44
6 INSTALLATION AND WIRING
6.4 Wiring of Terminal Block for Module Power Supply and FG
6.4
Wiring of Terminal Block for Module Power Supply
and FG
Tightening torque
Tighten the terminal block mounting screws within the following specified torque range.
Tightening the screws too much may damage the safety remote I/O module case.
Wire to be used
The following table describes the wire to be connected to the terminal block for module power supply and FG.
Applicable solderless terminal
The following table lists the applicable solderless terminal.
Installing and removing the terminal block
To remove the terminal block, loosen the terminal block mounting screws with a flathead screwdriver.
To install the terminal block, tighten the terminal block mounting screws with a flathead screwdriver.
Failure to secure the terminal block may cause drop, short circuit, or malfunction.
Screw type
Tightening torque range
Terminal block mounting screw (M2.5 screw)
0.2 to 0.3N
m
Diameter
Type
Material
Temperature rating
22 to 16 AWG
Stranded wire
Copper wire
75
or higher
Product name
Model
Applicable wire size
Contact
Bar solderless terminal
AI0.34-8TQ
0.34
PHOENIX CONTACT GmbH & Co.
KG
AI0.5-8WH
0.5
AI0.5-10WH
AI0.75-8GY
0.75
AI0.75-10GY
AI1-8RD
1.0
AI1-10RD
AI1.5-8BK
1.5
AI1.5-10BK
Bar solderless terminal tool
CRIMPFOX6