(4) If the fuse of the high-speed counter module is blown, it can be confirmed by
monitoring the link special registers for other station fuse blown status in the
master station.
SW0088 to SW008B: Fuse blown status (0: normal, 1: fuse blown)
If the "fuse blown" bit is set, check the following once.
Cause Corrective
Action
External power supply is not wired
Wire an external power supply to the high-speed
counter module.
When using the external output (EQU1 to EQU2)
terminals, wire an 10.2VDC to 30VDC external
power supply as it is needed.
Even when not using external output terminals
(EQU1 to EQU2), wire the 12/24V terminal (pin
number: 26) and the COM terminal (pin number:
27) to an external power supply. (Refer to Section
4.6.5)
Fuse is blown
The coincidence output function signal is not
output.
(Fuse for external power supply which operates
the internal photocoupler when the EQU terminals
are used)
The fuse cannot be changed by the user. Please
consult your local Mitsubishi representative.
Downloaded from
Summary of Contents for AJ65BT-D62
Page 2: ...Downloaded from ManualsNet com search engine ...
Page 102: ...MELSEC A 10 PROGRAMMING 10 24 Downloaded from ManualsNet com search engine ...
Page 105: ...MELSEC A 10 PROGRAMMING 10 27 Downloaded from ManualsNet com search engine ...
Page 107: ...MELSEC A 10 PROGRAMMING 10 29 Downloaded from ManualsNet com search engine ...
Page 109: ...MELSEC A 10 PROGRAMMING 10 31 Downloaded from ManualsNet com search engine ...
Page 113: ...MELSEC A 10 PROGRAMMING 10 35 Downloaded from ManualsNet com search engine ...
Page 115: ...MELSEC A 10 PROGRAMMING 10 37 Downloaded from ManualsNet com search engine ...
Page 117: ...MELSEC A 10 PROGRAMMING 10 39 Downloaded from ManualsNet com search engine ...
Page 142: ...Appendix 4 MELSEC A APPENDICES MEMO Downloaded from ManualsNet com search engine ...
Page 145: ...Downloaded from ManualsNet com search engine ...