3.2.  Operation mode

Each pressing of the [F1] button cycles through 

the following operation modes. 

Select the desired operation mode.

Cool

Drying

Fan

Auto

Heat

Setback

*  Operation modes that are not available for the 

connected indoor unit will not appear on the 

display.

*  Depending on the indoor unit model, either 

one or two set temperatures (single or dual set 

point(s)) can be set for Auto mode.

What the blinking mode icon means

The mode icon will blink when other indoor units in the same refrigerant 

system (connected to the same outdoor unit) are already operated in a 

different mode. In this case, the rest of the units in the same group can 

only be operated in the same mode.

Drying mode

• 

The indoor fan turns to the low-speed operation, disabling the change of fan speed.

• 

Dry operation cannot be carried out at room temperature of less than 18°C.

• 

The dry is a microcomputer-controlled dehumidifying operation which controls 

excessive air-cooling according to the room temperature of your choice. (Not usable 

for heating.)

1.  Until reaching room temperature of your choice 

The compressor and indoor fan function is linked motion according to the change of 

the room temperature and automatically repeat ON/OFF.

2.  When reaching room temperature of your choice 

Both the compressor and indoor fan stop. 

When stop continues for 10 minutes, the compressor and indoor fan are operated 

for 3 minutes to keep the humidity low.

Heat mode

“DEFROST” display

Displayed only during the defrosting operation.

“STAND BY” display

Displayed from the start of heating operation until the moment warm air blows out.

 Caution:

•  Never expose your body directly to cool air for a long time. Excessive 

exposure to cool air is bad for your health, and should therefore be avoided.

•  When the air-conditioner is used together with burners, thoroughly ventilate 

the area. Insufficient ventilation can result in accidents due to oxygen 

deficiency.

• 

Never place a burner at a place where it is exposed to the airflow from the air-

conditioner. Doing so can result in imperfect combustion of the burner.

•  The microcomputer functions in the following cases:

 

-

Air does not blow out when heating starts.

•  To prevent any cool air from escaping, the indoor fan is gradually switched 

in sequence from faint airflow/weak airflow/set airflow according to the 

temperature rise of the blown out air. Wait a moment until the airflow comes out 

naturally.

 

-

The fan is not moving at the set speed.

• 

In some models, the system switches over to faint airflow when the temperature 

of the room reaches the set temperature. In other cases, it stops to prevent any 

cool air from escaping during the defrosting operation.

 

- Air flows out even if operation is stopped.

•  Approximately 1 minute after the stop of operation, the indoor fan sometimes 

rotates to eliminate extra heat generated by the electric heater, etc. The fan 

speed comes to low or high.

Auto (dual set point) and Setback modes

When the operation mode is set to the Auto (dual set point) mode or the Setback mode, 

two set temperatures (one each for cooling and heating) can be set. Depending on the 

room temperature, indoor unit will automatically operate in either the cooling or heating 

mode and keep the room temperature within the preset range.

Differences between the two modes

• 

Auto (dual set point) mode 

The set temperatures that are specified for the Cool/Drying mode and the Heat 

mode will be used to automatically control the room temperature to stay within the 

set temperatures. This mode is especially effective during the in-between seasons, 

when the temperature difference between the highest and the lowest is large and 

both heating and cooling modes are used within the same day.

• 

Setback mode 

Room temperature is controlled to stay within the set temperature range that 

is specified for the Setback mode. By leaving sufficient temperature differential 

between the set temperature for cooling (upper limit) and heating (lower limit), 

it is possible to keep the room temperature within the specified range without 

overworking the air conditioners. This setting will be especially effective during 

periods of non-occupancy.

3.3.  Set temperature

<Cool, Drying, Heat, and Auto (single set point)>

Press the [F2] button to decrease the set 

temperature, and press the [F3] button to 

increase.

*  Refer to the table below for the settable 

temperature range for different operation 

modes.

*  Set temperature cannot be set for the Fan 

mode.

*  Depending on the Temperature unit setting, 

temperatures will decrease or increase by 

0.5ºC, 1ºC, 1ºF, or 2ºF increments.

<Auto (dual set point) or Setback mode>

The current set temperatures will appear.

Press the [F2] or [F3] button to display the 

Settings screen.

Set temp. 
(Cool)

Set temp. 
(Heat)

Operation pattern during Auto (dual set point) mode

The room temperature 

changes corresponding 

to the change in the 

outside temperature.

Heat

Cool

Heat

Cool

Room  
temperature

Operation pattern during Setback mode

Set temp. 
(Setback_Cool)

Set temp. 
(Setback_Heat)

Heat

Cool

Heat

Cool

The room temperature 

changes corresponding 

to the change in the 

outside temperature.

Room  
temperature

Set temperature for cooling

Set temperature for heating

Summary of Contents for City Multi PEFY-P06NMAU-E4

Page 1: ... este manual de instrucciones hasta el final antes de poner en marcha la unidad de aire acondicionado para garantizar un uso seguro y correcto MANUEL D UTILISATION Pour une utilisation correcte sans risques veuillez lire le manuel d utilisation en entier avant de vous servir du climatiseur Air Conditioners INDOOR UNIT PEFY P06 08 12 15 18 24 27 30 36 48 54NMAU E4 ...

Page 2: ...starting up or when there is an error The functions of the function buttons change depending on the screen Refer to the button function guide that appears at the bottom of the LCD for the functions they serve on a given screen When the system is centrally controlled the button function guide that corresponds to the locked button will not appear Main display Main menu Menu screen Function button F1...

Page 3: ...function is enabled appears when the timer is disabled by the centralized control system appears when the HOLD function is enabled Appears when the Weekly timer is enabled Appears while the units are operated in the energy save mode Will not appear on some models of indoor units Appears while the outdoor units are operated in the silent mode Appears when the built in thermistor on the remote contr...

Page 4: ...n violation of applicable laws MITSUBISHI ELECTRIC CORPORATION cannot be held responsible for malfunctions or accidents resulting from the use of the wrong type of refrigerant 1 Outdoor unit Warning The outdoor unit must be installed on a stable level surface in a place where there is no accumulation of snow leaves or rubbish Do not stand on or place any items on the unit You may fall down or the ...

Page 5: ...ce Improper repair work can result in water leakage electric shock fire etc If the remote controller displays an error indication the air conditioner does not run or there is any abnormality stop operation and contact your dealer Leaving the unit as it is under such conditions can result in fire or failure If the power breaker is frequently activated get in touch with your dealer Leaving it as it ...

Page 6: ...switches over to faint airflow when the temperature of the room reaches the set temperature In other cases it stops to prevent any cool air from escaping during the defrosting operation Air flows out even if operation is stopped Approximately 1 minute after the stop of operation the indoor fan sometimes rotates to eliminate extra heat generated by the electric heater etc The fan speed comes to low...

Page 7: ...lues are used for the set temperature for Heat mode and the heating set temperature for Auto mode dual set points 4 The cooling and heating set temperatures can be set under the following conditions The cooling set temperature is greater than the heating set temperature The difference between the cooling and heating set temperatures is equal or greater than the minimum temperature difference that ...

Page 8: ...ights are out except the ruled line and clock When other indoor units are engaged in cooling operation the machine stops after running a drain up mechanism for 3 minutes when air cooling operation is stopped Wait for 3 minutes The sound of the exhaust and the rotation of the motor can be heard intermittently after stop of running All lights are out except the ruled line and clock When other indoor...

Page 9: ...the absolute use of exclusive circuits The use of other products with the power source can result in burnt out beakers and fuses Never connect the grounding wire to a gas pipe water pipe arrester or telephone grounding wire For details consult with your dealer In some types of installation sites the installation of an earth leakage breaker is mandatory For details consult with your dealer Regardin...

Page 10: ...18 742 883 618 742 883 External staticpressure 2 in WG 0 14 0 20 0 28 0 40 0 60 Pa 35 50 70 100 150 Sound level Low Mid High 2 3 dB A 31 35 39 31 35 39 31 35 39 Filter Standard filter Item Model P36 P48 P54 Power source 208 230 V 60 Hz Cooling capacity 1 Heating capacity 1 Btu h 36 000 40 000 48 000 54 000 54 000 60 000 kW 10 6 11 7 14 1 15 8 15 8 17 6 Dimension Height mm in 250 9 13 16 Width mm i...

Page 11: ...nce est en cours de démarrage ou en cas d erreur Les fonctions réalisées par les touches varient en fonction de l écran Consultez le guide de fonction des touches en bas de l écran LCD pour voir les fonctions correspondant à un écran donné Lorsque le système est commandé de manière centralisée le guide de la fonction de la touche qui correspond à la touche verrouillée ne s affiche pas Écran princi...

Page 12: ...on On Off timer ou Arrêt auto timer est activée s affiche lorsque le timer est désactivé par le système de contrôle centralisé s affiche lorsque la fonction de verrouillage est activée S affiche lorsque le programmateur hebdomadaire est activé S affiche lorsque le système est en mode économie d énergie Ceci ne s affichera pas sur certains modèles d unités intérieures S affiche lorsque les unités e...

Page 13: ... ce qu ils ne puissent pas jouer avec l appareil N utilisez pas d additif de détection des fuites N utilisez pas de réfrigérant d un autre type que celui indiqué dans les manuels fournis avec l unité et la plaque signalétique Cela pourrait provoquer une brûlure de l unité ou de ses tuyaux une explosion ou un incendie pendant l utilisation la réparation ou lors de l élimination de l unité Cela pour...

Page 14: ...oquer des problèmes de santé Attention Ne dirigez pas le flux d air vers des plantes ou des animaux en cage Aérez fréquemment la pièce Si l unité fonctionne continuellement dans une pièce fermée pendant un long moment l air va devenir vicié En cas de panne Avertissement Ne réparez jamais le climatiseur Consultez votre revendeur pour toute réparation ou entretien Une mauvaise réparation peut causer...

Page 15: ...rait provoquer une combustion incomplète du brûleur Le micro ordinateur fonctionne dans les cas suivants L air ne souffle pas lorsque le chauffage démarre Pour éviter que de l air froid ne s échappe le ventilateur intérieur est progressivement commuté entre très faible débit d air faible débit d air et débit d air défini en fonction de l augmentation de la température de l air soufflé Il faut atte...

Page 16: ...sion Les températures de consigne actuelles s affichent Appuyez sur la touche F2 ou F3 pour afficher l écran des réglages Plage de température de consigne Mode de fonctionnement Plage de température de consigne Froid Déshumidification 19 ºC 30 ºC 67 ºF 87 ºF 1 Chaud 17 ºC 28 ºC 63 ºF 83 ºF 1 Automatique point de réglage unique 19 ºC 28 ºC 67 ºF 83 ºF 1 2 Automatique point de réglage double Froid I...

Page 17: ...chauffage et de dégivrage Patientez un instant L opération de chauffage commence lorsque l opération de dégivrage est terminée Le climatiseur fonctionne pendant un bref instant puis s arrête aussitôt Le code et la mention de vérification CONTRÔLE clignotent sur l affichage à cristaux liquides Des obstacles bloquent l entrée et la sortie d air des unités intérieures et extérieures Remettez en march...

Page 18: ...ormations concernant l installation et son déplacement Attention N installez jamais le climatiseur dans un endroit sujet à des fuites de gaz inflammable Un incendie pourrait se déclarer suite à des fuites ou à une accumulation de gaz à proximité de l unité N installez jamais le climatiseur dans les endroits suivants dans un endroit où il y a beaucoup d huile de machine à proximité de l océan et de...

Page 19: ...40 0 60 Pa 35 50 70 100 150 Niveau sonore Faible Moyen Élevé 2 3 dB A 31 35 39 31 35 39 31 35 39 Filtre Filtre standard Élément Modèle P36 P48 P54 Alimentation 208 230 V 60 Hz Capacité de refroidissement 1 Capacité de chauffage 1 Btu h 36 000 40 000 48 000 54 000 54 000 60 000 kW 10 6 11 7 14 1 15 8 15 8 17 6 Dimension Hauteur mm po 250 9 13 16 Largeur mm po 1 400 55 1 8 1 600 63 Profondeur mm po ...

Page 20: ...r remoto o cuando hay un error Las funciones de los botones de función cambian dependiendo de la pantalla Consulte la guía de funciones de los botones que aparece en la parte inferior del LCD para ver las funciones que tienen en cada una de las pantallas Cuando el sistema se controla a nivel central la guía de función del botón que corresponde al botón bloqueado no aparecerá Pantalla principal Men...

Page 21: ...n Program On Off o programador Auto Off aparece al deshabilitar el programador mediante el sistema de control centralizado aparece cuando la función Bloqueo está habilitada Aparece cuando se activa el programador semanal Aparece mientras las unidades están funcionando en modo ahorro de energía No aparecerá en algunos modelos de unidades interiores Aparece mientras las unidades exteriores están fun...

Page 22: ...aditivo detector de fuga No utilice un refrigerante diferente del indicado en los manuales que se entregan con la unidad y en la placa de identificación Si lo hace la unidad o las tuberías podrían explotar o producirse una explosión o incendio durante su uso o reparación o en el momento de la eliminación de la unidad También podría suponer un quebrantamiento de la normativa aplicable MITSUBISHI EL...

Page 23: ...cia Nunca repare personalmente el acondicionador Ante cualquier avería o servicio avise siempre a su proveedor Una reparación defectuosa puede provocar fugas de agua descarga eléctrica un incendio etc Si el controlador remoto muestra alguna indicación de error el acondicionador de aire no funciona o se produce cualquier tipo de anomalía pare la unidad y póngase en contacto con su proveedor Si deja...

Page 24: ...e no sale cuando se activa la calefacción Pare evitar que se escape aire frío el ventilador interior va incrementando la fuerza de la corriente de aire de forma gradual empezando muy débilmente y aumentando hasta llegar a la intensidad indicada a medida que aumenta la temperatura de la corriente de aire Espere un momento hasta que el aire salga de forma natural El ventilador gira a la velocidad in...

Page 25: ... o doble en función del modelo de unidad interior 3 Se utilizan los mismos valores para la temperatura de consigna del modo Frío Secar y la temperatura de consigna de refrigeración del modo Auto puntos de ajuste doble Asimismo se utilizan los mismos valores para la temperatura de consigna del modo Calor y la temperatura de consigna de calefacción del modo Auto puntos de ajuste doble 4 Las temperat...

Page 26: ...na mientras que el filtro de larga duración debería limpiarse al principio de cada estación La duración del filtro depende del lugar en que se ha instalado la unidad y de su funcionamiento Cómo limpiar el filtro Quite el polvo sacudiéndolo suavemente o con un aspirador En caso de manchas resistentes lave el filtro con un detergente neutro disuelto en agua templada después aclare bien los restos de...

Page 27: ...órmele del nombre del producto de la naturaleza del fallo etc Si la pantalla de información de error parpadea dígale al distribuidor la información indicada en la pantalla código de error No intente nunca reparar personalmente la unidad Los siguientes no son síntomas de ninguna avería El aire del acondicionador produce algún tipo de olor Esto se debe a que el acondicionador aspira el humo de los c...

Page 28: ...imensio nes Altura mm in 250 9 13 16 Anchura mm in 700 27 9 16 900 35 7 16 Fondo mm in 732 28 7 8 Peso neto kg lb 21 47 26 58 Ventilador Velocidad de la corriente de aire Baja Media Alta CFM 212 265 300 212 265 300 265 318 371 353 424 494 424 512 600 Presión estática externa 2 in WG 0 14 0 20 0 28 0 40 0 60 Pa 35 50 70 100 150 Nivel sonoro Bajo Medio Alto 2 3 dB A 24 28 30 24 28 30 26 30 34 27 31 ...

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ...U TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment KJ79M726H01 ...

Reviews: