58
59
To check the information about the units whose Filter Signs are turned on
1. Touch the
3
[Filter Sign] tab, and check the number of units whose Filter Signs are turned on, the
names of the groups they belong to, and their addresses.
・
When a Filter Sign appears, clean, wash, or replace the filter as necessary.
Refer to air conditioner or LOSSNAY manual for details.
・
When
appears on the
Reset
button, the button will not be available.
To reset the Filter Sign after cleaning the filter
4
Reset
button
:
Clears the specific Filter Sign.
5
All Reset
button
:
Clears all Filter Signs.
3
5
Number of Filter Signs detected
Displays the number of Filter Signs that
have been detected.
4
Main Menu > System Management
2
Using the System-Changeover function
Main Menu > System Management > System-Changeover
Use the System-Changeover mode to automatically change a group of indoor units that are connected to the same
outdoor unit over between the Cooling and Heating modes according to temperature changes.
Use this function to control the indoor units that do not have an automatic changeover mode. They can be operated in
the Heating mode in the morning, and then automatically changed over to the Cooling or Heating mode all at once in
the afternoon, for example, without the need to manually change the mode via each remote controller.
* This function should not be used in conjunction with the System-Changeover function on the outdoor unit or
other system controllers.
* When the System-Changeover mode is set to [Auto], the operation mode is selected based on the demands
of the majority of the group, taking into consideration the capacity of each indoor unit. When it is set to
[Representative Group], the operation mode is selected based on the demand of the representative group
through updating its status every 15 minutes and changing over to the cooling or heating mode as necessary.
Because the operation mode is selected based on the demands of the representative group or of the majority
of the groups, not all areas may be air conditioned to the optimum temperature.
・
If the temperature limits are set too high or low (see P44), the System-Changeover function may
not work properly and the units may not operate in the expected mode (Cooling or Heating).
・
The System-Changeover function is not available for the following types of products:
Simultaneous Cooling/Heating units (with Auto mode), Mr. SLIM®, LOSSNAY, and DIDO
controller.
1
2
・
When appears on the “System-Changeover” button, this function will not be available for
selection.
Usage - Main Menu Settings
System Management (cont'd)