Mirus LINEATOR Installation, Operation And Maintenance Manual Download Page 1

MIRUS

 

International Inc.

 

INSTALLATION, 

OPERATION AND 

MAINTENANCE GUIDE

 

 

THE

 

LINEATOR

™  

ADVANCED UNIVERSAL HARMONIC FILTER (AUHF)

 

 

 

 

         
       
                                                
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

AUHF-M001-A15

 

 

Summary of Contents for LINEATOR

Page 1: ...MIRUS International Inc INSTALLATION OPERATION AND MAINTENANCE GUIDE THE LINEATOR ADVANCED UNIVERSAL HARMONIC FILTER AUHF AUHF M001 A15...

Page 2: ...nance of the LineatorTM AUHF and its auxiliary equipment WARNING OPENING ENCLOSURES EXPOSES HAZARDOUS VOLTAGES ALWAYS REFER SERVICE TO QUALIFIED PERSONNEL ONLY WARNING As standards specifications and...

Page 3: ...TER AUHF INSTALLATION OPERATION AND MAINTENANCE GUIDE AUHF M001 A15 14 Dec 2021 MIRUS International Inc 31 Sun Pac Blvd Brampton Ontario Canada L6S 5P6 1 888 TO MIRUS 1 888 866 4787 Tel 905 494 1120 F...

Page 4: ...on maintenance use or operation 3 Exclusive Remedy If the LINEATOR AUHF does not conform with the warranties set out above the Customer must notify MIRUS of the defective unit within the applicable wa...

Page 5: ...lation 2 3 1 Location 2 3 2 Inspection and Energization 2 3 3 Handling 2 3 4 Grounding 3 4 0 Storage 3 5 0 Maintenance 3 5 1 Periodic Inspection and Maintenance 3 5 2 Cleaning 4 5 3 Drying of Core and...

Page 6: ...AUHF M001 A15 v...

Page 7: ...ating the possibility of attracting harmonics from upstream non linear loads 2 3 System Resonance The natural resonance frequency of the Lineator is below that of any predominant harmonic therefore in...

Page 8: ...ectrical Safety in the Workplace 3 2 1 Before Energization Verify that the Lineator external feeder circuit breaker is in the OFF OPEN position so that unit is de energized Check all bolts nuts screws...

Page 9: ...rnal fuse as this pressure builds Capacitors should be inspected regularly and replaced when found to have an expanded cover 5 1 4 Even though they may appear fine physically capacitors may require re...

Page 10: ...or reactor before installation or after an extended shutdown under relatively high humidity conditions internal and or external heating methods can be used See ANSI IEEE C57 94 1982 for a description...

Page 11: ...as of rated kW 5 to 75HP 20 100HP 15 Efficiency 99 Elevation 3300ft 1000m above sea level Ambient Temperature 104 Deg F 40 Deg C Ventilation Convection air cooled Winding Material Copper Insulating Va...

Page 12: ...34 292 MT4 800 363 1006 456 MT4 780 354 1006 456 400 315 470 498 375 398 325 345 397 349 825 374 LT1 E 1031 467 805 365 LT1 E 1031 467 450 355 530 562 424 449 369 391 448 394 870 395 1076 488 870 395...

Page 13: ...46 SU4 345 156 434 197 150 110 388 411 353 374 204 216 187 198 143 125 553 251 627 285 365 166 MT3 E 469 213 175 132 241 255 221 234 166 148 MT3 390 177 492 223 200 150 274 290 250 265 191 168 415 189...

Page 14: ...250 185 350 300 250 425 400 300 220 450 350 300 560 500 350 250 500 400 350 630 630 400 315 600 500 400 710 710 500 400 700 600 500 900 800 600 450 800 700 600 1000 1000 700 500 1000 800 700 1250 100...

Page 15: ...LINEATOR Operation Maintenance Manual AUHF M001 A15 9 7 5 Lineator Type Operational Curve...

Page 16: ...06 18 00 457 14 25 362 20 00 508 18 00 457 SU4 SU4 E 40 00 1016 22 00 559 19 75 502 22 00 559 20 00 508 20 00 508 MT3 MT3 E 45 00 1143 26 00 661 21 00 534 25 00 635 21 50 546 19 00 483 MT4 MT4 E 51 50...

Page 17: ...ch fuseholder with power applied to the filter If voltage is not near 0 fuse is blown and should be replaced Make sure that fuse rating used is appropriate for capacitor size Check with the factory fo...

Page 18: ...NOTES...

Page 19: ...NOTES...

Page 20: ...US International Inc 31 Sun Pac Blvd Brampton Ontario Canada L6S 5P6 1 888 TO MIRUS 1 888 866 4787 Tel 905 494 1120 Fax 905 494 1140 E Mail mirus mirusinternational com Website www mirusinternational...

Reviews: