6. Test run (Fig. 6-1)
Fig. 6-2
Water supply pump
Water (about 1000cc)
Drain plug
Pour water through outlet
. Be careful not to spray water
into the drain pump mechanism.
6.3. Check of drainage (Fig. 6-2)
• Ensure that the water is being properly drained out and that no water is leaking
from joints.
When electric work is completed.
. Pour water during cooling operation and check.
When electric work is not completed.
. Pour water during emergency operation and check.
* Drain pan and fan are activated simultaneously when single phase 208/230V is
turned on to L1 and L2 on terminal block after the connecter (SWE) on controller
board in the electrical branch box is set to ON.
Be sure to turn it back to the former state after work.
Fig. 6-1
°C
°C
SIMPLE
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK
DAY
MONITOR/SET
CLOCK
ON/OFF
TEST RUN
COOL, HEAT
A
ON/OFF button
B
Test run display
C
Liquid pipe (Indoor unit)
temperature display
D
ON/OFF lamp
E
Power display
F
Error code display
Test run remaining time display
G
Set temperature button
H
Mode selection button
I
Air direction button
M
TEST button
N
Fan Speed button
O
Louver button
Do not carry out this test on the control wiring (low voltage circuit) termi-
nals.
Warning:
Do not use the air conditioner if the insulation resistance is less than 1.0 M
"
.
6.1. Before test run
After completing installation and the wiring and piping of the indoor and
outdoor units, check for refrigerant leakage, looseness in the power sup-
ply or control wiring, wrong polarity, and no disconnection of one phase
in the supply.
Use a 500-volt megohmmeter to check that the resistance between the
power supply terminals and ground is at least 1.0 M
"
.
6.2. Test run
Using wired remote controller (Fig. 6-1)
1
Turn on the power at least 12 hours before the test run.
2
Press the [TEST] button twice. “TEST RUN” liquid crystal display
3
Press the [Mode selection] button and switch to the cooling (or heating) mode.
Make sure that cold (or warm) wind is blown out.
4
Press the [Fan speed] button. Make sure that the wind speed is switched.
5
Press the [Air direction button] or [Louver button].
Check operation of the vane or louver.
6
Check operation of the outdoor unit fan.
7
Release test run by pressing the [ON/OFF] button. Stop
8
Register a telephone number.
The telephone number of the repair shop, sales of
fi
ce, etc., to contact if an error
occurs can be registered in the remote controller. The telephone number will be
displayed when an error occurs. For registration procedures, refer to the opera-
tion manual for the indoor unit.
Note:
• If an error code is displayed on the remote controller or if the air condition-
er does not operate properly, refer to the outdoor unit installation manual
or other technical materials.
• The OFF timer is set for the test run to automatically stop after 2 hours.
• During the test run, the time remaining is shown in the time display.
• During the test run, the temperature of the indoor unit refrigerant pipes is
shown in the room temperature display of the remote controller.
• When the VANE or LOUVER button is pressed, the message “NOT AVAILA-
BLE” may appear on the remote controller display depending on the indoor
unit model, but this is not a malfunction.