Mirus LINEATOR Installation, Operation And Maintenance Manual Download Page 8

L

INEATOR

 Operation & Maintenance Manual 

 

 

 

AUHF-M001-A15 

 

 

 3.0 Installation 

 

3.1  Location

  

 
Location of the

 

Lineator™

 

should be made with 

consideration given to accessibility, ventilation and 
atmospheric conditions. 

Installation locations 

should be free of contaminants including dust, 
fertilizer, excessive moisture, corrosive gases, 
flammable materials or chemical fumes.  Filtered 
air may be considered to reduce maintenance 
where air born contaminants are a problem. 
 
Sufficient clearances from walls and other 
obstructions should be provided to permit 
unrestricted opening of hinged and removable 
doors, covers and panels for the purpose of wiring 
terminations, inspection, maintenance and testing. 
Also,

 

proper ventilation requires at least 6 in. 

(155mm) clearance 

at all ventilation openings, 

with the exception of the rear face of wall 
mountable enclosures such as the SU1, SU2, SU3 
and  SU4  type enclosures.  Ambient temperature 
must not exceed 104 Deg F (40 Deg C). In

 

enclosed rooms,

 

minimum air circulation of 100 ft

3

min per kilowatt of loss should be provided. 
 

Do not stack Lineators or install above other 
heat source equipment. 

 
Enclosures are designed in accordance with 
NEMA and UL standards and can allow for 
installation in various environments.  Standard 
enclosures for the

 

Lineator™

 

are NEMA3R rated. 

 

For derating factors which apply to installations 
above 3000ft [1000m] refer to Section 7.5 Lineator 
Type Operational Curve. 

 

3.2 Inspection and Energization 

 

Upon receipt of shipment,  the

 

Lineator™

 

should 

be inspected for any damage incurred during 
shipment.  Before energization an internal 
inspection should be conducted with emphasis on 
loose or broken connections, damaged or 
displaced parts, cracked insulators, dirt or foreign 
material, or evidence of moisture.  While servicing 
the Lineator, all relevant safety standards must be 
followed, including all applicable  electrical codes 
and  NFPA 70E  –  Standard for Electrical Safety in 
the Workplace.   
 
3.2.1 

Before Energization 

 

 

Verify that the Lineator external feeder 
circuit breaker is in the OFF/OPEN 
position so that unit is de-energized. 

 

 

Check all bolts, nuts, screws, and 
connections for tightness and inspect for 
broken or damaged components or 
cables. 

 

Clean, vacuum, and clear interior of 
Lineator enclosure of any extra hardware 
and debris.  

 

Verify proper three-phase wiring of system 
power wires, ground, and feeder breaker. 

 

Check all capacitors for swelling, leaking, 
or extruded vents; replace if necessary. 
Verify all fuses for integrity and rating.  

 

If Lineator has been sitting idle for 6 
months or longer before first energization, 
it is recommended that the maintenance 
procedure described in 5.0 is performed 
prior to startup.  

 
3.2.2 

Initial Lineator start-up and run 

 

 

If test measurements are to be taken, 
connect any test equipment before 
energization.   

 

It is recommended that any test 
instruments be connected such that all 
enclosure panels can be installed properly 
and Lineator can be fully enclosed. 
Consider using meters with remote 
wireless displays if possible.   

 

When energizing, use appropriate 
personal protection equipment (PPE) and 
other precautions as required by NFPA 
70E. 

 

3.3 Handling 

 

The

 

Lineator™

 

should be thoroughly protected 

against the entrance of dust, rain or snow when 
handled outdoors.  
 
When lifting the  Lineator™

the lifting cables 

should be held apart by a spreader to avoid 
bending the lifting lugs or other parts of the 
structure.  To access the lifting  lugs, remove the 
top enclosure cover. The

 

Lineator™

 

may be 

skidded or  moved on rollers but care must be 
taken not to damage the base or tip it over.  When 
rollers are used under larger units, skids must be 
used to distribute the stress over the base. 
 
After  the

 

Lineator™

 

is placed in permanent 

position, shipping braces should be removed and 
shipping bolts, if present, should be loosened. 

Where isolation pads have been included, the 
bolt should be loosened until the spring 
washer has been relaxed before putting into 
service

.  This will reduce noise resulting from the

 

Lineator’s™

 

natural vibration

.  

