11. Trouble Shooting

Having trouble?

Here is the solution. (Unit is operating normally.)

Noise is louder than specifications.

  The indoor operation sound level is affected by the acoustics of the par-

ticular room as shown in the following table and will be higher than the 
noise specification, which was measured in an echo-free room.

High sound-ab-

sorbing rooms

Normal rooms

Low sound-ab-

sorbing rooms

Location

examples

Broadcasting 

studio, music 

room, etc.

Reception 

room, hotel 

lobby, etc.

Office, hotel 

room

Noise levels

3 to 7 dB

6 to 10 dB

9 to 13 dB

Nothing appears in the wireless remote controller display, the display 

is faint, or signals are not received by the indoor unit unless the re-

mote controller is close.

  The batteries are low.

  Replace the batteries and press the Reset button.

  If nothing appears even after the batteries are replaced, make sure that 

the batteries are installed in the correct directions (+, –).

The operation lamp near the receiver for the wireless remote control-

ler on the indoor unit is blinking.

  The self diagnosis function has operated to protect the air conditioner.
  Do not attempt to repair this equipment by yourself.

  Turn off the power switch immediately and consult your dealer. Be sure 

to provide the dealer with the model name.

Warm air blows from the indoor unit intermittently when heating mode 

is off or during fan mode.

  When another indoor unit is operating in heating mode, the control valve 

opens and closes occasionally to maintain stability in the air conditioning 
system. This operation will stop after a while.
*  If this will cause an undesirable rise in the room temperature in small 

rooms, etc., stop the operation of the indoor unit temporarily.

The damper opens and closes automatically.

(For PFFY-P·VKM-E series)

  The damper is automatically controlled by a microcomputer according to 

the air flow temperature and operation time of the air conditioner.

 

Air outlet control (PFFY-P·VKM-E series)

This unit is automatically controlled that air comes out simultaneously from the upper and lower air outlets so that the room can be cooled or heated
effectively.

Description of operation

Operation

COOL

DRY

HEAT

FAN

Air flow

 

Upper and lower air flow

Upper air flow

Upper air flow only

Upper and lower air flow

Upper air flow

Upper and lower air flow

Conditions

Room temperature 
and set temperature 
are different.

Room temperature 
is close to set tem-
perature or thermo-
off.

(Normal condition 
(in heating))

During defrosting 
operation, start of 
operation, thermo-
off

•  Be sure to keep the area around the damper of the lower air outlet free of any objects.
  This unit can be set to blow out air from the upper air outlet only by changing the switch setting on the address board (ask the dealer).

Range of application

The range of working temperatures for both the indoor and outdoor units of the series Y, R2, Multi-S is as below.

 Warning:

If the air conditioner operates but does not cool or heat (depending on model) the room, consult your dealer since there may be a refriger-
ant leak. Be sure to ask the service representative whether there is refrigerant leakage or not when repairs are carried out.
The refrigerant charged in the air conditioner is safe. Refrigerant normally does not leak. However, if refrigerant gas leaks indoors, and 
comes into contact with the fire of a fan heater, space heater, stove, etc., harmful substances will be generated.

Summary of Contents for City Multi PCFY-P100VKM-E

Page 1: ...NUAL DE OPERAÇÃO Para segurança e utilização correctas leia atentamente o manual de operação antes de pôr a funcionar a uni dade de ar condicionado FOR USER PARA O UTILIZADOR PARA EL USUARIO PER L UTENTE VOOR DE GEBRUIKER POUR L UTILISATEUR FÜR BENUTZER Air Conditioners For Building Application INDOOR UNIT PKFY P VBM E PKFY P VHM E PCFY P VKM E PFFY P VKM E 2 PMFY P VBM E ΕΓΧΕΙΡΙΔΙΟ ΟΔΗΓΙΩΝ ΧΡΗΣΕΩ...

