background image

8

GB

4. Connecting refrigerant pipes and drain pipes

4.1. Connecting refrigerant pipes

1. Be sure to use non-oxidative brazing where necessary. If you do not use non-oxi-

dative brazing, it may clog the pipes.
When brazing the outdoor unit connecting port of HBC controller, supply nitrogen
gas into the pipe between the outdoor unit and HBC controller.

2. After completing pipe connection, support the pipes to ensure that load is not

imparted to the HBC controller’s end connections.

Warning:

When installing and moving the unit, do not charge it with refrigerant other
than the refrigerant (R410A) specified on the unit.

- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to mal-

function and result in severe damage.

Caution:

Use refrigerant piping made of phosphorus deoxidized copper and copper
alloy seamless pipes and tubes. In addition, be sure that the inner and outer
surfaces of the pipes are clean and free of hazardous sulphur, oxides, dust/
dirt, swarf, oils, moisture, or any other contaminants.

- R410A is a high-pressure refrigerant and can cause the existing piping to burst.

Store the piping to be used during installation indoors and keep both ends
of the piping sealed until just before brazing. (Store elbows and other joints
in a plastic bag.)

- If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and

compressor failure may result.

- Infiltration of a large amount of mineral oil may cause the refrigerant oil to dete-

riorate.

Do not vent R410A into the atmosphere.

R410A is a Fluorinated Greenhouse gas, covered by the Kyoto Protocol
with a Global Warming Potential (GWP) = 1975.

1. Size of HBC controller’s end connection piping

[Fig. 4.1.2] (P.3)

Note:
Be sure to use non-oxidative brazing.

4.2.  Refrigerant piping work

After connecting the refrigerant pipes of the outdoor units with the outdoor units’ stop
valves remained fully closed, evacuate vacuum from the outdoor units’ stop valve
service ports.
After completing the above, open the outdoor units’ stop valves. This connects the
refrigerant circuit (between outdoor and HBC controller) completely.
How to handle stop valves is described on each outdoor unit.

Notes:

After pipe connection, be sure to check that there is no gas leakage, using
a leak detector or soap-and-water solution.

Before brazing the refrigerant piping, 

always wrap the piping on the main

body, and the thermal insulation piping, with damp cloths to prevent heat
shrinkage and burning the thermal insulation tubing.

 Take care to ensure

that the flame does not come into contact with the main body itself.

Do not use leak-detection additives.

Warning:

Do not mix anything other than the specified refrigerant (R410A) into the refrig-
erating cycle when installing or moving. Mixing air may cause the refrigerating
cycle to reach abnormally high temperature, resulting in burst pipes.

Caution:

Cut the tip of the outdoor unit piping, remove the gas, and then remove the
brazed cap.

[Fig. 4.2.1] (P.3)

4.3. Insulating refrigerant pipes

Be sure to add insulation work to refrigerant piping by covering high-pressure pipe
and low-pressure pipe separately with enough thickness heat-resistant polyethylene
foam, so that no gap is observed in the joint between the HBC controller and insulat-
ing material, and insulating materials themselves. When insulation work is insuffi-
cient, there is a possibility of condensation. Pay special attention to insulation work in
the ceiling plenum.

[Fig. 4.3.1] (P.3)

Insulation materials for the pipes to be added on site must meet the following
specifications:

Installation of pipes in a high-temperature high-humidity environment, such as
the top floor of a building, may require the use of insulation materials thicker than
the ones specified in the chart above.

When certain specifications presented by the client must be met, ensure that
they also meet the specifications on the chart above.

The brazed connections must be covered with insulation, with its seam facing
upward and fastened with the bands.

4.4. Drain piping work

1. Drain piping work

Ensure that the drain piping is downward (sloped gradient of more than 1/100) to
the outdoor (discharge) side. If it is impossible to take any downward pitch, use
an optionally available drain-up mechanism to obtain a downward pitch of more
than 1/100.

Ensure that any cross-wise drain piping is less than 20 m. If the drain piping is
long, support it with metal brackets to prevent it from bending, warping, or vibrat-
ing.

Connect the supplied drain hose to the discharge port on the unit body. Use hard
vinyl chloride pipes VP-25 (ø32) for drain piping (

2

). Tighten the supplied drain

hose onto the discharge port using the supplied hose band. (For this, do not use
any adhesive because the drain hose will need to be removed for servicing at a
later date.)

Do not use any odor trap around the discharge port.

[Fig. 4.4.1] (P.3)

As shown in 

3

, install a collecting pipe about 10 cm below the drain ports and give

it a downward pitch of more than 1/100. This collecting pipe should be of VP-30.

Set the end of drain piping in a place without any risk of odor generation.

Do not put the end of drain piping into any drain where ionic gases are generated.

Drain piping may be installed in any direction. However, please be sure to
observe the above instructions.

[Fig. 4.4.2] (P.3)

2. Discharge test

After completing drain piping work, open the HBC controller panel, and test drain dis-
charge using a small amount of water. Also, check to see that there is no water leak-
age from the connections.

3. Insulating drain pipes

Provide sufficient insulation to the drain pipes just as for refrigerant pipes.

Caution:

Be sure to provide drain piping with heat insulation in order to prevent excess
condensation. Without drain piping, water may leak from the unit causing
damage to your property.

HBC CONTROLLER

Unit model

Model name

High pressure 

side

Low pressure 

side

PURY-WP200

(HBC CONTROLLER)
CMB-WP108V-G

ø15.88

(Brazing)

ø19.05

(Brazing)

PURY-WP250

ø19.05

(Brazing)

ø22.2

(Brazing)

A

To outdoor unit

B

End connection (brazing)

C

HBC controller

D

Indoor unit

E

Twinning pipe (field supply)

F

Up to three units for 1 branch hole; total capacity: below 80 (but in same mode, cool-
ing/heating)

A

Cut here

B

Remove brazed cap

Ou

td

oor un

it s

ide

A

Locally procured insulating material for pipes

B

Bind here using band or tape.

C

Do not leave any opening.

D

Lap margin: more than 40 mm

E

Insulating material (field supply)

F

Unit side insulating material

Outdoor unit

High-pressure pipe

10 mm or more

-HBC controller Low-pressure pipe

20 mm or more

Temperature Resistance

100°C min.

A: 25 cm

B: 1.5 – 2 m

A

Downward gradient of more than 1/100

B

Insulating material

C

Supporting bracket

D

Drain discharge port

E

Drain hose (200 mm long, accessory)

F

Cable tie (accessory)

G

Hose band (accessory)

A

HBC controller

B

Indoor unit

C

Collecting pipe

D

Please ensure this length is at least 10 cm.

WT06421X02.book  Page 8  Wednesday, April 25, 2012  8:43 AM

Summary of Contents for City Multi CMB-WP108V-G

Page 1: ...r Conditioners For Building Application INDOOR UNIT CMB WP108V G GB INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit ...

Page 2: ...tdoor unit is lower than the indoor unit F Twinning pipe field supply G Less than 110 m H Less than 60 m I Up to three units for 1 branch port Total capacity less than 80 but in same mode cooling heating J Less than 15 m K Less than 15 m CMB WP108V G Notes 1 Indoor units that are connected to the same branch joint cannot be si multaneously operated in different operation modes Unit m Item Piping p...

Page 3: ...it B End connection brazing C HBC controller D Indoor unit E Twinning pipe field supply F Up to three units for 1 branch hole total capacity below 80 but same in cooling heating mode B A A Cut here B Remove brazed cap E D A C B F A Locally procured insulating material for pipes B Bind here using band or tape C Do not leave any opening D Lap margin more than 40 mm E Insulating material field supply...

Page 4: ... 80 but in same mode cooling heating Water pipework is screw connections Note 1 Connection of multiple indoor units with one connection or joint pipe Total capacity of connectable indoor units Less than 80 Number of connectable indoor units Maximum 3 Sets Selection of water piping Select the size according to the total capacity of indoor units to be installed downstream Please group units that ope...

Page 5: ...ns etc Use of any product except that specified by this company may lead to damage fire explosions etc Do not spray water on electrical parts This could lead to shorting fire smoke electrical shock unit failure etc Do not create a situation where the refrigeration circuit is sealed yet incom plete with oil or refrigerant in the system This may result in an explosion Do not touch electrical compone...

Page 6: ...er where food pets plants precision instru ments or artwork are kept The quality of the food etc may deteriorate Do not use the air conditioner in special environments Oil steam sulfuric smoke etc can significantly reduce the performance of the air conditioner or damage its parts When installing the unit in a hospital communication station or similar place provide sufficient protection against noi...

Page 7: ... resulting in an injury Caution Be sure to install the unit horizontally Install the HBC level less than 1 tilt so that the drain pan can function correctly Install the HBC in an environment where the temperature in always above 0 C 2 3 Securing installation and service space 1 For hanging from the ceiling This is a reference view showing the least installation space Fig 2 3 1 P 2 2 4 Checking the...

Page 8: ...ere is a possibility of condensation Pay special attention to insulation work in the ceiling plenum Fig 4 3 1 P 3 Insulation materials for the pipes to be added on site must meet the following specifications Installation of pipes in a high temperature high humidity environment such as the top floor of a building may require the use of insulation materials thicker than the ones specified in the cha...

Page 9: ...stant polyethylene so that no gap is observed in the joint between indoor unit and insulating material and insulating materials themselves When insulation work is insufficient there is a possibility of condensation etc Pay special attention to insulation work in the ceiling plenum Fig 5 2 1 P 4 Insulation materials for the pipes to be added on site must meet the following specifications This speci...

Page 10: ...plete grounding may cause a risk of electric shock 7 Setting addresses and operating units The address switch of each HBC controller is set to 000 when shipped from the fac tory Set the address switch to 1 the address of the outdoor unit The HBC controller address should generally be set to 1 the address of the outdoor unit However if this would result in it having the same address as another outd...

Page 11: ... more than 1 0 MΩ between the power terminal block and the ground If it is less than 1 0 MΩ do not operate the unit When water has been supplied to the water pipework purge the system of air The details of air purging can be found separately in the water circuit mainte nance manual Caution Never measure the insulation resistance of the terminal block for any con trol cables Incomplete purging of t...

Page 12: ...tions Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STAREET UXBRIDGE MIDDLESEX UB8 1QQ U K ...

Reviews: