6. Test run
6.3. Test run
The following 3 methods are available.
6.3.1. Using wired remote controller (Fig. 6-2)
▌
1
[ON/OFF] button
Press to turn ON/OFF the indoor unit.
▌
2
[SELECT] button
Press to save the setting.
▌
3
[RETURN] button
Press to return to the previous screen.
▌
4
[MENU] button
Press to bring up the Main menu.
▌
5
Backlit LCD
Operation settings will appear.
When the backlight is off, pressing any button turns the backlight on and it will
stay lit for a certain period of time depending on the screen.
When the backlight is off, pressing any button turns the backlight on and does
not perform its function. (except for the [ON/OFF] button)
▌
6
ON/OFF lamp
This lamp lights up in green while the unit is in operation. It blinks while the
remote controller is starting up or when there is an error.
▌
7
Function button [F1]
Main display: Press to change the operation mode.
Menu screen: The button function varies with the screen.
▌
8
Function button [F2]
Main display: Press to decrease temperature.
Main menu: Press to move the cursor left.
Menu screen: The button function varies with the screen.
▌
9
Function button [F3]
Main display: Press to increase temperature.
Main menu: Press to move the cursor right.
Menu screen: The button function varies with the screen.
▌
0
Function button [F4]
Main display: Press to change the fan speed.
Menu screen: The button function varies with the screen.
Controller interface
Fig. 6-2
6.1. Before test run
► After completing installation and the wiring and piping of the indoor and
outdoor units, check for refrigerant leakage, looseness in the power supply
or control wiring, wrong polarity, and no disconnection of 1 phase in the
supply.
► Use a 500-volt megohmmeter to check that the resistance between the power
supply terminals and ground is at least 1.0 MΩ.
► Do not carry out this test on the control wiring (low voltage circuit) terminals.
Warning:
Do not use the air conditioner if the insulation resistance is less than 1.0 MΩ.
Caution:
• Turn on the power at least 12 hours before starting operation.
- Starting operation immediately after turning on the main power switch can result
in severe damage to internal parts. Keep the power switch turned on during the
operational season.
• Do not touch the switches with wet fingers.
- Touching a switch with wet fingers can cause electric shock.
• Do not operate the air conditioner with the panels and guards removed.
- Rotating, hot, or high-voltage parts can cause injuries.
• Do not turn off the power immediately after stopping operation.
- Always wait at least five minutes before turning off the power. Otherwise, water
leakage and trouble may occur.
• When water has been supplied to the water pipework, purge the system of
air. The details of air purging can be found separately in the water circuit
maintenance manual.
E
D
C
B
A
Fig. 6-1
6.2. Air purging
6.2.1. The details of air purging
As for the details of air purging, please refer to the water circuit maintenance
manual included in the package of the HBC controller, or hydro unit.
6.2.2. The air vent valve of indoor unit (Fig. 6-1)
1
Remove the air purge valve cover.
2
Turn the knob on the air purge valve to release the air.
A
Air purge valve
B
Air purge valve cover (Tightening torque: 1.3 ± 0.3 N·m)
C
Screw
D
Outlet (To HBC/optional VALVE KIT)
E
Inlet (From HBC/hydro unit)
4
3
2
1
5
6
7
8
9
0
Function buttons
15
en
BT79D035H01_en.indd 15
2019/07/30 11:12:49