Summary of Contents for LINEATOR

Page 1: ...MIRUS International Inc INSTALLATION OPERATION AND MAINTENANCE GUIDE THE LINEATOR ADVANCED UNIVERSAL HARMONIC FILTER AUHF AUHF M001 A15...

Page 2: ...nance of the LineatorTM AUHF and its auxiliary equipment WARNING OPENING ENCLOSURES EXPOSES HAZARDOUS VOLTAGES ALWAYS REFER SERVICE TO QUALIFIED PERSONNEL ONLY WARNING As standards specifications and...

Page 3: ...TER AUHF INSTALLATION OPERATION AND MAINTENANCE GUIDE AUHF M001 A15 14 Dec 2021 MIRUS International Inc 31 Sun Pac Blvd Brampton Ontario Canada L6S 5P6 1 888 TO MIRUS 1 888 866 4787 Tel 905 494 1120 F...

Page 4: ...on maintenance use or operation 3 Exclusive Remedy If the LINEATOR AUHF does not conform with the warranties set out above the Customer must notify MIRUS of the defective unit within the applicable wa...

Page 5: ...lation 2 3 1 Location 2 3 2 Inspection and Energization 2 3 3 Handling 2 3 4 Grounding 3 4 0 Storage 3 5 0 Maintenance 3 5 1 Periodic Inspection and Maintenance 3 5 2 Cleaning 4 5 3 Drying of Core and...

Page 6: ...AUHF M001 A15 v...

Page 7: ...ating the possibility of attracting harmonics from upstream non linear loads 2 3 System Resonance The natural resonance frequency of the Lineator is below that of any predominant harmonic therefore in...

Page 8: ...ectrical Safety in the Workplace 3 2 1 Before Energization Verify that the Lineator external feeder circuit breaker is in the OFF OPEN position so that unit is de energized Check all bolts nuts screws...

Page 9: ...rnal fuse as this pressure builds Capacitors should be inspected regularly and replaced when found to have an expanded cover 5 1 4 Even though they may appear fine physically capacitors may require re...

Page 10: ...or reactor before installation or after an extended shutdown under relatively high humidity conditions internal and or external heating methods can be used See ANSI IEEE C57 94 1982 for a description...

Page 11: ...as of rated kW 5 to 75HP 20 100HP 15 Efficiency 99 Elevation 3300ft 1000m above sea level Ambient Temperature 104 Deg F 40 Deg C Ventilation Convection air cooled Winding Material Copper Insulating Va...

Page 12: ...34 292 MT4 800 363 1006 456 MT4 780 354 1006 456 400 315 470 498 375 398 325 345 397 349 825 374 LT1 E 1031 467 805 365 LT1 E 1031 467 450 355 530 562 424 449 369 391 448 394 870 395 1076 488 870 395...

Page 13: ...46 SU4 345 156 434 197 150 110 388 411 353 374 204 216 187 198 143 125 553 251 627 285 365 166 MT3 E 469 213 175 132 241 255 221 234 166 148 MT3 390 177 492 223 200 150 274 290 250 265 191 168 415 189...

Page 14: ...250 185 350 300 250 425 400 300 220 450 350 300 560 500 350 250 500 400 350 630 630 400 315 600 500 400 710 710 500 400 700 600 500 900 800 600 450 800 700 600 1000 1000 700 500 1000 800 700 1250 100...

Page 15: ...LINEATOR Operation Maintenance Manual AUHF M001 A15 9 7 5 Lineator Type Operational Curve...

Page 16: ...06 18 00 457 14 25 362 20 00 508 18 00 457 SU4 SU4 E 40 00 1016 22 00 559 19 75 502 22 00 559 20 00 508 20 00 508 MT3 MT3 E 45 00 1143 26 00 661 21 00 534 25 00 635 21 50 546 19 00 483 MT4 MT4 E 51 50...

Page 17: ...ch fuseholder with power applied to the filter If voltage is not near 0 fuse is blown and should be replaced Make sure that fuse rating used is appropriate for capacitor size Check with the factory fo...

Page 18: ...NOTES...

Page 19: ...NOTES...

Page 20: ...US International Inc 31 Sun Pac Blvd Brampton Ontario Canada L6S 5P6 1 888 TO MIRUS 1 888 866 4787 Tel 905 494 1120 Fax 905 494 1140 E Mail mirus mirusinternational com Website www mirusinternational...

Reviews: