background image

7

GB

2. Selecting an installation site

2.1. About the product

This unit uses R410A-type refrigerant.

Piping for systems using R410A may be different from that for systems using
conventional refrigerant because the design pressure in systems using R410A is
higher. Refer to the Data Book for more information.

Some of the tools and equipment used for installation with systems that use other
types of refrigerant cannot be used with the systems using R410A. Refer to the
Data Book for more information.

Do not use the existing piping, as it contains chlorine, which is found in conven-
tional refrigerating machine oil and refrigerant. This chlorine will deteriorate the
refrigerant machine oil in the new equipment. The existing piping must not be
used as the design pressure in systems using R410A is higher than that in the
systems using other types of refrigerant and the existing pipes may burst.

2.2. Installation site

Install the unit in a place not exposed to rain. The HBC controller is designed to
be installed indoors.

Install the unit with adequate space around it for servicing.

Do not install the unit in a place that would result in the piping length restrictions
being exceeded.

Install the unit in a place not exposed to direct radiant heat from other heat
sources.

Do not install the unit in any oily steamy place or near any machine that gener-
ates high frequencies. Doing so may cause a risk of fire, erroneous operation or
condensation.

Install the unit in a location where the noise from the unit will not be a problem.
(Install indoor unit and HBC controller at least 5 m away from each other when
installed in a space with low background noise, e.g., hotel rooms).

Allow enough space and access to ensure water piping, refrigerant piping and
electrical wiring can be easily connected.

Avoid places exposed to the generation, inflow, accumulation or leakage of flam-
mable and sulfuric gases.

Ensure a downward gradient of at least 1/100 for drain piping.

Properly install the unit on a stable, load-bearing surface.

1. For hanging from the ceiling [Fig. 2.2.1] (P.2)

Provide 2 inspection holes 450 mm square in the ceiling surface as shown in
[Fig. 2.3.1] (P.2).

Install the unit in a suitable location (such as in the ceiling of a corridor or in the
bathroom etc) away from places regularly occupied. Avoid installing in the center
of a room.

Ensure hanging bolts are of sufficient pull out strength.

Install a sub drain pan (sold separately, PAC-HBC01DP-E). If leakage from
underneath the HBC would cause no problem in the installed location, installation
of the sub drain pan is not necessary.  [Fig. 2.2.1] (P.2)  [Fig. 2.3.1] (P.2)

Warning:

Be sure to install the unit in a place that can sustain the entire weight.
If there is a lack of strength, it may cause the unit to fall down, resulting in an
injury.

Caution:

Be sure to install the unit horizontally.
Install the HBC level (less than 1° tilt), so that the drain pan can function
correctly.

Install the HBC in an environment where the temperature in always above
0°C.

2.3.  Securing installation and service space

1. For hanging from the ceiling

(This is a reference view showing the least installation space.)

[Fig. 2.3.1] (P.2)

2.4.  Checking the installation site

Check that the difference of elevation between indoor and outdoor units and the
length of refrigerant piping are within the following limitations.

1. CMB-WP108V-G

[Fig. 2.4.1] (P.2)

Notes:
*1 Indoor units that are connected to the same branch joint cannot be simul-

taneously operated in different operation modes.

3. Installing the HBC controller

3.1. Checking the accessories with the HBC 

controller

The following items are supplied with each HBC controller.

3.2. Installing HBC controllers

Installing hanging bolts

Install locally procured hanging bolts (threaded rod) following the procedure given in
the figure. The hanging bolt size is ø10 (M10 screw).
To hang the unit, use a lifting machine to lift and pass it through the hanging bolts.
The suspension bracket has an oval hole. Use a large diameter washer.

[Fig. 3.2.1] (P.2)

Be sure to install the HBC controller horizontally. Check using a level. If
the controller is installed at an angle, drain water may leak out. If the unit
is slanted, loosen the fixing nuts on the hanging brackets to adjust its
position.
Install the HBC level (less than 1° tilt), so that the drain pan can function
correctly.

Caution:

Be sure to install the unit horizontally.
Install the HBC level (less than 1° tilt), so that the drain pan can function
correctly.

<A> Top view

<B> Front view

A

Inspection hole

B

Side of outdoor unit piping

C

Control box

D

Side of indoor unit piping

E

Water inlet

F

Sub drain pan

G

Service space

H

Indoor unit side

*1 Dimensions with which pipe connection can be handled at site

Model name

A

B

CMB-WP108V-G

1600

A

Outdoor unit

B

HBC controller

C

Indoor unit

D

Less than H=50 m (when the outdoor unit is higher than the indoor unit)

E

Less than H1=40 m (when the outdoor unit is lower than the indoor unit)

F

Twinning pipe (field supply)

G

Less than 110 m

H

Less than 60 m

I

Up to three units for 1 branch port
Total capacity: less than 80 (but in same mode, cooling/heating)

J

Less than 15 m

K

Less than 15 m

(Unit: m)

Item

Piping portion

Allowable value

Between outdoor unit and HBC 
controller (refrigerant pipework)

A

110 or less

Water pipework between indoor units and 
HBC controller

f

60 or less

Between 
indoor and 
outdoor units

Above outdoor unit

H

50 or less

Below outdoor unit

H1

40 or less

Between indoor units and HBC controller

h1

15 or less

Between indoor units

h2

15 or less

Pipe Leng

ths

Dif

feren

ce o

f ele

vat

ion

Model name

CMB-WP108V-G

Item

Qty

1

Drain hose

1

2

Cable tie

1

3

Hose band

1

4

Refrigerant connection pipe

2

1

Hanging method
A: Min.30 mm

A

Hanging bolt ø10 (field supply)

B

Washer (field supply)

WT06421X02.book  Page 7  Wednesday, April 25, 2012  8:43 AM

Summary of Contents for City Multi CMB-WP108V-G

Page 1: ...r Conditioners For Building Application INDOOR UNIT CMB WP108V G GB INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit ...

Page 2: ...tdoor unit is lower than the indoor unit F Twinning pipe field supply G Less than 110 m H Less than 60 m I Up to three units for 1 branch port Total capacity less than 80 but in same mode cooling heating J Less than 15 m K Less than 15 m CMB WP108V G Notes 1 Indoor units that are connected to the same branch joint cannot be si multaneously operated in different operation modes Unit m Item Piping p...

Page 3: ...it B End connection brazing C HBC controller D Indoor unit E Twinning pipe field supply F Up to three units for 1 branch hole total capacity below 80 but same in cooling heating mode B A A Cut here B Remove brazed cap E D A C B F A Locally procured insulating material for pipes B Bind here using band or tape C Do not leave any opening D Lap margin more than 40 mm E Insulating material field supply...

Page 4: ... 80 but in same mode cooling heating Water pipework is screw connections Note 1 Connection of multiple indoor units with one connection or joint pipe Total capacity of connectable indoor units Less than 80 Number of connectable indoor units Maximum 3 Sets Selection of water piping Select the size according to the total capacity of indoor units to be installed downstream Please group units that ope...

Page 5: ...ns etc Use of any product except that specified by this company may lead to damage fire explosions etc Do not spray water on electrical parts This could lead to shorting fire smoke electrical shock unit failure etc Do not create a situation where the refrigeration circuit is sealed yet incom plete with oil or refrigerant in the system This may result in an explosion Do not touch electrical compone...

Page 6: ...er where food pets plants precision instru ments or artwork are kept The quality of the food etc may deteriorate Do not use the air conditioner in special environments Oil steam sulfuric smoke etc can significantly reduce the performance of the air conditioner or damage its parts When installing the unit in a hospital communication station or similar place provide sufficient protection against noi...

Page 7: ... resulting in an injury Caution Be sure to install the unit horizontally Install the HBC level less than 1 tilt so that the drain pan can function correctly Install the HBC in an environment where the temperature in always above 0 C 2 3 Securing installation and service space 1 For hanging from the ceiling This is a reference view showing the least installation space Fig 2 3 1 P 2 2 4 Checking the...

Page 8: ...ere is a possibility of condensation Pay special attention to insulation work in the ceiling plenum Fig 4 3 1 P 3 Insulation materials for the pipes to be added on site must meet the following specifications Installation of pipes in a high temperature high humidity environment such as the top floor of a building may require the use of insulation materials thicker than the ones specified in the cha...

Page 9: ...stant polyethylene so that no gap is observed in the joint between indoor unit and insulating material and insulating materials themselves When insulation work is insufficient there is a possibility of condensation etc Pay special attention to insulation work in the ceiling plenum Fig 5 2 1 P 4 Insulation materials for the pipes to be added on site must meet the following specifications This speci...

Page 10: ...plete grounding may cause a risk of electric shock 7 Setting addresses and operating units The address switch of each HBC controller is set to 000 when shipped from the fac tory Set the address switch to 1 the address of the outdoor unit The HBC controller address should generally be set to 1 the address of the outdoor unit However if this would result in it having the same address as another outd...

Page 11: ... more than 1 0 MΩ between the power terminal block and the ground If it is less than 1 0 MΩ do not operate the unit When water has been supplied to the water pipework purge the system of air The details of air purging can be found separately in the water circuit mainte nance manual Caution Never measure the insulation resistance of the terminal block for any con trol cables Incomplete purging of t...

Page 12: ...tions Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STAREET UXBRIDGE MIDDLESEX UB8 1QQ U K ...