(N) Operation via communication and its settings
60
• Reply code definition
The reply to the instruction execution is set to RWr2, 10, 12, 14, 16, 18.
When executing the frequency setting (RYD, RYE) or instruction code execution (RYF), check the reply code (RWr2) in
the remote register after execution.
The contents of the reply code 1 are changed when torque commands are given or the torque is limited from the FR-A800-E (when
Pr.544
="14,
18, 24, or 28").
The upper 4 bits of the reply code 1 are used as the reply code to the torque command / torque limit, and the lower 4 bits are used as the reply
code to the frequency command.
Example) The error code is H0030 when the torque command value is outside the setting range.
Instruction codes
Set the instruction code using a remote register (RWw) (Refer to
The definition read by the instruction code is stored in the remote register (RWr). (Refer to
Data
Item
Alarm definition
Remarks
Reply code
H0000
Normal
No error (normal completion of instruction code
execution)
• Reply code to RWr2 when
Pr.544
= 0
• Reply code to RWw10, 12, 14,
16, and 18 when
Pr.544
= 18
H0001
Write mode error
Parameter write was attempted during operation
other than a stop in the network operation mode.
H0002
Parameter selection error
Unregistered code number was set.
H0003
Setting range error
Set data is outside the permissible data range.
Reply code 1
H00
Normal
No error (normal completion of instruction code
execution)
Reply code to RWr2 when
Pr.544
≠
0
H01
Write mode error
Parameter write was attempted during operation
other than a stop in the network operation mode.
H03
Frequency command /
torque command / torque
limit setting range error
The value outside the range is set.
Reply code 2
H00
Normal
No error (normal completion of instruction code
execution)
H01
Write mode error
Parameter write was attempted during operation
other than a stop in the network operation mode.
H02
Parameter selection error
Unregistered code number was set.
H03
Setting range error
Set data is outside the permissible data range.
Item
Read/
write
Instruction
code
Description
Operation mode
Read
H7B
H0000: Network operation mode
H0001: External operation mode, External JOG operation mode
H0002: PU operation mode, External/PU combined operation mode 1 and 2,
PUJOG operation mode
Write
HFB
H0000: Network operation mode
H0001: External operation mode
H0002: PU operation mode (
Pr.79
= "6")
Monitor
Output frequency/
speed
,
Read
H6F
H0000 to HFFFF
Output frequency: Increments 0.01 Hz
(The display can be changed to the rotations per minute using
Pr.37
,
Pr.144
and
Pr.811
. (Refer to the Instruction Manual (Detailed) of the FR-A800/FR-F800
inverter.))
Output current
Read
H70
H0000 to HFFFF
Output current (hexadecimal): Increments 0.01 A / 0.1 A
Output voltage
Read
H71
H0000 to HFFFF
Output voltage (hexadecimal): Increments 0.1 V
Special monitor
Read
H72
H0000 to HFFFF: Check the data of the monitor selected by the instruction code
HF3.
Special monitor
selection No.
Read
H73
H01 to HFF: Monitor selection data
Refer to monitor code. (Refer to
.)
Write
HF3
Bit15
Bit0
Reply code2
Reply code1
Reply code to
the torque command /
torque limit
Reply code to
the frequency
command
Bit15
Bit0
Reply code to
the torque command
0
0
0
0
0
0
0
0
0
0
1
1
0
0
0
0