11. Trouble Shooting

Having trouble?

Here is the solution. (Unit is operating normally.)

Air conditioner does not heat or cool well.

  Clean the filter. (Airflow is reduced when the filter is dirty or clogged.)
  Check the temperature adjustment and adjust the set temperature.
  Make sure that there is plenty of space around the outdoor unit. Is the 

indoor unit air intake or outlet blocked?

  Has a door or window been left open?

When heating operation starts, warm air does not blow from the indoor 
unit soon.

  Warm air does not blow until the indoor unit has sufficiently warmed up.

During heating mode, the air conditioner stops before the set room 
temperature is reached.

  When the outdoor temperature is low and the humidity is high, frost 

may form on the outdoor unit. If this occurs, the outdoor unit performs a 
defrosting operation. Normal operation should begin after approximate-
ly10 minutes.

Airflow direction changes during operation or airflow direction cannot 
be set.

  During cooling mode, the vanes automatically move to the horizontal 

(down) position after 1 hour when the down (horizontal) airflow direction 
is selected. This is to prevent water from forming and dripping from the 
vanes.

  During heating mode, the vanes automatically move to the horizontal 

airflow direction when the airflow temperature is low or during defrost-
ing mode.

When the airflow direction is changed, the vanes always move up and 
down past the set position before finally stopping at the position.

  When the airflow direction is changed, the vanes move to the set posi-

tion after detecting the base position.

A flowing water sound or occasional hissing sound is heard.

  These sounds can be heard when refrigerant is flowing in the air condi-

tioner or when the refrigerant flow is changing.

A cracking or creaking sound is heard.

  These sounds can be heard when parts rub against each due to expan-

sion and contraction from temperature changes.

The room has an unpleasant odor.

  The indoor unit draws in air that contains gases produced from the 

walls, carpeting, and furniture as well as odors trapped in clothing, and 
then blows this air back into the room.

A white mist or vapor is emitted from the indoor unit.

  If the indoor temperature and the humidity are high, this condition may 

occur when operation starts.

  During defrosting mode, cool airflow may blow down and appear like a 

mist.

Water or vapor is emitted from the outdoor unit.

  During cooling mode, water may form and drip from the cool pipes and 

joints.

  During heating mode, water may form and drip from the heat exchang-

er.

  During defrosting mode, water on the heat exchanger evaporates and 

water vapor may be emitted.

The operation indicator does not appear in the remote controller dis-
play.

  Turn on the power switch. “   ” will appear in the remote controller 

display.

The air conditioner does not operate even though the ON/OFF button 
is pressed. The operation mode display on the remote controller disap-
pears.

  Is the power switch of the indoor unit turned off? Turn on the power 

switch.

” appears in the remote controller display.

  During central control, “ 

 ” appears in the remote controller display 

and air conditioner operation cannot be started or stopped using the 
remote controller.

When restarting the air conditioner soon after stopping it, it does not 

operate even though the ON/OFF button is pressed.

  Wait approximately three minutes.

  (Operation has stopped to protect the air conditioner.)

Air conditioner operates without the ON/OFF button being pressed.

  Is the on timer set?

  Press the ON/OFF button to stop operation.

  Is the air conditioner connected to a central remote controller?

  Consult the concerned people who control the air conditioner.

  Does “ 

 ” appear in the remote controller display?

  Consult the concerned people who control the air conditioner.

  Has the auto recovery feature from power failures been set?

  Press the ON/OFF button to stop operation.

Air conditioner stops without the ON/OFF button being pressed.

  Is the off timer set?

  Press the ON/OFF button to restart operation.

  Is the air conditioner connected to a central remote controller?

  Consult the concerned people who control the air conditioner.

  Does “ 

 ” appear in the remote controller display?

  Consult the concerned people who control the air conditioner.

Remote controller timer operation cannot be set.

  Are timer settings invalid?

  If the timer can be set, 

WEEKLY  

SIMPLE

 or 

AUTO OFF

 appears in the re-

mote controller display.

“PLEASE WAIT” appears in the remote controller display.

  The initial settings are being performed. Wait approximately 3 minutes.

An error code appears in the remote controller display.

  The protection devices have operated to protect the air conditioner.
  Do not attempt to repair this equipment by yourself.

  Turn off the power switch immediately and consult your dealer. Be sure 

to provide the dealer with the model name and information that ap-
peared in the remote controller display.

Draining water or motor rotation sound is heard.

  When cooling operation stops, the drain pump operates and then stops. 

Wait approximately 3 minutes.

Summary of Contents for City Multi PCFY-P100VKM-E

Page 1: ...NUAL DE OPERAÇÃO Para segurança e utilização correctas leia atentamente o manual de operação antes de pôr a funcionar a uni dade de ar condicionado FOR USER PARA O UTILIZADOR PARA EL USUARIO PER L UTENTE VOOR DE GEBRUIKER POUR L UTILISATEUR FÜR BENUTZER Air Conditioners For Building Application INDOOR UNIT PKFY P VBM E PKFY P VHM E PCFY P VKM E PFFY P VKM E 2 PMFY P VBM E ΕΓΧΕΙΡΙΔΙΟ ΟΔΗΓΙΩΝ ΧΡΗΣΕΩ...

Page 2: ...ixed with the refrigerant then it can be the cause of ab normal high pressure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified for the system will cause mechanical failure or sys tem malfunction or unit breakdown In the worst case this could lead to a serious impediment to securing product safety Caution Do not use any sh...

Page 3: ...hr 100 hr 100 hr 2 Parts Names PCFY P VKM E Ceiling Suspended PKFY P VBM E Wall Mounted PMFY P VBM E 1 way Ceiling Cassette Filter Air intake Louver Air outlet Vane Filter Air inlet Louver Air outlet Vane Louver Louver Air outlet Damper Filter Vane Air outlet Air inlet Filter Air intake Louver Air outlet Vane PFFY P VKM E 2 Floor Standing PKFY P VHM E Wall Mounted This operation is available only ...

Page 4: ...on Set Temperature buttons Down Up Mode button Return button Set Time buttons Timer On Off button Set Day button Opening the cover ON OFF button Fan Speed button Filter button Enter button Test Run button Check button Clear button Airflow Up Down button Louver button Operation button To return operation number Ventilation button Operation button Note PLEASE WAIT message This message is displayed f...

Page 5: ...ion do not get the remote controller wet or leave it in a location with high hu midity To avoid misplacing the remote controller install the holder included with the remote controller on a wall and be sure to always place the remote controller in the holder after use Battery installation replacement 1 Remove the top cover insert two AAA bat teries and then install the top cover 2 Press the Reset b...

Page 6: ...e Set the current day of the week or time Standard Control Screens View and set the air conditioning system s op erating status Timer Monitor View the currently set timer weekly timer sim ple timer or Auto Off timer Timer Setup Set the operation of any of the timers weekly timer simple timer or Auto Off timer How to change the screen A Hold down both the Mode button and the Timer On Off button for...

Page 7: ...tes switches from cool ing to heating Because the room temperature is automatically adjusted in order to maintain a fixed effective temperature cooling operation is performed a few degrees warmer and heating operation is performed a few de grees cooler than the set room temperature once the temperature is reached automatic energy saving operation 5 3 Temperature setting To decrease the room temper...

Page 8: ... Sunday Start the air conditioner at 8 30 with the temperature set to 23 C Operation 2 settings for every day Turn off the air conditioner at 10 00 C SUN ON WEEKLY Shows the selected operation ON or OFF Does not appear if operation is not set Shows the temperature setting Does not appear if temperature is not set Shows the time set ting Low High No display Stop OFF 5 6 Ventilation For LOSSNAY comb...

Page 9: ... 3 ON timer The air conditioner will start operation when the specified number of hours has elapsed OFF timer The air conditioner will stop operation when the specified number of hours has elapsed 4 With ON or OFF showing at 3 Press the appropriate Set Time button as necessary to set the hours to ON if ON is displayed or the hours to OFF if OFF is displayed at 4 Available Range 1 to 72 hours 5 To ...

Page 10: ...ns countdown when the air conditioner starts and shuts the air conditioner off when the set time has elapsed Available settings run from 30 minutes to 4 hours in 30 minute intervals Note 1 Weekly Timer Simple Timer Auto Off Timer cannot be used at the same time 2 The Auto Off timer will not operate when any of the following condi tions is in effect The timer is off the system is in malfunction sta...

Page 11: ...k type see section 8 item 4 2 1 Specifically you can use either of the following two lock types 1 Lock All Buttons Locks all of the buttons on the remote controller 2 Lock All Except ON OFF Locks all buttons other than the ON OFF button Note The Locked indicator appears on the screen to indicate that but tons are currently locked How to Lock the Buttons 1 While holding down the Filter button 4 pre...

Page 12: ...r non use of clock function 3 Timer function setting WEEKLY TIMER Setting the timer type 4 Contact number setting for error situation CALL Contact number display in case of error Setting the telephone number 4 Display change DISP MODE SET TING 1 Temperature display C F setting TEMP MODE C F Setting the temperature unit C or F to display 2 Suction air temperature display setting ROOM TEMP DISP SELE...

Page 13: ...e is displayed when the operation mode is selected Initial setting value The automatic mode is not displayed when the operation mode is selected The temperature range limit is not active Initial setting value The temperature range can be changed on cooling dry mode The temperature range can be changed on heating mode The temperature range can be changed on automatic mode The remote controller will...

Page 14: ...y can be selected Press the MENU button G to change the language 1 English GB 2 German D 3 Spanish E 4 Russian RU 5 Italian I 6 Chinese CH 7 French F 8 Japanese JP Refer to the dot display table 4 2 Function limit 1 Operation function limit setting operation lock To switch the setting press the ON OFF button 1 no1 Operation lock setting is made on all buttons other than the ON OFF button 2 no2 Ope...

Page 15: ...ature cooling day mode Limit temperature heating mode Limit temperature auto mode Mode selection Remote controller setting MAIN Remote controller setting SUB Use of clock setting Setting the day of the week and time Timer set Timer monitor Weekly timer Timer mode off Auto off timer Simple timer Contact number setting of error situation Display change Temperature display C F setting Room air temper...

Page 16: ...ng period when the air conditioner was used under general indoor air conditions by criteria time Since the degree of dirtiness depends on the environmental con ditions clean the filter accordingly The filter cleaning period cumulative time differs with the model This indication is not available for wireless remote controller Cleaning the filters Clean the filters using a vacuum cleaner If you do n...

Page 17: ...e intake grille causes the intake grille to open 2 A filter with an intake grille on it can be removed by pulling the filter forward 10 Care and Cleaning PFFY P VKM E 2 1 Remove the catechin air filter A Open the front grille B Catechin air filter Caution When the catechin air filter is to be removed do not touch the metal parts of the indoor unit This may cause an injury 2 Install the catechin ai...

Page 18: ...g mode water may form and drip from the cool pipes and joints During heating mode water may form and drip from the heat exchang er During defrosting mode water on the heat exchanger evaporates and water vapor may be emitted The operation indicator does not appear in the remote controller dis play Turn on the power switch will appear in the remote controller display The air conditioner does not ope...

Page 19: ...able rise in the room temperature in small rooms etc stop the operation of the indoor unit temporarily The damper opens and closes automatically For PFFY P VKM E series The damper is automatically controlled by a microcomputer according to the air flow temperature and operation time of the air conditioner Air outlet control PFFY P VKM E series This unit is automatically controlled that air comes o...

Page 20: ... the maximum value at operation under the following condition Cooling Indoor 27 C DB 19 C WB Outdoor 35 C DB Heating Indoor 20 C DB Outdoor 7 C DB 6 C WB PMFY P VBM E Series Model P20 P25 P32 P40 Power source Voltage V Frequency Hz N 220 230 240 50 220 60 Capacity Cooling Heating kW 2 2 2 5 2 8 3 2 3 6 4 0 4 5 5 0 Dimension Height mm 230 30 Dimension Width mm 854 1000 Dimension Depth mm 395 470 Ne...

Page 21: ... Детям и немощным людям ЗАПРЕЩАЕТСЯ самостоятельно пользоваться данным кондиционером воздуха Необходимо наблюдать за маленькими детьми с тем чтобы они не играли с кондиционером воздуха Если происходит выброс или утечка газа хладагента остано вите работу кондиционера тщательно проветрите помеще ние и свяжитесь с вашим поставщиком Этот прибор не предназначен для использования его детьми инвалидами а...

Page 22: ...ый Обычный Долговечный Обычный Обычный Индикация очистки фильтра 100 часов 100 часов 2 500 часов 100 часов 100 часов 2 Наименование деталей Выходные воздушные отверстия Лопатка Жалюзи Выходные воздушные отверстия Фильтр Фильтр Впуск воздуха Жалюзи Выходные воздушные отверстия Лопатка Выходные воздушные отверстия Жалюзи Лопатка Фильтр Внутренняя часть воздухозаборника Louver Louver Air outlet Dampe...

Page 23: ...олько один час Отображается в случае настройки понижения мощности исходящего воздушного потока и направления его книзу в режиме охлаждения COOL или сушки DRY Работа в этом режиме зависит от модели устройства Индикатор отключается через час работы во время изменения направления воздушного потока Настройка температуры Показывает целевую температуру Индикатор направления воздуха вверх вниз Индикатор ...

Page 24: ...Не роняйте пульт дистанционного управления и не подвергайте его сильным ударам Кроме того следите за тем чтобы пульт дистанционного управления не попал в воду и не оставляйте его в местах с высокой влажностью Во избежание неправильного местоположения пульта дистанционного управления установите на стене держатель входящий в комплект поставки пульта дистанционного управления и обязательно устанавлив...

Page 25: ...жмите кнопки установки времени или 1 Нажмите кнопку настройки времени или 1 для включения отображения на дисплее 2 2 Нажмите кнопку включения выключения таймера On Off установка дня 9 для установки дня недели Каждое нажатие кнопки переключает день как показано на 3 Sun Вск Mon Пнд Fri Птн Sat Сбт 3 Нажмитесоответствующуюкнопкунастройкивремени1 дляустановкивремени Пока вы удерживаете кнопку нажатой...

Page 26: ...ора зависит от типа подключенного устройства Некоторые устройства не имеют возможности настройки параметра Auto Авто В следующих случаях действительная скорость вентилятора устройства будет отличаться от скорости отображаемой на пульте дистанционного управления 1 Во время отображения индикации STAND BY ОБОГРEB ПАУЗА или DEFROST OTTAИBAHИE 2 Когда температура теплообменника низкая в режиме обогрева...

Page 27: ...становки дня недели Каждое нажатие кнопки отображает 3 следующий параметр настройки в последовательности Вск Пнд Втр Срд Чтв Птн Сбт Sun Fri Sat Sun Mon Tues Wed Thurs Fri Sat 4 Нажмите или кнопку операции 7 или 8 необходимое число раз для установки нужного значения 1 8 4 Во время выполнения действий 3 и 4 будет выбран один из элементов показанной ниже таблицы Слева на дисплее пульта дистанционног...

Page 28: ...ия В этих условиях операции включения и отключения запрещены Настройка простого таймера Для включения недельного таймера Нажмите кнопку включения выключения таймера On Off 9 после чего индикатор Timer Off Выкл таймер потемнеет на экране 7 Нажмите соответствующую кнопку настройки температуры 3 для установки нужного значения температуры 7 К а ж д о е н а ж а т и е к н о п к и и з м е н я е т н а с т...

Page 29: ...у самотестирования или диагностики пользователь пытается выбрать режим работы пользователь выполняет настройку таймера система управляется из центрального пульта управления В этих условиях операции включения и отключения запрещены 1 Убедитесь что на экране отображается индикатор простого таймера 1 2 Нажмите кнопку таймера Menu 2 после чего на экране отобразится сообщение Monitor Монитор 5 Если про...

Page 30: ...едующих типа блокировки Блокировка всех кнопок Блокирует все кнопки пульта дистанционного управления Блокировка всех кнопок кроме ON OFF Блокирует все кнопки кроме ON OFF ВКЛ ВЫКЛ Примечание Индикатор блокировки Locked Блокировано появляется на экране после того как кнопки будут блокированы Как блокировать кнопки 1 Удерживая нажатой кнопку Filter Фильтр 4 нажмите и удерживайте в течение 2 секунд к...

Page 31: ...включения или отключения функции часов 3 Настройка функции таймера Heдeлыйтаймера Настройка типа таймера 4 Настройка номера контакта при возникновении ошибки CALL Индикация номера контакта в случае возникновения ошибки Настройка номера телефона 4 Изменение индикации Настройка индрежима 1 Настройка индикации температуры C F Eдин темпер C F Настройка индикации единиц измерения температуры C или F 2 ...

Page 32: ...кции с помощью пульта дистанционного управления Выбор языка Bыбор функции Bыбор режима Пункт 2 Пункт 1 Пункт 3 Настройка блокировки работы не используется Значение первоначальной настройки Настройка блокировки работы кроме кнопок On Off Вкл Выкл Настройка блокировки работы для всех кнопок При выборе режима работы отображается автоматический режим Значение первоначальной настройки При выборе режима...

Page 33: ...в нажмите кнопку H Выбранный параметр мигает можно установить температуру Устанавливаемый диапазон Режим охлаждения сушки Нижний предел от 19 C до 30 C Верхний предел от 30 C до 19 C Режим обогрева Нижний предел от 17 C до 28 C Верхний предел от 28 C до 17 C Автоматический режим Нижний предел от 19 C до 28 C Верхний предел от 28 C до 19 C 4 3 Настройка выбора режима 1 Настройка пульта дистанционно...

Page 34: ...Выбор языка Bыбор функции Настройка ограничения рабочей функции Использование настройки автоматического режима Настройка ограничения температурного диапазона Ограничение температуры охлаждения дневного режима Ограничение температуры режима обогрева Ограничение температуры автоматического режима Выбор режима Пульт дистанционного управления настроен как ОСНОВНОЙ Пульт дистанционного управления настр...

Page 35: ...как это может привести к их деформации Не забывайте устанавливать фильтры на место Эксплуатация прибора без фильтров воздуха может привести к его поломке Осторожно Прежде чем начать чистку остановите работу прибора и отключите подачу электропитания Внутренние приборы оборудованы фильтрами для удаления пыли из засасываемого воздуха Прочищайте фильтры с помощью методов обозначенных на рисунках ниже ...

Page 36: ...показано C Установите на место 3 Плотно закройте переднюю решетку PCFY P VKM E 1 Откройте воздухозаборную решетку 2 Удерживайте рукоятку фильтра затем потяните его вверх в направлении стрелки При установке фильтра после чистки убедитесь что он вставлен достаточно глубоко до стопора A Фильтр B Воздухозаборная решетка C Рукоятка D Стопор PMFY P VBM E 1 Нажатие кнопки PUSH на внешней стороне воздухоз...

Page 37: ...ть с холодных труб и стыков В режиме обогрева вода может образовываться и капать с теплообменника В режиме размораживания вода на теплообменнике испаряется и может появиться водяной пар Индикатор работы не появляется на дисплее пульта дистанционного управления Включите питание На дисплее пульта дистанционного управления появится Кондиционер не работает даже после нажатия кнопки ON OFF ВКЛ ВЫКЛ Окн...

Page 38: ...богревателя огнем кухонной плиты и т п происходит образование вредных для здоровья веществ Возникла проблема Вот решение Прибор работает нормально Уровень шума превышает уровень указанный в технических характеристиках Уровень шума работающего кондиционера зависит от акустики конкретного помещения см таблицу ниже Он может быть выше чем указано в спецификации поскольку тестовый замер проводился в бе...

Page 39: ...Температура снаружи 35 С DB Обогрев Температура в помещении 20 С DB Температура снаружи 7 С DB 6 С WB DB шарик сухого термометра WB шарик влажного термометра Серия PMFY P VBM E Модель P20 P25 P32 P40 Электропитание Напряжение В Частота Гц N 220 230 240 50 220 60 Мощность Охлаждение Обогрев кВт 2 2 2 5 2 8 3 2 3 6 4 0 4 5 5 0 Габариты Высота мм 230 30 Габариты Ширина мм 854 1000 Габариты Глубина мм...

Page 40: ...ase be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan RG79D837H01 ...

Reviews: