background image

13

GB

D

F

I

NL

E

P

GR

RU

TR

7.5. External I/O Specifications

I/O Specifications

Input

7.4. Setting addresses

(Be sure to operate with the main power turned OFF.)

There are two types of rotary switch setting available: setting addresses 1 to 9
and over 10.
<How to set addresses>

Example: If Address is “3”, remain SW12 (for over 10) at “0”, and match
SW11(for 1 to 9)  with “3”.

 Caution:

Setting the address of the indoor unit controller

For the Model 500
The top side indoor controller address of the indoor unit must always be
odd number. The bottom side indoor controller address must be 1 more
than the top side indoor controller address.

Setting the address of the outdoor unit controller
The address must be 50 more than the address of the indoor units using
the same refrigerant.

* If the address is not correctly set, operation will not run correctly.

After setting the address, enter the set address on the product nameplate on the
front panel using a permanent marker.

The rotary switches are all set to “0” when shipped from the factory. These
switches can be used to set unit addresses.

The determination of indoor unit addresses varies with the system at site. Set
them referring to technical data.

If connecting a controller inside a central controller, the address of the two con-
trollers inside the Model 500 indoor unit must always be set in the same group.

[Fig. 7.4.1]

 

(P.5)

• When there is a single Model 250 unit

A

CN41 as it is

*1 The numbers shown in the square ( 

 ) are addresses.

*2 The Model 250 indoor unit contains one indoor controller board.

[Fig. 7.4.2]

 

(P.5)

• When there is a single Model 500 unit

A

Replace CN41 with CN40

B

CN41 as it is

* The Model 500 indoor unit contains two indoor controller boards.

[Fig. 7.4.3]

 

(P.5)

• When connected to G-50

A

CN41 as it is

B

Group 1

C

Group 2

D

Power supply unit

E

DC Power supply (DC 12V)

Function

Start/Stop

Application

Turning ON/
OFF the indoor
unit

Signal specifications

Pulse [Factory setting: Dip SW1-9 ON]
(a-contact with voltage/without voltage)*1

<With voltage>

Power Source: DC12~24V
Electrical Current:
Approximately 10mA (DC12V)

<Standard Pulse>

* 1 Use minute-current contact  (DC12V 1mA)

 Caution:

1. Wiring should be covered by insulation tube with supplementary insula-

tion.

2. Use relays or switches with IEC or equivalent standard.
3. The electric strength between accessible parts and control circuit should

have 2750 V or more.

Daisy-chain terminals M1 and M2 of the terminal block for transmission line for
centralized control (TB7) on each outdoor unit (OC). * Only use shielded ca-
bles.

Disconnect the male power supply connector from CN41 and connect it to
CN40 on only one outdoor unit.

Daisy-chain the S terminal of terminal block (TB7) on each outdoor unit with
each other with the grounding wire of the shielded cable.

Connect the S terminal of terminal block (TB7) on the outdoor unit whose male
power supply switch connector has been connected to CN40 to the earth ter-
minal   on the control box.

Install a remote controller following the manual supplied with the remote con-
troller.

Connect the “1” and “2” on indoor unit TB15 to a MA remote controller. (Non-
polarized 2-wire)

[Fig. 7.2.1]

 

(P.3) MA Remote controller

<A> Model 250

<B> Model 500

A

Terminal block for indoor transmission cable

B

Terminal block for outdoor transmission cable

C

MA Remote controller

DC 9 to 13 V between 1 and 2 (MA remote controller)

[Fig. 7.2.2]

 

(P.3) MA Remote controller

<A> Model 250

<B> Model 500

A

Non-polarized

B

Upper level

C

Lower level

D

MA Remote Controller

Note:
1. Ensure that the wiring is not pinched when fitting the terminal box cover.

Pinching the wiring may cut it.

2. Put the transmission cable earth via the outdoor unit’s earth terminal 

to the ground.

 Caution:

Install wiring so that it is not tight and under tension. Wiring under tension
may break, or overheat and burn.

Fix power source wiring to control box by using buffer bushing for tensile force.
(PG connection or the like.) Connect transmission wiring to transmission ter-
minal block through the knockout hole of control box using ordinary bushing.

After wiring is complete, make sure again that there is no slack on the connec-
tions, and attach the cover onto the control box in the reverse order removal.

7.3. Connecting electrical connections

(Be sure to prevent terminal screws from loosening.)

 Caution:

Fix the site wiring firmly in place with wiring clamps.

Ensure that wiring installation work does not result in tension being ap-
plied to the wiring. Such tension may result in breaks in wiring, and con-
sequent overheating, smoke, or flame.

Step 1. Turn the key in the center of the panel at the bottom of the unit to

open the panel. Next, remove the four screws in the control box cover
to remove the cover.

Step 2. Install electrical wiring, internal and external connecting wiring, and

earth wiring, as shown in [Fig. 7.3.1]. Refer to “7.5. External I/O Speci-
fications” if installing wiring when external I/O terminals are used.

Step 3. When wiring is complete, check for less connections and wiring mis-

takes, and close the panel.

<In the case of two refrigerant circuits>
Changes to the connector connection and switch settings are required as shown in
[Fig.7.3.2].

[Fig. 7.3.1]

 

(P.4) MA Remote controller

<A> Model 250

<B> Model 500

A

Transformer

B

External I/O board

C

No.1 Transmission line terminal block

D

No.2 Transmission line terminal block (Note: Connect to top terminal block)

E

Connect transmission line to outdoor unit

F

Fix in place after connecting wiring.

G

Earth

H

Fuse

I

Control box

J

Bottom panel

[Fig. 7.3.2]

 

(P.4)

<When connected to a 2-refrigerant circuit>
The unit is shipped ready to be connected to a single-refrigerant circuit.
When connected to a 2-refrigerant circuit, make the connection changes and switch
setting changes (SW 2, 3, and 4 on both No. 1 and No.2 boards) as shown in [Fig. 7.3.2]
on site.

over 200ms

(Pulse interval)

over 200ms

(Pulse powering time)

Level [Dip SW1-9 OFF]
Short: operate
Open: stop

Level
Refer to the wiring diagram <Dehumidifica-
tion command>.

Sending a
command to
perform
dehumidifica-
tion with
priority

Dehumidifi-

cation signal

Summary of Contents for City Multi PFD-P250 500VM-E

Page 1: ...ut accident et vous assurer d une utilisation correcte MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente questo manuale di installazione prima di installare il condizionatore d aria MANUAL DE INSTALAÇÃO Para um uso seguro e corre...

Page 2: ...quid A N Main drain piping joint outlet Rp1 1 4 W Air outlet O Emergency drain piping joint outlet Rp1 1 4 P As seen from bottom face A 220 68 68 68 124 320 710 680 135 68 124 120 171 150 440 185 135 Rp1 1 4 A Q Location of refrigerant piping R Refrigerant piping ø28 58 Brazed gas S Refrigerant piping ø15 88 Brazed liquid W Air outlet W Air outlet V As seen from bottom face A U Emergency drain pip...

Page 3: ...pper level TB5 1 C Lower level TB15 B2 S S A1 B1 TB5 2 DC10 13V A B 1 2 A1 1 2 A Non polarized D MA Remote Controller Upper level TB5 C Lower level TB15 B1 S B B Fig 7 2 2 A Model 250 A Model 250 B Model 500 B Model 500 100mm or more 100mm or more A Drain pan B Drain hose C As seen from front of unit D Main drain piping on site E Emergency drain piping on site G Drain piping on site for humid filt...

Page 4: ...erant circuit Remove the LEV2B connector from the adapter board and connect it to CN60 on No 2 board CN60 6 5 4 3 2 1 6 5 4 3 2 1 CN3A CN2M 1 2 2 1 3 No 2 board Connect the connectors to CN3A and CN2M on No 2 board When connected to a single refrigerant circuit factory setting When connected to t a 2 refrigerant circuit Model 500 SW2 SW3 SW4 ON 1 2 3 4 5 6 1 2 3 4 5 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 ...

Page 5: ... S M1 TB15 MA 1 2 M2 A B S 52 OC PUHY P250YGM A 02 TB15 MA 1 2 A B TB3 TB7 M1 M2 M1 M2 S M1 TB5 TB5 1 TB5 2 M2 S 51 OC IC model 250 IC model 500 01 TB3 TB7 M1 M2 M1 M2 S M1 TB15 MA 1 2 M2 A B S 53 OC 03 04 M1 M2 S TB3 TB7 M1 M2 M1 M2 S 54 OC OC A B S A B S TB2 2 The Model 250 indoor unit contains one indoor controller board A CN41 as it is A Replace CN41 with CN40 B Group 1 C Group 2 A CN41 as it ...

Page 6: ...to a two refrigerant circuit connect the short circuit plate that is supplied with the unit to the appropriate terminals on the external input output board Without the short circuit plate the unit will not function properly Don t connect the short circuit plate in case of a one refrigerant circuit Caution External input output board The case of with voltage input Connecting the short circuit plate...

Page 7: ...emove the front panel L Bolt 2 M Screw Detailed view of section A B Model 500 Heat exchanger unit top Fan unit bottom Decoration panel Height mm 1120 510 1 860 Dimensions and weight of parts Length of protruded pipe removable Width mm P250 1380 P500 1980 P250 1380 P500 1980 Depth mm 780 780 Weight kg P250 158 P500 246 P250 128 5 P500 159 P250 93 5 P500 115 Fig 10 0 2 A Model 250 B Model 500 A Line...

Page 8: ...iping side C Fan B Model 500 Fig 10 0 5 A Model 250 No 1 board G Connector location on the board A CN60 B CN31 C CN20 D CN21 E CN29 F CN22 G Connector location on the board J Connector location on the adapter board No 1 board B CN31 C CN20 D CN21 E CN29 Same with the No 2 board H LEV2B I LEV2A B Model 500 Board No No 1 Connector CN31 CN20 CN21 CN29 CN60 Table 1 Wire mark 1 S1 E1 G1 V1 Connector co...

Page 9: ...efrigerant concentration from exceeding the safety limit even if the refrigerant should leak Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceeded Should the refrigerant leak and cause the safety limit to be exceeded hazards due to lack of oxygen in the room could result When moving and reinstalling the air conditioner consult the dealer or an author...

Page 10: ...orate Since R410A does not contain any chlorine gas leak detectors for conven tional refrigerants will not react to it Do not use a charging cylinder Using a charging cylinder may cause the refrigerant to deteriorate Be especially careful when managing the tools If dust dirt or water gets in the refrigerant cycle the refrigerant may deterio rate 1 3 Before getting installed Caution Do not install ...

Page 11: ...ze Pipe size Insulating material s thickness 6 4 mm to 25 4 mm More than 10 mm 28 6 mm to 38 1 mm More than 15 mm 2 If the unit is used on the highest story of a building and under conditions of high temperature and humidity it is necessary to use pipe size and insulating material s thickness more than those given in the table above 3 If there are customer s specifications simply follow them 4 1 H...

Page 12: ...braces to prevent it from waving Never provide any air vent pipe Otherwise drain may be ejected 3 Do not provide any odor trap at the drain discharge port 4 Put the end of the drain piping in a position where no odor is generated 5 Do not put the end of the drain piping in any drain where ionic gases are generated 6 Check drainage by pouring water into the drain pan and check to see that it drains...

Page 13: ... on the control box Install a remote controller following the manual supplied with the remote con troller Connect the 1 and 2 on indoor unit TB15 to a MA remote controller Non polarized 2 wire Fig 7 2 1 P 3 MA Remote controller A Model 250 B Model 500 A Terminal block for indoor transmission cable B Terminal block for outdoor transmission cable C MA Remote controller DC 9 to 13 V between 1 and 2 M...

Page 14: ...y I Operation status J Fault K External I O board L Terminal block connection M Connector connection N Wiring distance 100 m or less A With voltage input D No voltage input G Relay contact output Settings for indoor unit Check that the following settings have been entered when using external input 1 Control board DIP SW3 8 ON Set to ON prior to shipment from factory External input disabled when se...

Page 15: ...cedures below when separating the sections Necessary tools and materials Ratchet wrench with a socket size of 17 mm for M10 General tools Cable ties for wires Gray vinyl tape for pipes Supporting wood piece Height 800 mm x Width 100 mm x Thickness 20 mm 1 piece 1 Removing the decoration panel and filter Model 250 Remove the front panels 2 rear panels 2 and the side panels 2 in this order by removi...

Page 16: ...together When the frames will not fit back into place loosen bolt 2 as shown in Fig 10 0 1 place the frames and tighten bolt 2 Be sure to securely tighten all screws and bolts tightening torque 74N m Using Fig 10 0 5 and Table 1 as a reference connect all connectors correctly Use a cable tie and bundle the wires as they were before Keep torch flame away from the insulation material on the drain pa...

Page 17: ...act address telephone number on this manual before handing it to the customer The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commer cial and light industrial environment ...

Reviews: