Table 25-1
Characteristic setting of optional setting module
< Characteristics setting of G1 module >
1
2
No.
1
2
Mark
Ig
Tg
Adjustable setting range
0.1 to 1.0
✕
In (0.1 steps)
3.0-1.5-0.8-0.5-0.3-0.15-
0.1 -
0.1-0.15-0.3-0.5-0.8-1.5-3.0 s
Accuracy
±
20%
±
20%
Setting for shipment
1.0
3s(TRIP)
Setting item
Ground fault
pick-up current
Ground fault
time
(TRIP)
(ALARM)
(at 1.5
×
Ig)
Oper
ation time (s)
Ground fault current (% of CT rating In)
1
Pick-up current: Ig
2
Operating time: Tg
0.1
1.0
3.0
±
20%
0.1
(0.04 to 0.1s)
0.15
±
20%
¡
When the 3pole breaker is used on a 3phase-4wires system, the
neutral CT (NCT) is required for ground fault protection. As for the
NCT installation, refer to instruction manual (included in the product).
¡
In the case of
✽
low-rating of AE630-SW, G1 module can not be
mounted.
✽
AE630-SW low rating type: 500A, 315A and 250A
Note: If the ground fault current setting Ig is 0.1, it is neces-
sary to control the power supply. (Ground fault pro-
tection does not operate correctly without power
supply.)
1
Pick-up current: I
Δ
n
1A
10A
3.0s
±
20%
0.15s
±
20%
2
Operation time: Te
0.1s
(0.04 ~ 0.1s)
Oper
ation time (s)
Earth leakage current (A)
< Characteristic setting of E1 module >
By combining the ETR with Earth leakage protection(ER) and
External ZCT, earth leakage protection is possible. Control
supply is necessary for this function.
ZCT for load circuit
ZCT with primary conductors
ZCT for ground wire of transformer types
2
1
AE630-SW ~ AE1600-SW 3P
AE630-SW ~ AE1600-SW 4P
AE2000-SW ~ AE3200-SW 3P
AE2000-SW ~ AE3200-SW 4P
ZCT types
ZCT163
ZCT323
ZCT324
ACB types, poles
As for outline dimensions, refer to AE-SW catalogue,
and make your choice in reference to the BUSBAR size.
AE630-SW ~ AE1600-SW 3P
AE1250-SW ~ AE1600-SW, AE2000-SWA 3P
ZCT types
ZTA1200A
ZTA2000A
ACB types, poles
ZCT types
ZT15B ZT30B ZT40B ZT60B ZT80B ZT100B
¡
Be sure to combine with ZCT of our products.
¡
As for the ZCT installation, reter to instruction manual (included in
the product).
Table 25-2
No.
q
w
Mark
I
Δ
n
Te
Adjustable setting range
1A-2A-3A-5A-10A
3-1.5-0.8-0.5-0.3-0.15-
0.1s -
0.1-0.15-0.3-0.5-0.8-1.5-3 s
Accuracy
0%
–30%
±
20%
Setting for shipment
10A
3s(TRIP)
Setting item
ER pick-up
current
ER time
(TRIP)
(ALARM)
(at 1.5
×
I
Δ
n)