background image

34   0.5(1.33)

50   1(1.96)

60

26.5(1.04)

18.3(0.72)

21

.3

(0.83)

68(2.68)

24(0.94)

25

(0.98)

200

+1  0

M4 mounting screw

19

2   1

4.3(0.17)

2-4.5   6 mounting screw

1)

6)

d

7)

Storage
sheet

6)

c

33(1.30)

+1

  0

(2.36)

(7.87)

25

(0.98)

25(0.98)

(7.56)

A

J65FBTA42-16DTE

Y8

Y9

YA

YB

YC

YD

YE

YF

Y

Y

Y

Y

Y

Y

Y

Y

POWER

PROTECT

4.1(0.16)

35(1.37)

21.7(0.85)

32(1.26)

6(0.24)

48(1.89)

6(0.24)

 

Unit:mm(inch)

 

 

External connection 

Communication connector 

Pin 
No. 

LINK IN 

LINK OUT

1 SLD  SLD 
2 DB 

DB 

3 DG 

DG 

4 DA 

DA 

5 No 

pins  Empty 

Power connector 

Pin 
No. 

UNIT 

POWER 

AUX. 

1 +24V(UNIT)

+24V(I/O) 

2 Empty  Empty 
3 24G(UNIT)  24G(I/O) 
4 Empty  Empty 

 (FG) 

 (FG) 

I/O connector 

Pin  
No. 

Signal 

name 

Pin  
No. 

Signal

name

1 +24V 

1 Empty

2 X1 

2

Y9 

3 24G 

3

24G 

4 X0 

4

Y8 

X0

X1

 

5 Empty 

Y8

Y9

5 Empty

1 +24V 

1 Empty

2 X3 

2

YB 

3 24G 

3

24G 

4 X2 

4

YA 

X2

X3

 

5 Empty 

YA

YB

5 Empty

1 +24V 

1 Empty

2 X5 

2

YD 

3 24G 

3

24G 

4 X4 

4

YC 

X4

X5

 

5 Empty 

YC

YD

5 Empty

1 +24V 

1 Empty

2 X7 

2

YF 

3 24G 

3

24G 

4 X6 

4

YE 

X6

X7

 

5 Empty 

YE

YF

5 Empty

Unit mounting screw

(FG)

I/O connector

Costant voltage

circuit

4-wire type sensor (source output)

110

130

Communication

circuit

Insulation

Terminal

resistance

select switch


5

LINK IN 



5

LINK OUT

UNIT POWER

5

DC/DC

AUX.

5

5

5

L

L

5

Load power

Detection circuit

3-wire type sensor (source output)

2-wire type sensor (source output)

Black

Brown
Blue

White

Black

Brown
Blue

Brown

Blue

 

 

 

ON

ON

TERMINATION
110

130

40

10

4

1

2

20

8

2

4

1

STATION NO

B RATE

Communication adapter(back)

Communication adapter(front)

Connector for connection to main module

4)

5)

b

a

9)

Connector for connection
to communication adapter

10)

3)

8)

Communication
adapter

Main module

2)

1 2

 

2. Name and Setting of Each Area

 

No.

Item Description 

LED name

Confirmation details 

POWER 

ON:  Power supply ON  OFF: Power supply OFF 

PROTECT 

Lights up when the output section protection function is 

working (During the protect operation, fuse interruption is 

searched in the master unit side) 

L RUN 

ON: Normal 

communication 

OFF:  Communication shut off (time expiration error) 

L ERR. 

ON:  Communication data error 

Flash at regular intervals: 

Indicates that the station number setting or 

transmission speed setting switch position was 

changed while power is ON 

Flash at irregular intervals:  

When the setting of the terminal resistor is wrong; 

when the cable for the module or CC-Link is 

affected by noise 

OFF: Normal communication 

1) 

Operating 

status indicator 

LEDs 

X0 to X7 

Y8 to YF 

ON: Input/Output 

ON 

OFF: Input/Output OFF 

 

Setting switch status 

Setting value

4 2 1 

Transmission speed

0 OFF 

OFF 

OFF 156 

kbps 

1 OFF 

OFF 

ON 625 

kbps 

2 OFF 

ON 

OFF 2.5 

Mbps 

3 OFF 

ON 

ON 5.0 

Mbps 

 

4 ON 

OFF 

OFF 10 

Mbps 

 

2) 

Transmission 

speed setting 

switch 

Be sure to set the transmission speed within the above range. 

Remove the communication adapter on the top part of the module to 

set the transmission speed. (When shipped from the factory, all 

settings are set to OFF.) 
Select “10”, “20” or “40” to set the tens place of the station number. 

Select “1”,”2”,”4” or “8” to set the ones place of the station number. 

Always set the station number within the range of 1 to 64. (*1) 

(Example)  Set the switches as below when setting the station number 

to 32: 

Tens place 

Ones place 

Station 

number 

40 20 10  8  4  2  1 

 

32 

OFF ON  ON OFF OFF

ON OFF

 

3)  Station number 

setting switch 

Remove the communication adapter on the top part of the module to 

set the station number. (When shipped from the factory, all settings 

are set to OFF.) 
The terminal resistor can be turned to the ON setting by using the 

select switch. 

DIP switch1  DIP switch2 

Contents 

OFF 

OFF 

No terminal resistance 

ON OFF 

110

Ω

 resistor ON 

OFF ON 

130

Ω

 resistor ON 

 

ON ON 

Setting 

prohibited 

 

4) 

Terminal 

resistance 

setting switch 

(When shipped from the factory, all settings are set to OFF.) 

 

 Silk 

Contents 

a LINK 

 

IN 

 

Connector for connecting the 

transmission line from the IN side (master 

station side). (Male 4 pins) 

 

b LINK  

OUT  

Connector for connecting the 

transmission line from the OUT side.  

Be sure to attach the waterproof cap 

when not in use. (Female 5 pins) 

(Tightening torque range: 29 to 34 N.cm) 

 

5) 

Waterproof 

connector for 

transmission 

line *2 

 

 

 Silk 

Contents 

c UNIT 

POWER  Connector for supplying power to the 

module. (Male 5 pins) 

 

d  

AUX. 

 

Connector for supplying power to a load, 

etc. (Male 5 pins) 

 

6) 

Waterproof 

connector for 

power line *2 

 

7) 

Waterproof 
connector for 
input 
connection *2 

Waterproof connector for connection I/O signal. (Female 5 pins) 
Be sure to attach waterproof cap A6CAP-WP2 (sold separately) when 
not in use. (Tightening torque range: 29 to 34 N.cm) 

8)  FG metal fitting For module FG terminal (tightening torque range: 78 to 118 N.cm) 

9) 

Communication 
adapter fixing 
screw 

When replacing the main body online or changing switch setting, 
attach/remove the communication adapter with this screw. 
(Tightening torque range: 42 to 58 N.cm) 

10)

Module 
attachment 
hole 

Screw hole for module attachment. 2-4.5 X 6 length hole  
(M4 attachment screw) (Tightening torque range: 78 to 118 N.cm) 

*1: Duplicate station number cannot be set. 
*2: Waterproof connector (based on IEC947-5-2, M12 type) 

 

Reviews: