(mm)

Summary of Contents for City Multi PMFY-P100VBM-E

Page 1: ... ÛË Ú Î ÏÂ ÛÙÂ È ÛÂÙÂ ÚÔÛÂ ÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÚÈÓ Ú ÛÂÙÂ ÙËÓ ÂÁÎ Ù ÛÙ ÛË ÙË ÌÔÓ ÎÏÈÌ ÙÈÛÌÔ MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado MONTAJ ELK TABI Emniyetli ve do ru biçimde nas l kullan laca n ö renmek için lütfen klima cihaz n monte etmeden önce bu elkitab n dikkatle okuyunuz...

Page 2: ...s etc 1 Safety precautions 2 2 Installing the indoor unit 2 3 Refrigerant pipe and drain pipe 4 4 Electrical work 6 5 Installing the grille 7 6 Test run Fig 6 1 9 1 Safety precautions Indicates an action that must be avoided Indicates that important instructions must be followed Indicates a part which must be grounded Indicates that caution should be taken with rotating parts Indicates that the ma...

Page 3: ... been fixed and the direction of the pipes has been determined place the refrigerant and drainage pipes the wiring for the remote controller and the wiring that connects the indoor and outdoor units in their desired locations before suspending the indoor unit This is especially important in cases where the ceiling is already in existence 1 Wooden structures Fig 2 4 Use tie beams single storied hou...

Page 4: ...ter in it Fig 2 8 Make sure that any slant in the unit after installation is less than 0 5 degrees approx 6 mm on the long dimension of the unit 5 Tighten all the nuts Fig 2 9 A Suspension bolt 3 8 or M10 B Clear plastic tubing C Underside of bracket D Secure front panel here E Make these surfaces are flush with each other 0 3 mm 2 5 Fresh air intake hole Fig 2 10 At the time of installation use t...

Page 5: ...Fig 3 4 Use O D ø26 mm PVC TUBE for drain piping and provide 1 100 or more down ward slope Be sure to connect the piping joints using adhesive of polyvinyl chloride family Observe the figure for piping work Use attached drain hose to change the pipe extraction direction 1 Correct piping 2 Wrong piping A Insulation 9 mm or more B Downward slope 1 100 or more C Support metal K Air bleeder L Raised M...

Page 6: ...er Connect the remote controller s transmission cable within 10 m using a 0 75 mm2 core cable If the distance is more than 10 m use a 1 25 mm2 junction cable 1 MA Remote controller Connect the 1 and 2 on indoor unit TB15 to a MA remote controller Non polar ized 2 wire DC 9 to 13 V between 1 and 2 MA remote controller 2 M NET Remote controller Connect the M1 and M2 on indoor unit TB5 to a M NET rem...

Page 7: ...mm2 2 M NET Remote control cables Kind of remote control cable Shielding wire MVVS Cable diameter More than 0 5 to 1 25 mm2 Remarks When 10 m is exceeded use cable with the same specifications as transmission line wiring 3 MA Remote control cables Kind of remote control cable 2 core cable unshielded Cable diameter 0 3 to 1 25 mm2 Fig 4 3 SW14 0 SW11 0 SW12 0 1 2 3 4 5 6 7 8 9 10 ON OFF SW1 SW5 220...

Page 8: ...ng bolts 2 and securing screws 3 in the center three places Finally tighten the securing bolts 2 in the four places at left and right At this point make sure there are no gaps between the indoor unit and the front panel and between the front panel and the ceiling surface If there are gaps the wind may come in and it may cause water to drip Fig 5 6 Tighten the securing bolts 2 and securing screws 3...

Page 9: ... adjustment button Check that the wind speed is changed 4 Press Up down airflow selection button to change wind direction 5 Press ON OFF button to clear test run Test run stops A Lighting in operation B Displaying inspection code C Displaying remaining test run time D Displaying indoor unit s liquid pipe temperature E Displaying test run Note The 2 hour set timer is activated to automatically stop...

Page 10: ... EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U328H02 The product at hand is based on the following EU regulations ...

Reviews: