• V1 and V2
V1 and V2 are the breaker coefficient.
V1: Breaker coefficient of rated current
V2: Breaker coefficient of current sensitivity
The values of V1 and V2 differ from depending on the model. Therefore, please refer to IM of each model.
• C : Multiple of tripping current at tripping time 0.01 s
Please pick up “C” from the tripping characteristic of the breaker.
<Example of “F2” calculation>
*Condition : PKFY-NLMU × 2 + PLFY-NEMU × 2 + PEFY-NMAU × 1
V1 of PKFY-NLMU = 19.8, V1 of PLFY-NEMU = 19.8, V1 of PEFY-NMAU = 38, C = 8 (refer to right sample chart)
F2 = 19.8 × 2/8 + 19.8 × 2/8 + 38 × 1/8
= 14.65
→ 15 A breaker (Tripping current = 8 × 15 A at 0.01 s)
*3 Current sensitivity is calculated using the following formula.
G1 = V2 × (Quantity of indoor unit 1) + V2 × (Quantity of indoor unit 2) + V2 × (Quantity of indoor unit 3)
+ ··· + V3 × (Wire length [km])
<Example of “G1” calculation>
*Condition : PKFY-NLMU × 2 + PLFY-NEMU × 2 + PEFY-NMAU × 1
V2 of PKFY-NLMU = 2.4, V2 of PLFY-NEMU = 2.4, V2 of PEFY-NMAU = 1.6, Wire thickness and length: 1.5 mm
2
(AWG14) 0.2 km
G1 = 2.4 × 2 + 2.4 × 2 + 1.6 × 1 + 48 × 0.2
= 20.8
As a result , current sensitivity is 30 mA 0.1 sec or less.
V1
V2
PKFY-NLMU
19.8
2.4
Fig. 6-2
C
C
C
C
C
A
B
D
D
C
TB2
TB5
TB15
S
1 2
M1
L1 L2
M2
A
B
~208/230 V
~208/230 V
6. Electrical work
6.2. Power supply wiring
• Wiring size must comply with the applicable local and national codes.
• Use copper supply wires.
Use UL wires rated 300 V or more for the power supply cords.
• Install a ground wire longer than other cables.
• A switch with at least 3 mm, 1/8 inch contact separation in each pole shall be
provided by the air conditioner installation.
[Fig. 6-2]
A
Ground-fault interrupter
B
Local switch/Wiring breaker
C
Indoor unit
D
Pull box
Warning:
Never splice the power cable or the indoor-outdoor connection cable,
otherwise it may result in a smoke, a fire or communication failure.
Total operating current of the indoor
unit
Minimum wire thickness (mm²/AWG)
Breaker for wiring
(NFB)
Ground-fault interrupter *1
Main cable
Branch
Ground
Capacity
Fuse
F0 = 15 A or less *2
2.1/14
2.1/14
2.1/14
15
15
15
15 A current sensitivity *3
F0 = 20 A or less *2
3.3/12
3.3/12
3.3/12
20
20
20
20 A current sensitivity *3
F0 = 30 A or less *2
5.3/10
5.3/10
5.3/10
30
30
30
30 A current sensitivity *3
Apply to IEC61000-3-3 about max. permissive system impedance.
*1 The Ground-fault interrupter should support inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
*2 Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.2
F2 = {V1 × (Quantity of indoor unit 1)/C} + {V1 × (Quantity of indoor unit 2)/C} + {V1 × (Quantity of indoor unit 3)/C} +
···
6000
600
60
10
1
1
2
3 4
6 8
C
10
20
Sample chart
Tripping T
ime
[s]
Rated Tripping current (x)
0.1
0.01
SAMPLE
G1
Current sensitivity
30 or less
30 mA 0.1 sec or less
100 or less
100 mA 0.1 sec or less
Wire thickness
V3
1.5 mm
2
, AWG14
48
2.5 mm
2
, AWG13
56
4.0 mm
2
, AWG11
66
en
~ 208/230 V
Indoor
unit 1
Indoor
unit 1
Indoor
unit 2
Indoor
unit 3
Indoor
unit 3