7
WIRING
3.2 Wiring fundamentals
3.2.1 Cable size
Select the recommended cable size to ensure that a voltage drop will be 2% max.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque
to decrease especially at the output of a low frequency.
The following table indicates a selection example for the wiring length of 20m.
400V class (when input power supply is 440V)
Applicable Inverter Type
Terminal Screw Size
*
4
Tightening Torque [Nm]
Crimping Terminal
R/L1, S/L2, T/L3
U, V, W
FR-A 740-00023–00126-EC
M4
1.5
2-4
2-4
FR-A 740-00170-EC
M4
1.5
2-4
2-4
FR-A 740-00250-EC
M4
1.5
5.5-4
5.5-4
FR-A 740-00310-EC
M5
2.5
5.5-5
5.5-5
FR-A 740-00380-EC
M5
2.5
8-5
8-5
FR-A 740-00470-EC
M6
4.4
14-6
8-6
FR-A 740-00620-EC
M6
4.4
14-6
14-6
FR-A 740-00770-EC
M6
4.4
22-6
22-6
FR-A 740-00930-EC
M8
7.8
22-8
22-8
FR-A 740-01160-EC
M8
7.8
38-8
38-8
FR-A 740-01800-EC
M8
7.8
60-8
60-8
FR-A 740-02160-EC
M10
14.7
60-10
60-10
FR-A 740-02600-EC
M10
14.7
60-10
60-10
FR-A 740-03250-EC
M10/M12
14.7
80-10
80-10
FR-A 740-03610-EC
M10/M12
14.7
100-10
100-10
FR-A 740-04320-EC
M12/M10
24.5
150-12
150-12
FR-A 740-04810-EC
M12/M10
24.5
150-12
150-12
FR-A 740-05470-EC
M12/M10
24.5
100-12
100-12
FR-A 740-06100-EC
M12/M10
24.5
100-12
100-12
FR-A 740-06830-EC
M12/M10
24.5
150-12
150-12
FR-A 740-07700-EC
M12/M10
24.5
150-12
150-12
FR-A 740-08660-EC
M12/M10
24.5
C2-200
C2-200
FR-A 740-09620-EC
M12/M10
24.5
C2-200
C2-200
FR-A 740-10940-EC
M12/M10
24.5
C2-250
C2-250
FR-A 740-12120-EC
M12/M10
24.5
C2-200
C2-250