Mirus LINEATOR Installation, Operation And Maintenance Manual Download Page 9

L

INEATOR

 Operation & Maintenance Manual 

 

 

 

AUHF-M001-A15 

 

3.4 Grounding 

 

Consideration must be given to equipment 
grounding (case and core) and must be made in 
accordance with all applicable electrical codes.  

 

 4.0 Storage 

 

Condensation and moisture absorption must be 
prevented during storage.  The

 

Lineator™

  

must 

be stored in a warm, dry location. Ventilation 
openings should be covered to keep out dust.  If 
outdoor storage cannot be avoided, the

 

Lineator™

 

must be protected to prevent entrance of water, 
moisture and foreign material.  

 

 5.0 Maintenance 

 

Caution:

  

Before entering or working on the

 

Lineator™

it should be de-energized, properly 

grounded and isolated.  Only qualified service 
technicians should be allowed to maintain the filter. 
While servicing the Lineator, all relevant safety 
standards must be followed, including all 
applicable electrical codes and NFPA 70E – 
Standard for Electrical Safety in the Workplace.  
 

5.1 Periodic Inspection and Maintenance 

 

The

 

Lineator™

 

has no moving or active parts and 

therefore requires only minimal periodic 
maintenance when installed in a clean and well 
ventilated environment.  Annual maintenance is 
recommended.  This should include:

 

 

  5.1.1   Visual inspection for evidence of loose 

connections, dirt, moisture, rusting, 
corrosion, and deterioration of the 
insulation, varnish or paint.   

 

Observations should be made for signs of 
overheating and overvoltage creeping. 

 

Corrective measures should be taken as 
necessary

.  

5.1.2 

For early detection of any developing 
hotspots, an infrared scan can be 

performed while the

 

Lineator™

 

is 

operating under its heaviest load 
condition. 

5.1.3 

Lineator™  capacitors are equipped with 

an internal ‘Tear-Off’ fuse pressure 
interrupter to prevent explosive failure. At 
the end of its service life, pressure within 
a capacitor will build due to the release of 
gases as its dielectrics breakdown. The 
covers on the cans are designed to 
expand or bulge and Tear-Off the internal 
fuse as this pressure builds. Capacitors 
should be inspected regularly and 
replaced when found to have an 
expanded cover. 

5.1.4 

Even though they may appear fine 

physically, capacitors may require 
replacement if their capacitance value 
has degraded significantly. With the 
Lineator de-energized and locked out, 
pull capacitor fuses and measure the 
capacitance of each capacitor. If this 
value indicates a drop in capacitance of 
more than 5%, the capacitor should be 
replaced.  
 

Caution:

  Ensure that power to the Lineator™ has 
been turned off and safely isolated before 
replacing failed capacitors.  

  

5.1.5 

Most  Lineators™  are also equipped with 

capacitor fuses. Capacitor fuses are 
intended to provide additional protection 
against overloading of the capacitors and 
upstream reactor. A blown fuse can be 
detected by checking for illumination of 
the blown fuse indicator when this option 
has been purchased or by testing for 
conductivity. If the blown fuse indicator is 
on  or the fuse is open,  it  should be 
replaced. 
 

 

Caution:

  Ensure that power to the Lineator™ has 

been turned off and safely isolated before 
replacing blown fuses.  

 
  5.1.6 

Measuring the current in each of the 3 
phases of the capacitor circuit can be 
another  method of determining the 
condition of the capacitors. The 
capacitors can be assumed to be in good 
operating  condition when all 3 phases 
carry approximately the same amount of 
load current. Measurements should be 
taken at the input to the capacitor 
distribution block and can be done at any 
loading condition. Phase currents that are 
imbalanced by more than 10%, indicate a 
capacitor failure or blown fuse. When the 
filter capacitor bank has been connected 
in a wye configuration (ie. two jumpers 
create  a common point  on each set of 
three capacitors),  locating the problem 
capacitor(s) 

can be achieved by 

measuring the voltage between the 
common neutral point of each set  to 
ground. If the voltage difference is greater 
than 10V, at least one of the capacitors in 
that set has  failed or has a blown fuse. 
Testing  should be conducted annually or 
whenever the unit seems to be operating 
in an abnormal manner. 

Summary of Contents for LINEATOR

Page 1: ...MIRUS International Inc INSTALLATION OPERATION AND MAINTENANCE GUIDE THE LINEATOR ADVANCED UNIVERSAL HARMONIC FILTER AUHF AUHF M001 A15...

Page 2: ...nance of the LineatorTM AUHF and its auxiliary equipment WARNING OPENING ENCLOSURES EXPOSES HAZARDOUS VOLTAGES ALWAYS REFER SERVICE TO QUALIFIED PERSONNEL ONLY WARNING As standards specifications and...

Page 3: ...TER AUHF INSTALLATION OPERATION AND MAINTENANCE GUIDE AUHF M001 A15 14 Dec 2021 MIRUS International Inc 31 Sun Pac Blvd Brampton Ontario Canada L6S 5P6 1 888 TO MIRUS 1 888 866 4787 Tel 905 494 1120 F...

Page 4: ...on maintenance use or operation 3 Exclusive Remedy If the LINEATOR AUHF does not conform with the warranties set out above the Customer must notify MIRUS of the defective unit within the applicable wa...

Page 5: ...lation 2 3 1 Location 2 3 2 Inspection and Energization 2 3 3 Handling 2 3 4 Grounding 3 4 0 Storage 3 5 0 Maintenance 3 5 1 Periodic Inspection and Maintenance 3 5 2 Cleaning 4 5 3 Drying of Core and...

Page 6: ...AUHF M001 A15 v...

Page 7: ...ating the possibility of attracting harmonics from upstream non linear loads 2 3 System Resonance The natural resonance frequency of the Lineator is below that of any predominant harmonic therefore in...

Page 8: ...ectrical Safety in the Workplace 3 2 1 Before Energization Verify that the Lineator external feeder circuit breaker is in the OFF OPEN position so that unit is de energized Check all bolts nuts screws...

Page 9: ...rnal fuse as this pressure builds Capacitors should be inspected regularly and replaced when found to have an expanded cover 5 1 4 Even though they may appear fine physically capacitors may require re...

Page 10: ...or reactor before installation or after an extended shutdown under relatively high humidity conditions internal and or external heating methods can be used See ANSI IEEE C57 94 1982 for a description...

Page 11: ...as of rated kW 5 to 75HP 20 100HP 15 Efficiency 99 Elevation 3300ft 1000m above sea level Ambient Temperature 104 Deg F 40 Deg C Ventilation Convection air cooled Winding Material Copper Insulating Va...

Page 12: ...34 292 MT4 800 363 1006 456 MT4 780 354 1006 456 400 315 470 498 375 398 325 345 397 349 825 374 LT1 E 1031 467 805 365 LT1 E 1031 467 450 355 530 562 424 449 369 391 448 394 870 395 1076 488 870 395...

Page 13: ...46 SU4 345 156 434 197 150 110 388 411 353 374 204 216 187 198 143 125 553 251 627 285 365 166 MT3 E 469 213 175 132 241 255 221 234 166 148 MT3 390 177 492 223 200 150 274 290 250 265 191 168 415 189...

Page 14: ...250 185 350 300 250 425 400 300 220 450 350 300 560 500 350 250 500 400 350 630 630 400 315 600 500 400 710 710 500 400 700 600 500 900 800 600 450 800 700 600 1000 1000 700 500 1000 800 700 1250 100...

Page 15: ...LINEATOR Operation Maintenance Manual AUHF M001 A15 9 7 5 Lineator Type Operational Curve...

Page 16: ...06 18 00 457 14 25 362 20 00 508 18 00 457 SU4 SU4 E 40 00 1016 22 00 559 19 75 502 22 00 559 20 00 508 20 00 508 MT3 MT3 E 45 00 1143 26 00 661 21 00 534 25 00 635 21 50 546 19 00 483 MT4 MT4 E 51 50...

Page 17: ...ch fuseholder with power applied to the filter If voltage is not near 0 fuse is blown and should be replaced Make sure that fuse rating used is appropriate for capacitor size Check with the factory fo...

Page 18: ...NOTES...

Page 19: ...NOTES...

Page 20: ...US International Inc 31 Sun Pac Blvd Brampton Ontario Canada L6S 5P6 1 888 TO MIRUS 1 888 866 4787 Tel 905 494 1120 Fax 905 494 1140 E Mail mirus mirusinternational com Website www mirusinternational...

Reviews: