(N) Operation via communication and its settings
18
Error reset operation selection at inverter fault (Pr.349)
• In the External operation mode or the PU operation mode, use this parameter to disable an error reset command sent
through the Ethernet network (CC-Link IE Field Network Basic) or from a communication option.
Operation mode switching and communication startup mode (Pr.79,
Pr.340)
• Check the following before switching the operation mode.
- The inverter is at a stop.
- Both the STF and STR signals are off.
- The
Pr.79 Operation mode selection
setting is correct. (Check the setting on the operation panel of the inverter.)
• The operation mode at power ON and at restoration from instantaneous power failure can be selected. Set a value other
than "0" in
Pr.340
Communication startup mode selection
to select the Network operation mode.
• After the inverter starts up in the Network operation mode, parameter write can be commanded via the network.
NOTE
• The changed value in
Pr.340
is applied after the next power-ON or inverter reset.
• The
Pr.340
setting can be changed on the operation panel in any operation mode.
• When setting a value other than "0" in
Pr.340
, make sure that the communication settings of the inverter are correct.
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration time
Instruction Manual (Detailed) of the FR-A800/FR-F800 inverter
Pr.79 Operation mode selection
Instruction Manual (Detailed) of the FR-A800/FR-F800 inverter
Pr.340 Communication startup mode selection
Instruction Manual (Detailed) of the FR-A800/FR-F800 inverter
Pr.550 NET mode operation command source selection
Pr.551 PU mode operation command source selection
Pr.1431 Ethernet signal loss detection function selection
Pr.1432 Ethernet communication check time interval
CAUTION
When Pr.502 = "3" and a communication line error occurs, or Pr.502 = "4" and a communication line
error or a communication option fault occurs, the operation continues. When setting "3 or 4" in
Pr.502, provide a safety stop countermeasure other than via communication. For example, input a
signal (RES, MRS, or X92) through an external terminal or press the PU stop on the operation panel.
Pr.349 setting
Description
0 (initial value)
Error reset is enabled independently of operation mode
1
Error reset is enabled only in the network operation mode