Page 2: ...ixed with the refrigerant then it can be the cause of ab normal high pressure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified for the system will cause mechanical failure or sys tem malfunction or unit breakdown In the worst case this could lead to a serious impediment to securing product safety Caution Do not use any sh...

Page 3: ...hr 100 hr 100 hr 2 Parts Names PCFY P VKM E Ceiling Suspended PKFY P VBM E Wall Mounted PMFY P VBM E 1 way Ceiling Cassette Filter Air intake Louver Air outlet Vane Filter Air inlet Louver Air outlet Vane Louver Louver Air outlet Damper Filter Vane Air outlet Air inlet Filter Air intake Louver Air outlet Vane PFFY P VKM E 2 Floor Standing PKFY P VHM E Wall Mounted This operation is available only ...

Page 4: ...on Set Temperature buttons Down Up Mode button Return button Set Time buttons Timer On Off button Set Day button Opening the cover ON OFF button Fan Speed button Filter button Enter button Test Run button Check button Clear button Airflow Up Down button Louver button Operation button To return operation number Ventilation button Operation button Note PLEASE WAIT message This message is displayed f...

Page 5: ...ion do not get the remote controller wet or leave it in a location with high hu midity To avoid misplacing the remote controller install the holder included with the remote controller on a wall and be sure to always place the remote controller in the holder after use Battery installation replacement 1 Remove the top cover insert two AAA bat teries and then install the top cover 2 Press the Reset b...

Page 6: ...e Set the current day of the week or time Standard Control Screens View and set the air conditioning system s op erating status Timer Monitor View the currently set timer weekly timer sim ple timer or Auto Off timer Timer Setup Set the operation of any of the timers weekly timer simple timer or Auto Off timer How to change the screen A Hold down both the Mode button and the Timer On Off button for...

Page 7: ...tes switches from cool ing to heating Because the room temperature is automatically adjusted in order to maintain a fixed effective temperature cooling operation is performed a few degrees warmer and heating operation is performed a few de grees cooler than the set room temperature once the temperature is reached automatic energy saving operation 5 3 Temperature setting To decrease the room temper...

Page 8: ... Sunday Start the air conditioner at 8 30 with the temperature set to 23 C Operation 2 settings for every day Turn off the air conditioner at 10 00 C SUN ON WEEKLY Shows the selected operation ON or OFF Does not appear if operation is not set Shows the temperature setting Does not appear if temperature is not set Shows the time set ting Low High No display Stop OFF 5 6 Ventilation For LOSSNAY comb...

Page 9: ... 3 ON timer The air conditioner will start operation when the specified number of hours has elapsed OFF timer The air conditioner will stop operation when the specified number of hours has elapsed 4 With ON or OFF showing at 3 Press the appropriate Set Time button as necessary to set the hours to ON if ON is displayed or the hours to OFF if OFF is displayed at 4 Available Range 1 to 72 hours 5 To ...

Page 10: ...ns countdown when the air conditioner starts and shuts the air conditioner off when the set time has elapsed Available settings run from 30 minutes to 4 hours in 30 minute intervals Note 1 Weekly Timer Simple Timer Auto Off Timer cannot be used at the same time 2 The Auto Off timer will not operate when any of the following condi tions is in effect The timer is off the system is in malfunction sta...

Page 11: ...k type see section 8 item 4 2 1 Specifically you can use either of the following two lock types 1 Lock All Buttons Locks all of the buttons on the remote controller 2 Lock All Except ON OFF Locks all buttons other than the ON OFF button Note The Locked indicator appears on the screen to indicate that but tons are currently locked How to Lock the Buttons 1 While holding down the Filter button 4 pre...

Page 12: ...r non use of clock function 3 Timer function setting WEEKLY TIMER Setting the timer type 4 Contact number setting for error situation CALL Contact number display in case of error Setting the telephone number 4 Display change DISP MODE SET TING 1 Temperature display C F setting TEMP MODE C F Setting the temperature unit C or F to display 2 Suction air temperature display setting ROOM TEMP DISP SELE...

Page 13: ...e is displayed when the operation mode is selected Initial setting value The automatic mode is not displayed when the operation mode is selected The temperature range limit is not active Initial setting value The temperature range can be changed on cooling dry mode The temperature range can be changed on heating mode The temperature range can be changed on automatic mode The remote controller will...

Page 14: ...y can be selected Press the MENU button G to change the language 1 English GB 2 German D 3 Spanish E 4 Russian RU 5 Italian I 6 Chinese CH 7 French F 8 Japanese JP Refer to the dot display table 4 2 Function limit 1 Operation function limit setting operation lock To switch the setting press the ON OFF button 1 no1 Operation lock setting is made on all buttons other than the ON OFF button 2 no2 Ope...

Page 15: ...ature cooling day mode Limit temperature heating mode Limit temperature auto mode Mode selection Remote controller setting MAIN Remote controller setting SUB Use of clock setting Setting the day of the week and time Timer set Timer monitor Weekly timer Timer mode off Auto off timer Simple timer Contact number setting of error situation Display change Temperature display C F setting Room air temper...

Page 16: ...ng period when the air conditioner was used under general indoor air conditions by criteria time Since the degree of dirtiness depends on the environmental con ditions clean the filter accordingly The filter cleaning period cumulative time differs with the model This indication is not available for wireless remote controller Cleaning the filters Clean the filters using a vacuum cleaner If you do n...

Page 17: ...e intake grille causes the intake grille to open 2 A filter with an intake grille on it can be removed by pulling the filter forward 10 Care and Cleaning PFFY P VKM E 2 1 Remove the catechin air filter A Open the front grille B Catechin air filter Caution When the catechin air filter is to be removed do not touch the metal parts of the indoor unit This may cause an injury 2 Install the catechin ai...

Page 18: ...g mode water may form and drip from the cool pipes and joints During heating mode water may form and drip from the heat exchang er During defrosting mode water on the heat exchanger evaporates and water vapor may be emitted The operation indicator does not appear in the remote controller dis play Turn on the power switch will appear in the remote controller display The air conditioner does not ope...

Page 19: ...able rise in the room temperature in small rooms etc stop the operation of the indoor unit temporarily The damper opens and closes automatically For PFFY P VKM E series The damper is automatically controlled by a microcomputer according to the air flow temperature and operation time of the air conditioner Air outlet control PFFY P VKM E series This unit is automatically controlled that air comes o...

Page 20: ... the maximum value at operation under the following condition Cooling Indoor 27 C DB 19 C WB Outdoor 35 C DB Heating Indoor 20 C DB Outdoor 7 C DB 6 C WB PMFY P VBM E Series Model P20 P25 P32 P40 Power source Voltage V Frequency Hz N 220 230 240 50 220 60 Capacity Cooling Heating kW 2 2 2 5 2 8 3 2 3 6 4 0 4 5 5 0 Dimension Height mm 230 30 Dimension Width mm 854 1000 Dimension Depth mm 395 470 Ne...

Page 21: ... Детям и немощным людям ЗАПРЕЩАЕТСЯ самостоятельно пользоваться данным кондиционером воздуха Необходимо наблюдать за маленькими детьми с тем чтобы они не играли с кондиционером воздуха Если происходит выброс или утечка газа хладагента остано вите работу кондиционера тщательно проветрите помеще ние и свяжитесь с вашим поставщиком Этот прибор не предназначен для использования его детьми инвалидами а...

Page 22: ...ый Обычный Долговечный Обычный Обычный Индикация очистки фильтра 100 часов 100 часов 2 500 часов 100 часов 100 часов 2 Наименование деталей Выходные воздушные отверстия Лопатка Жалюзи Выходные воздушные отверстия Фильтр Фильтр Впуск воздуха Жалюзи Выходные воздушные отверстия Лопатка Выходные воздушные отверстия Жалюзи Лопатка Фильтр Внутренняя часть воздухозаборника Louver Louver Air outlet Dampe...

Page 23: ...олько один час Отображается в случае настройки понижения мощности исходящего воздушного потока и направления его книзу в режиме охлаждения COOL или сушки DRY Работа в этом режиме зависит от модели устройства Индикатор отключается через час работы во время изменения направления воздушного потока Настройка температуры Показывает целевую температуру Индикатор направления воздуха вверх вниз Индикатор ...

Page 24: ...Не роняйте пульт дистанционного управления и не подвергайте его сильным ударам Кроме того следите за тем чтобы пульт дистанционного управления не попал в воду и не оставляйте его в местах с высокой влажностью Во избежание неправильного местоположения пульта дистанционного управления установите на стене держатель входящий в комплект поставки пульта дистанционного управления и обязательно устанавлив...

Page 25: ...жмите кнопки установки времени или 1 Нажмите кнопку настройки времени или 1 для включения отображения на дисплее 2 2 Нажмите кнопку включения выключения таймера On Off установка дня 9 для установки дня недели Каждое нажатие кнопки переключает день как показано на 3 Sun Вск Mon Пнд Fri Птн Sat Сбт 3 Нажмитесоответствующуюкнопкунастройкивремени1 дляустановкивремени Пока вы удерживаете кнопку нажатой...

Page 26: ...ора зависит от типа подключенного устройства Некоторые устройства не имеют возможности настройки параметра Auto Авто В следующих случаях действительная скорость вентилятора устройства будет отличаться от скорости отображаемой на пульте дистанционного управления 1 Во время отображения индикации STAND BY ОБОГРEB ПАУЗА или DEFROST OTTAИBAHИE 2 Когда температура теплообменника низкая в режиме обогрева...

Page 27: ...становки дня недели Каждое нажатие кнопки отображает 3 следующий параметр настройки в последовательности Вск Пнд Втр Срд Чтв Птн Сбт Sun Fri Sat Sun Mon Tues Wed Thurs Fri Sat 4 Нажмите или кнопку операции 7 или 8 необходимое число раз для установки нужного значения 1 8 4 Во время выполнения действий 3 и 4 будет выбран один из элементов показанной ниже таблицы Слева на дисплее пульта дистанционног...

Page 28: ...ия В этих условиях операции включения и отключения запрещены Настройка простого таймера Для включения недельного таймера Нажмите кнопку включения выключения таймера On Off 9 после чего индикатор Timer Off Выкл таймер потемнеет на экране 7 Нажмите соответствующую кнопку настройки температуры 3 для установки нужного значения температуры 7 К а ж д о е н а ж а т и е к н о п к и и з м е н я е т н а с т...

Page 29: ...у самотестирования или диагностики пользователь пытается выбрать режим работы пользователь выполняет настройку таймера система управляется из центрального пульта управления В этих условиях операции включения и отключения запрещены 1 Убедитесь что на экране отображается индикатор простого таймера 1 2 Нажмите кнопку таймера Menu 2 после чего на экране отобразится сообщение Monitor Монитор 5 Если про...

Page 30: ...едующих типа блокировки Блокировка всех кнопок Блокирует все кнопки пульта дистанционного управления Блокировка всех кнопок кроме ON OFF Блокирует все кнопки кроме ON OFF ВКЛ ВЫКЛ Примечание Индикатор блокировки Locked Блокировано появляется на экране после того как кнопки будут блокированы Как блокировать кнопки 1 Удерживая нажатой кнопку Filter Фильтр 4 нажмите и удерживайте в течение 2 секунд к...

Page 31: ...включения или отключения функции часов 3 Настройка функции таймера Heдeлыйтаймера Настройка типа таймера 4 Настройка номера контакта при возникновении ошибки CALL Индикация номера контакта в случае возникновения ошибки Настройка номера телефона 4 Изменение индикации Настройка индрежима 1 Настройка индикации температуры C F Eдин темпер C F Настройка индикации единиц измерения температуры C или F 2 ...

Page 32: ...кции с помощью пульта дистанционного управления Выбор языка Bыбор функции Bыбор режима Пункт 2 Пункт 1 Пункт 3 Настройка блокировки работы не используется Значение первоначальной настройки Настройка блокировки работы кроме кнопок On Off Вкл Выкл Настройка блокировки работы для всех кнопок При выборе режима работы отображается автоматический режим Значение первоначальной настройки При выборе режима...

Page 33: ...в нажмите кнопку H Выбранный параметр мигает можно установить температуру Устанавливаемый диапазон Режим охлаждения сушки Нижний предел от 19 C до 30 C Верхний предел от 30 C до 19 C Режим обогрева Нижний предел от 17 C до 28 C Верхний предел от 28 C до 17 C Автоматический режим Нижний предел от 19 C до 28 C Верхний предел от 28 C до 19 C 4 3 Настройка выбора режима 1 Настройка пульта дистанционно...

Page 34: ...Выбор языка Bыбор функции Настройка ограничения рабочей функции Использование настройки автоматического режима Настройка ограничения температурного диапазона Ограничение температуры охлаждения дневного режима Ограничение температуры режима обогрева Ограничение температуры автоматического режима Выбор режима Пульт дистанционного управления настроен как ОСНОВНОЙ Пульт дистанционного управления настр...

Page 35: ...как это может привести к их деформации Не забывайте устанавливать фильтры на место Эксплуатация прибора без фильтров воздуха может привести к его поломке Осторожно Прежде чем начать чистку остановите работу прибора и отключите подачу электропитания Внутренние приборы оборудованы фильтрами для удаления пыли из засасываемого воздуха Прочищайте фильтры с помощью методов обозначенных на рисунках ниже ...

Page 36: ...показано C Установите на место 3 Плотно закройте переднюю решетку PCFY P VKM E 1 Откройте воздухозаборную решетку 2 Удерживайте рукоятку фильтра затем потяните его вверх в направлении стрелки При установке фильтра после чистки убедитесь что он вставлен достаточно глубоко до стопора A Фильтр B Воздухозаборная решетка C Рукоятка D Стопор PMFY P VBM E 1 Нажатие кнопки PUSH на внешней стороне воздухоз...

Page 37: ...ть с холодных труб и стыков В режиме обогрева вода может образовываться и капать с теплообменника В режиме размораживания вода на теплообменнике испаряется и может появиться водяной пар Индикатор работы не появляется на дисплее пульта дистанционного управления Включите питание На дисплее пульта дистанционного управления появится Кондиционер не работает даже после нажатия кнопки ON OFF ВКЛ ВЫКЛ Окн...

Page 38: ...богревателя огнем кухонной плиты и т п происходит образование вредных для здоровья веществ Возникла проблема Вот решение Прибор работает нормально Уровень шума превышает уровень указанный в технических характеристиках Уровень шума работающего кондиционера зависит от акустики конкретного помещения см таблицу ниже Он может быть выше чем указано в спецификации поскольку тестовый замер проводился в бе...

Page 39: ...Температура снаружи 35 С DB Обогрев Температура в помещении 20 С DB Температура снаружи 7 С DB 6 С WB DB шарик сухого термометра WB шарик влажного термометра Серия PMFY P VBM E Модель P20 P25 P32 P40 Электропитание Напряжение В Частота Гц N 220 230 240 50 220 60 Мощность Охлаждение Обогрев кВт 2 2 2 5 2 8 3 2 3 6 4 0 4 5 5 0 Габариты Высота мм 230 30 Габариты Ширина мм 854 1000 Габариты Глубина мм...

Page 40: ...ase be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan RG79D837H01 ...

Reviews: