(N) Operation via communication and its settings
70
• Program example for writing data to EEPROM
as follows:
Frequency setting command Y100D
Y100E
Frequency setting completion X100D
X100E
For EEPROM, write is made only once when Y100E is switched on.
If the set data is changed with Y100E on, it is not reflected on the inverter.
Program example for fault record reading
The following program reads fault records of station 1 inverter to D1.
• Faults history No. 1, No. 2 reading instruction code: H74 (hexadecimal)
For the error codes, refer to the Instruction Manual (Detailed) of the FR-A800/FR-F800 inverter.
The reply code at the time of instruction code execution is set to D2. (Refer to
Program example for resetting the inverter at inverter error
The following is a program example for resetting station 1 inverter.
NOTE
• The above inverter reset using RY1A may be made only when an inverter error occurs. When
Pr.349 Communication reset
selection
= "0", inverter reset is available independently of the operation mode.
• When using the instruction code execution request (RYF) with the instruction code (HFD) and data (H9696) to reset the
inverter, set a value other than "0" in
Pr.340 Communication startup mode selection
or change the operation mode to the
network operation mode. (For the program example, refer to
• Refer to
for operation conditions of inverter reset.
<Timing chart when writing to RAM>
Y100D
W101
Inverter
running
frequency
Y100E
(
∗
2
)
(
∗
1
)
W101
Inverter
running
frequency
Reflect to the inverter when Y100E turns on
<Timing chart when writing to EEPROM>
Write error history No.1 and No.2 read
code (H74) to RWw2.
Turn off the instruction code execution request
(RY0F)
Turn on the instruction code execution request
(RY0F)
Read alarm data (RWr3) and reply code
(RWr2) to D1 and D2 when the instruction
code execution completion (RX0F) turns on.
Check the data link status of the station 1
(0)
SM1536
SD1536.0 SD1540.0
M0
(4)
M0
X20
PLS
M300
(8)
M300
SET
M301
(10)
M301
X100F
MOV
H74
W102
SET
Y100F
RST
M301
SET
M302
(17)
M302
X100F
MOV
W3
D1
MOV
W2
D2
RST
Y100F
RST
M302
(25)
END
Check the data link status of the station 1
Turn on the error reset request flag (RY1A)
Turn off the error reset request flag (RY1A)
when the error status flag (RX1A) is off.
(0)
SM1536
SD1536.0 SD1540.0
M0
(4)
M0
X101A
X20
Y101A
(8)
END